background image

-2-

1. TABLE OF CONTENTS

2.  Pre-Installation Checklist .................................................

2

3.  Required Components and Accessories Checklist .........

3

4.  WH-7 & 9 Classic Series Piping Installation ....................

4

5.  Top Down™ TD-Series Piping Installation ......................

6

6.  Ready-To-Run RTR-Series Piping Installation ................

8

7.  WHS Premier Series Piping Installation ........................

10

8.  Wiring All Smart Control™ Models ...............................

12

9.  Wiring All Dial Control Models 

(Except RTR Models)

 .........

20

10. Wiring All Ready-To-Run (RTR) Models .......................

23

11. Startup Procedure For All Models ................................

25

12. Setting the Smart Control™ ..........................................

26

13. Troubleshooting .............................................................

27

14. Replacement Parts ........................................................

28

15. Cleaning the BoilerMate

®

 Heat Exchanger ...................

29

16. General Safety Information ...........................................

30

2. PRE-INSTALLATION CHECKLIST

IMPORTANT STEPS AND DECISIONS REQUIRED BEFORE INSTALLATION

M

  THIS  PRODUCT  MUST  BE  INSTALLED  AND 

MAINTAINED  BY  A  LICENSED  PROFESSIONAL.  IN 

ADDITION  TO  THE  INSTRUCTIONS  IN  THIS  MANUAL, 

FOLLOW ALL APPLICABLE LOCAL AND STATE CODES 

OR IN THE ABSENCE OF SUCH CODES, THE CURRENT 

EDITIONS  OF  THE  NATIONAL  PLUMBING  CODE  AND 

THE NATIONAL ELECTRIC CODE.

M

  DRIP  PAN  AND  DRAIN:  This  appliance  should  not 

be  installed  in  an  area  where  leakage  of  the  tank  or 

connections can result in damage to the area adjacent 

to  the  appliance  or  to  lower  floors  of  the  structure. 

When  such  locations  cannot  be  avoided,  a  suitable 

drain pan, adequately drained and kept clear, must be 

installed under the appliance.

M

  CAUTION:  Determine  whether  your  water  is  corrosive 

or  acidic,  and  that  there  are  no  suspended  solids, 

toxic  or  other  substances  or  abnormally  high  chlorine 

levels  in  the  water  that  could  damage  or  affect  the 

BOILERMATE

®

 or the rest of your plumbing system.

USE 

GLYCOL 

ONLY 

WITH 

DOUBLE-WALLED HEAT EXCHANGER 

MODELS. Glycol is a hazardous substance. To avoid 

seepage  or  leakage  of  glycol  to  surfaces  where 

humans  or  animals  can  ingest  it,  use  glycol  only  in 

double-walled units, so that any leaks will most likely 

be released to the atmosphere.  However, a leak to a 

surface area may still occur, so any use of glycol must 

be monitored closely and humans and animals should 

be protected from contact with the unit.

Do  not  connect  the  BOILERMATE

®

 

domestic  supply  with  baseboard 

or  other  space  heating  units  or  elements.  Any 

contaminants in the baseboard units will contaminate 

the  potable  water  in  the  BOILERMATE

®

  and  also 

adversely affect its performance.

M

  Wiring Options. Select either a Non-Priority or Priority 

System:

Two options are available when wiring the controls of the 

BOILERMATE

®

  in  the  space  heating  system  (boiler  and 

distribution elements).

1.  Non-Priority  System  -  The  controls  of  the 

BOILERMATE

®

 must be wired as a separate heating 

zone  with  a  standard  zone  valve  or  a  separate 

circulator dedicated to the BOILERMATE

®

 “zone”.

NOTICE:  In  this  non-priority  option,  the  BOILERMATE

®

 

will be supplied just as another zone. This means that if all 

space heating zones call for hot boiler water at the same 

time, the BOILERMATE

®

 may not be supplied with enough 

hot  boiler  water  to  “recover”  adequately.  The  delivery  of 

domestic hot water will be diminished. In many, but not all 

cases, this is not a problem because the routine oversizing 

of boiler output is adequate for both loads.

2. Priority  System  -  Under  this  wiring  option  the 

BOILERMATE

®

 will be supplied before space heating.

In  limited  circumstances,  space 

heating can be lost in the home in 

this  priority  mode.  Any  demand  for  space  heating  is 

postponed until the BOILERMATE

®

 has reached its set 

temperature.  This delay in supplying the space heating 

zones  is  usually  not  noticed  by  the  inhabitants  of  the 

living  spaces.    However,  in  the  event  of  certain 

malfunctions  such  as  circulator  or  thermostat  failure, 

space  heating  could  be  delayed  indefinitely.  If 

undetected and uncorrected, freezing damage to piping 

could result.

Select Circulator versus Zone Valve

  The  flow  of  hot  boiler  water  to  the  BOILERMATE

®

 

can 

be  controlled  with  either  a  motorized  zone  valve  or  a 

circulator.

1. Separate  circulator.    The  recommended  way  to 

provide  adequate  flow  through  the  BOILERMATE

®

 

heat  exchanger  is  to  use  a  separate  dedicated 

circulator with a minimum flow rate of 5 gpm.  This 

option may be used even though the heating system 

utilizes zone valves.

2. Zone valve (system flow of 4-8 gpm).  If a zone valve 

is to be used, a minimum flow rate of 5 gpm with all 

zones in use is required. A full-port zone valve should 

be used.

All installations require a low-water cut-off or automatic fill 

valve on your boiler system to reduce the risk of boiler water 

loss. 

Steam boiler installations require a low-water cut-off which 

is also required by most codes.

Installation  of  a  vacuum  breaker  is  required  to  prevent 

damage  to  the  BOILERMATE

®

  when  drained.  There  must 

be  no  valves  installed  between  the  vacuum  breaker  and 

BOILEMATE

®

.

Содержание BoilerMate RTR

Страница 1: ...TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE The heat transfer medium m...

Страница 2: ...nd also adversely affect its performance M Wiring Options Select either a Non Priority or Priority System Two options are available when wiring the controls of the BOILERMATE in the space heating syst...

Страница 3: ...or not used Required WHS SERIES Commercial 10GPM 3 4 Full Port 4 1 Included See Therm X Trol Included Except P Models or 1 STD Sizing Guide ALL INSTALLATIONS REQUIRE TEFLON SEALING TAPE OR PIPE DOPE F...

Страница 4: ...lent is used BOILER PIPING 1 Plumb the circulator or zone valve on the BOILER SUPPLY line If using a separate circulator the pump flange can be mounted directly to the threaded pipe marked BOILER SUPP...

Страница 5: ...5 PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR...

Страница 6: ...e on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT plumbed to the suction side of any heating circulators This may require moving...

Страница 7: ...7 PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR...

Страница 8: ...are factory installed 2 Pipe the BOILER RETURN connection to the boiler return line Be sure the return line is NOT plumbed to the suction side of any heating circulators This may require moving the he...

Страница 9: ...9 PIPING MODELS WITH PRE INSTALLED CIRCULATOR W INTEGRAL FLOW CHECK...

Страница 10: ...nted directly to the threaded pipe marked BOILER SUPPLY Alternately the circulator can be placed anywhere on the boiler supply line 2 Pipe the BOILER RETURN connection to the boiler return line Be sur...

Страница 11: ...11 PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR...

Страница 12: ...the zone valve sensor contains a built in temperature offset to account for the time it takes the zone valve to fully close This results in potable water temperature that is representative of the Smar...

Страница 13: ...BOX PLACE A WIRE NUT OVER EACH WIRE NOT USED ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK HONEYWELL L8124 B D BOILERMATE CIRCULATOR L1 L2 L8124 B D B1 B2 C1 C2 2 1 B R B R W T T HIGH LIMIT LOW L...

Страница 14: ...MIT HONEYWELL L8148 J WITH 24 VOLT GAS VALVE BOILERMATE JUNCTION BOX PLACE A WIRE NUT OVER EACH WIRE NOT USED ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK BOILERMATE CIRCULATOR L1 L2 L8148J C1 C2...

Страница 15: ...A C 2 1 ZC ZR B2 B1 C2 C1 T T BOILERMATE CIRCULATOR PRIORITY WIRING HONEYWELL L8124 A C L1 L2 BOILERMATE JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK HEATING CIRCULATOR PRIORITY WIR...

Страница 16: ...ORITY WIRING HONEYWELL L8148B B R HIGH LIMIT BOILERMATE CIRCULATOR BOILERMATE JUNCTION BOX ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK L1 L2 L2 L1 T T C1 C2 B1 B2 L8148B PRIORITY WIRING HONEYWEL...

Страница 17: ...S VALVE BOILERMATE CIRCULATOR BOILERMATE JUNCTION BOX PLACE A WIRE NUT OVER EACH WIRE NOT USED ORANGE ORANGE BLUE BLUE VIOLET VIOLET WHITE BLACK TV W T TP Z B B1 B2 B3 L1 L2 C1 C2 8J48A HEATING CIRCUL...

Страница 18: ...OLET VIOLET BLACK WHITE L1 L2 120V Supply BoilerMate Circulator PLACE A WIRE NUT OVER EACH WIRE NOT USED Typical Multi Zone Relay 24V without Post Purge Feature T T X X Boiler Aquastat Zone Outputs Pr...

Страница 19: ...must be placed on a flat section of floor in an area where water will first collect If the level cannot reach 1 32 the alarm feature may not function Do not place in a high traffic area where the sens...

Страница 20: ...trol models select the appropriate diagram from the following pages If a suitable diagram is not available for your application please contact AMTROL Tech Support at 401 535 1216 Always disconnect pow...

Страница 21: ...oiler Aquastat Zone Outputs Priority or DHW Zone Thermostat Inputs Typical Multi Zone Relay BoilerMate Circulator BoilerMate Thermostat PRIORITY W CIRCULATORS SCHEMATIC 4 ZONE VALVES SCHEMATIC 3 3 WIR...

Страница 22: ...R 4 WIRE ZONE VALVE L1 L2 40VA 24 VOLT L1 L2 NOTE TAKE L1 AND L2 OFF THE BOILER CONTROL T T ON BOILER CONTROL END SWITCH MOTOR ORANGE 1 ORANGE BLUE BLUE VIOLET VIOLET BLACK WHITE SMART CONTROL JUNCTIO...

Страница 23: ...Support at 401 535 1216 Always disconnect power before wiring the unit Ensure that the proper conduit and connections are used per your local code In lieu of local code the National Electric Code sho...

Страница 24: ...X LIVE NEUT PR OUT PR IN 1 2 3 4 L1 L2 Indirect Aquastat L1 L2 B2 B HONEYWELL L8148J W MILLIVOLT GAS VALVE WHITE RODGERS 8J48A W 24V GAS VALVE CIRCULATOR RELAY BOX Indirect Aquastat L2 LIVE NEUT PR OU...

Страница 25: ...ar as hot water is used 3 START HEATER Turn power on to the unit Smart Control models come pre set at 120 F for safety Dial units should have the knob rotated to the 120 F mark The circulator and boil...

Страница 26: ...until n is displayed Pressing the MODE pushbutton a fifth time will cause to be displayed and releasing the MODE pushbutton will cause 41 to be displayed This is the tank volume in gallons To change t...

Страница 27: ...at exchanger as outlined below Install water treatment equipment to prevent recurrence 5 Check for undersized or faulty circulator stuck or undersized zone valve Ensure all shutoff valves are open Che...

Страница 28: ...tom Drain O Ring 2500 178 2500 178 2500 178 2500 178 N A N A N A N A Smart Control 2704A233 2704A233 2704A233 2704A233 2704A233 2704A233 N A N A Sensor thermistor wire 2704 259 2704 259 2704 259 2704...

Страница 29: ...phosphoric acid solution commercial icemaking cleaning solution into the water tank through the top opening Be sure that the manufacturer s directions and warnings are followed 29 15 CLEANING THE BOI...

Страница 30: ...en to prevent pressure build up Electrocution hazard The BoilerMate must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to pre...

Страница 31: ...31...

Страница 32: ...West Warwick Rhode Island 02893 Part 9040 586 07 08 Boiler Mate AMTROL AMTROL logo Therm X Trol Radiant EXTROL and EXTROL are registered trademarks of AMTROL Inc and affiliates All rights reserved...