Only recent 9 groups of the alarming record can be stored in memory of
A
i
205-P2 or -P3. The format of the record is,
When the alarming parameter resume normal (no longer over the limit), it is
also recorded. User can get the total period of over limit time.
Note: when the alarming parameter resume to normal, the highest bit of Var
bit15 is set to be 1.
Energy pulse output:
The two digital outputs (DO) can be select as energy
pulse output. Any two of the 8 energy and reactive energy can be assigned to be
as the pulse output. The pulse width and pulse ratio can be set, while pulse width
means how long the duration of the pulse is and pulse ratio means how much
energy that one pulse is represented. When the energy accumulates to the setting
limit, there will be a pulse output from the assigned DO port.
Pulse output assignment register: any integer from 0 to 8. The digit 0 means
no assignment, while 1 to 8 corresponding to Ep_imp, Ep_exp, Eq_imp, Eq_exp,
Ep_total, Ep_net, Eq_total and Eq_net respectively.
59
Address
Alarming record addr
Addr +1
Addr +2
Addr+3
Addr+4
Addr+5
Addr+6
Addr+7
Table3.4 Alarm record
Content
Alarming parameter number: Var
Alarming value
Year
Month
Date
Hour
Minute
Second
Remark
Refer to Table3.3
Record the value of alarming
parameter
Alarming date
Alarming time
PDF created with FinePrint pdfFactory trial version
http://www.pdffactory.com
Содержание Ai205
Страница 1: ......
Страница 12: ...Chapter 2 Installation Appearance and Dimensions Installation method Wiring of Ai205 7 ...
Страница 26: ...3 2LN 2CT 4 2LN 1CT 5 2LL 3CT 21 Fig 2 20 2LN 2CT Fig 2 21 2LN 1CT Fig 2 22 2LL 3CT ...
Страница 66: ...Introducing Modbus Protocol Format of Communication Data Address Table 61 Chapter 4 Communication ...
Страница 98: ...Appendix Appendix A Technical data and specifications Appendix B Ordering 93 ...
Страница 103: ......