12
Amphenol Network Solutions
All rights reserved. 12.16.19 138661-5 A0
509.926.6000 – amphenol-ns.com
Dual-Feed 350A 6-Circuit
Breaker/TFD Distribution
Panel with 5 GMTs
•
Expect an open circuit (
∞
Ω)
between Terminals
C
and
NC
.
•
Expect continuity (0
Ω
) between Terminals
C
and
NO
.
Re-install the operable GMT fuse before proceeding.
38. Record circuit assignments in accordance with operating company procedures and guidelines.
The manufacturer’s designation card, shown below, is a 10-in. (254 mm) by 2
1
/
4
-in. (57 mm) card that folds in half to
fit a card holder located to the right of the status LEDs.
39. Re-install the terminal cover.
40. Lastly, enable equipment loads one at a time to verify the proper operation of loads.
41. This procedure is complete.
NOTE: For service or warranty, see our amphenol-ns.com website and click on the “Support” tab, email inquiries to
[email protected] or phone us at 1.509.926.6000.
SIDE A
POS AMP
FUSE TYPE
DESCRIPTION
DESCRIPTION
POS AMP
RACK/BAY #
SIDE B
POS AMP
FUSE TYPE
DESCRIPTION
DESCRIPTION
RACK/BAY #
POS AMP
Fig. 11: Designation Card