background image

PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY

5. After making sure the air charge is correct, replace the 1 1/2” plug over the 

air valve.

6. The  EXTROL

®

 may now be piped to the system (use the suggested 

EXTROL

®

 piping diagrams on the next page).

7. Using the table below, select appropriate pipe size. Connection to each 

EXTROL

®

 must have a lock shield gate valve and union to allow isolation and 

removal if required. Make up and fill valves, whether manual or automatic, 
should be tied into the connecting line. This will ensure that pump operation 
will not affect valve operation. 

Operational Limits

Maximum Operating Pressure: As stamped on nameplate
Maximum Operating Temperature: 240 °F
Minimum Operating Temperature: 35°F (non-glycol application)
If unit is being installed in a glycol system where minimum temperatures 
fall below 35°F, contact the AMTROL technical service department at (401) 
535-1216.

Operating Instructions

1. Check the expansion tank pre-charge before the system is filled with water. 

The charge is 12 psig unless noted otherwise on the tank label. Check to 
make sure this is the correct pre-charge pressure specified for the system.

2. If the tank pre-charge pressure needs to be changed on a dry system follow 

the following procedure:

  a.  Check the expansion tank air pressures at the pre-charge connection with 

an accurate tire type pressure gauge. The pre-charge connection is the same 
kind of connection found on automobile tires.

  b. If the pressure is low, charge the tank with nitrogen gas or with oil free 

compressed air. Check the pressure frequently during this process as you 
would when filling a tire with air.

Danger: Excessive pressure can cause tank to explode. Exercise 
care when filling a tank with air so the pressure does not exceed 
that required or does not exceed the working pressure of the 

tank as stamped on the nameplate. Failure to follow these instructions will 
result in serious personal injury or death and property damage.

3. If, after the system has been filled with water and operating, it is found that 

the expansion tank pre-charge must be changed use the following procedure:

  a.  Turn off the heat source and allow the system water to cool to ambient 

temperature.

  b.  Close the lock-shield valve in the tank-to-system piping. 

IMPORTANT: Expansion tank cannot be properly air charged 
other than at ambient temperature. 

  c.  Open the drain valve to empty the water from the tank.
  d.  Check the tank air pressure at the pre-charge connection with an accurate 

tire type air gauge. 

  e.  Refer to 2b above.
  f.  Close the drain valve, open the lock-shield valve and turn on the heat 

source.

  g.  Relock the lock-shield valve.

Potable Water and Radiant Heating Warning.  

This Product must not be used in radiant 

heating, potable water or open systems of any kind.  These systems 

contain oxygenated water which will cause internal corrosion and 

premature Product failure.  Use a Therm-X-Trol

®

 for potable water 

systems and a Radiant Extrol™ for radiant heating systems.  Mount 

vertically only.  Do not install on dead-end pipe.
IMPORTANT GENERAL SAFETY INFORMATION - ADDITIONAL 

SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING 

INSTRUCTIONS.
Note:  Inspect for shipping damage and notify freight carrier or 

store where purchased immediately if damage is present.  To avoid 

risk of personal injury and property damage, if the product appears 

to be malfunctioning or shows signs of corrosion, call a qualified 

professional immediately.  Current copies of the Product manual 

can be viewed at www.amtrol.com.  Use proper safety equipment 

when installing.

FAILURE TO PROPERLY SEAL WILL RESULT 

IN LOSS OF PRECHARGE CAUSING 

PRODUCT TO FAIL.

CALIFORNIA PROPOSITION 65 WARNING: 

This product contains a chemical known by 

the State of California to cause cancer and to cause birth defects or 

other reproductive harm. (California Installer/Contractor - California 

law requires that this notice be given to consumer/end user of this 

product.) For more information:  www.amtrol.com/prop65/htm.

  Firing Rate  

Length of Pipe Connecting

  of Boiler 

Tank to System:

  MBTU/H 

Below 11’ 

11’ – 30’ 

31’ – 100’

 2,000 

1/2” 

3/4” 

1”

 

4,000 

3/4” 

1” 

1 1/4”

 

8,000 

1” 

1 1/4” 

1 1/2”

 

12,000 

1 1/4” 

1 1/2” 

2”

 

16,000 

1 1/4” 

2” 

2 1/2”

 

20,000 

1 1/2” 

2” 

2 1/2”

EXPLOSION HAZARD. FAILURE TO FOLLOW INSTRUCTIONS IN THE ACCOMPANYING PRODUCT MANUAL CAN CAUSE RUPTURE 
OR EXPLOSION, POSSIBLY CAUSING SERIOUS OR FATAL INJURY, LEAKING OR FLOODING AND/OR PROPERTY DAMAGE.

Location of EXTROL

®

 Expansion Tanks

DO NOT LOCATE THIS PRODUCT WHERE 

LEAKING OR FLOODING COULD CAUSE DAMAGE 

TO THE SURROUNDING PROPERTY.

The AMTROL

®

 expansion tank may be placed in any convenient position within 

the mechanical room (or building). If multiple tanks are installed, they should all 

be on the same level. 

Point of Connection

Unlike a conventional tank, the EXTROL

®

 sealed air cushion does not require 

replenishment so DO NOT connect to an air separator or other air collection 

device. 

As with any expansion tank, it is recommended that the EXTROL

®

 be connected 

to the suction side of the pump. This will prevent the pump head from becoming 

subtractive which may result in entry of air and vapor formation at high points in 

the system. 

By connecting the EXTROL

®

 on the boiler return, displacement of coolest system 

water into tank is ensured reducing energy waste.

Low pressure drop components such as air separators and boilers may be placed 

between point of connection and pump suction if desired. System design will 

dictate the feasibility of this.

Natural convection losses and the entry of air into tanks are eliminated by 

connection to the side or underside of main pipe. The piping should be pitched up 

and away from the EXTROL

®

 to eliminate any potential air traps.

Installation

THIS PRODUCT MUST BE INSTALLED BY A 

QUALIFIED PROFESSIONAL.

1. Note location of system connection, air charge valve and drain connection on 

tank.

2. Remove the plug or pipe cap from the system connection.

3. Remove the 1 1/2” NPT plug covering the air charge valve.

4. Before making any connection to the tank, check the tank and air charge (use 

an accurate pressure gauge). The air pressure must be equal to the minimum 

system pressure at the tank location.

Отзывы: