A  diminished  temperature  difference  between 
the  boiler  water  entering  and  leaving  the  heat 
exchanger coil may indicate heat exchanger scale 
buildup.  Water  treatment  equipment  and  proper 
maintenance  will  help  to  avoid  this  problem.  To 
clean  a  scaled  heat  exchanger  coil  proceed  as 
follows:

1.  Shut  off  the  cold  water  supply  to  the 

BoilerMate

®

.

2.  Make a note of the temperature control setting 

on the BoilerMate

®

, then turn the unit off.

3.  Relieve  the  water  pressure  in  the  tank  by 

opening a hot water faucet. This will reduce the 
risk of scalding injury.

4.  Remove  the  relief  valve  from  the  top  of  the 

BoilerMate

®

, taking care to avoid contact with 

the  hot  water,  which  may  drain  out  of  the 
plumbing.

5.  Drain the BoilerMate

®

 until the water within the 

tank is even with the top of the heat exchanger 
- approximately 15 gallons for 41-gallons units 
and 5 gallons for 26-gallon units.

Do  not  over-drain  the  tank. 
Improper  thermostatic  control 

could result during Step 6 and lead to damage to 
the BoilerMate

®

.

6.  Using  a  funnel,  pour  one  gallon  of  non-

toxic  commercial  phosphoric  acid  solution 
(commercial  icemaking  cleaning  solution)  into 
the  water  tank  through  the  top  opening.  Be 
sure  that  the  manufacturer’s  directions  and 
warnings are followed.

-29-

15. CLEANING THE BOILERMATE

®

HEAT EXCHANGER COIL

7.  Set the temperature control to its highest setting and 

operate  the  unit  until  the  control  is  satisfied.  Note: 
Boiler may cycle on its high limit several times during 
this period. If the tank temperature setting has not been 
satisfied after 45 minutes of boiler operation, turn the 
BoilerMate

®

 control off to stop boiler operation.

8.  Allow  heated  solution  to  set  in  tank  for  30  minutes, 

then  drain  tank  completely  using  fitting  and  hose,  as 
required.

9.  Fill water tank with fresh, cold, conditioned water and 

drained completely at least two times or until drained 
water runs clear.

10.  Reinstall the safety relief valve.

11.  Open the cold water supply and fill the tank with water. 

Purge  plumbing  by  operating  all  hot  and  cold  water 
fixtures in the building.

12.  Return  the  control  to  the  setting  noted  in  Step  2  and 

verify that the unit is functioning properly.

 

As an alternative to the above, the teat exchange may 
be removed from the BoilerMate

®

 and cleaned. A new 

gasket must be installed whenever the heat exchanger 
is removed.

Содержание BoilerMate RTR

Страница 1: ...TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE The heat transfer medium m...

Страница 2: ...nd also adversely affect its performance M Wiring Options Select either a Non Priority or Priority System Two options are available when wiring the controls of the BOILERMATE in the space heating syst...

Страница 3: ...or not used Required WHS SERIES Commercial 10GPM 3 4 Full Port 4 1 Included See Therm X Trol Included Except P Models or 1 STD Sizing Guide ALL INSTALLATIONS REQUIRE TEFLON SEALING TAPE OR PIPE DOPE F...

Страница 4: ...lent is used BOILER PIPING 1 Plumb the circulator or zone valve on the BOILER SUPPLY line If using a separate circulator the pump flange can be mounted directly to the threaded pipe marked BOILER SUPP...

Страница 5: ...5 PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR...

Страница 6: ...e on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT plumbed to the suction side of any heating circulators This may require moving...

Страница 7: ...7 PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR...

Страница 8: ...are factory installed 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT plumbed to the suction side of any heating circulators This may require moving the he...

Страница 9: ...9 PIPING MODELS WITH PRE INSTALLED CIRCULATOR W INTEGRAL FLOW CHECK...

Страница 10: ...nted directly to the threaded pipe marked BOILER SUPPLY Alternately the circulator can be placed anywhere on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sur...

Страница 11: ...11 PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR...

Страница 12: ...the zone valve sensor contains a built in temperature offset to account for the time it takes the zone valve to fully close This results in potable water temperature that is representative of the Smar...

Страница 13: ...BOX PLACE A WIRE NUT OVER EACH WIRE NOT USED ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK HONEYWELL L8124 B D BOILERMATE CIRCULATOR L1 L2 L8124 B D B1 B2 C1 C2 2 1 B R B R W T T HIGH LIMIT LOW L...

Страница 14: ...MIT HONEYWELL L8148 J WITH 24 VOLT GAS VALVE BOILERMATE JUNCTION BOX PLACE A WIRE NUT OVER EACH WIRE NOT USED ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK BOILERMATE CIRCULATOR L1 L2 L8148J C1 C2...

Страница 15: ...A C 2 1 ZC ZR B2 B1 C2 C1 T T BOILERMATE CIRCULATOR PRIORITY WIRING HONEYWELL L8124 A C L1 L2 BOILERMATE JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK HEATING CIRCULATOR PRIORITY WIR...

Страница 16: ...ORITY WIRING HONEYWELL L8148B B R HIGH LIMIT BOILERMATE CIRCULATOR BOILERMATE JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK L1 L2 L2 L1 T T C1 C2 B1 B2 L8148B PRIORITY WIRING HONEYWEL...

Страница 17: ...S VALVE BOILERMATE CIRCULATOR BOILERMATE JUNCTION BOX PLACE A WIRE NUT OVER EACH WIRE NOT USED ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK TV W T TP Z B B1 B2 B3 L1 L2 C1 C2 8J48A HEATING CIRCUL...

Страница 18: ...OLET VIOLET BLACK WHITE L1 L2 120V Supply BoilerMate Circulator PLACE A WIRE NUT OVER EACH WIRE NOT USED Typical Multi Zone Relay 24V without Post Purge Feature T T X X Boiler Aquastat Zone Outputs Pr...

Страница 19: ...must be placed on a flat section of floor in an area where water will first collect If the level cannot reach 1 32 the alarm feature may not function Do not place in a high traffic area where the sens...

Страница 20: ...trol models select the appropriate diagram from the following pages If a suitable diagram is not available for your application please contact AMTROL Tech Support at 401 535 1216 Always disconnect pow...

Страница 21: ...oiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs Typical Multi Zone Relay BoilerMate Circulator BoilerMate Thermostat PRIORITY W CIRCULATORS SCHEMATIC 4 ZONE VALVES SCHEMATIC 3 3 WIR...

Страница 22: ...R 4 WIRE ZONE VALVE L1 L2 40VA 24 VOLT L1 L2 NOTE TAKE L1 AND L2 OFF THE BOILER CONTROL T T ON BOILER CONTROL END SWITCH MOTOR ORANGE 1 ORANGE BLUE BLUE VIOLET VIOLET BLACK WHITE SMART CONTROL JUNCTIO...

Страница 23: ...Support at 401 535 1216 Always disconnect power before wiring the unit Ensure that the proper conduit and connections are used per your local code In lieu of local code the National Electric Code sho...

Страница 24: ...X LIVE NEUT PR OUT PR IN 1 2 3 4 L1 L2 Indirect Aquastat L1 L2 B2 B HONEYWELL L8148J W MILLIVOLT GAS VALVE WHITE RODGERS 8J48A W 24V GAS VALVE CIRCULATOR RELAY BOX Indirect Aquastat L2 LIVE NEUT PR OU...

Страница 25: ...ar as hot water is used 3 START HEATER Turn power on to the unit Smart Control models come pre set at 120 F for safety Dial units should have the knob rotated to the 120 F mark The circulator and boil...

Страница 26: ...until n is displayed Pressing the MODE pushbutton a fifth time will cause to be displayed and releasing the MODE pushbutton will cause 41 to be displayed This is the tank volume in gallons To change t...

Страница 27: ...at exchanger as outlined below Install water treatment equipment to prevent recurrence 5 Check for undersized or faulty circulator stuck or undersized zone valve Ensure all shutoff valves are open Che...

Страница 28: ...tom Drain O Ring 2500 178 2500 178 2500 178 2500 178 N A N A N A N A Smart Control 2704A233 2704A233 2704A233 2704A233 2704A233 2704A233 N A N A Sensor thermistor wire 2704 259 2704 259 2704 259 2704...

Страница 29: ...phosphoric acid solution commercial icemaking cleaning solution into the water tank through the top opening Be sure that the manufacturer s directions and warnings are followed 29 15 CLEANING THE BOI...

Страница 30: ...en to prevent pressure build up Electrocution hazard The BoilerMate must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to pre...

Страница 31: ...31...

Страница 32: ...West Warwick Rhode Island 02893 Part 9040 586 07 08 Boiler Mate AMTROL AMTROL logo Therm X Trol Radiant EXTROL and EXTROL are registered trademarks of AMTROL Inc and affiliates All rights reserved...

Отзывы: