Dual-Feed 350A 6-Circuit 

Breaker/TFD Distribution 

Panel with 5 GMTs

 

 
 

ALERT! Only use components and crimping tools 

approved by agencies or certifying bodies 

recognized in your country or region such as 

Underwriter’s Laboratories (UL), TUV, etc.  
 

6.  Use a listed (approved) crimping tool to attach a 

listed (approved), dual-hole compression lug onto 

suitable ground wire. (The size of the ground 

depends on the input interruption device.) 

7.  If required, lightly coat an antioxidant on the lug 

and grounding surface on the rear of the panel.  

8.  Connect using 

1

/

4

-20 hex nuts and flat washers 

provided, as shown in Figure 4.  

9.  Tighten the bolt to 25 in-lb. (2.83 N

m), max.  

 
 

WARNING! Before connecting input power cables,  

make sure input power to panel is turned off.  

10. Make sure the input power is off (open breaker,  

dummy fuse or open fuse holder at primary power 

distribution unit or battery) before connecting this 

panel’s input cables to the PDU or battery.  

11. For input wiring — wiring used as inputs to this 

load center — crimp dual-hole compression 

lugs onto #1-AWG to 750-MCM copper wires.  

The choice of input wiring depends on the 

following criteria:  

  The input interrupt device rating affects the 

size of the input wiring.  

  Ambient operating temperature affects the 

type of input wire insulation. For further  

information consult the National 

Electrical Code (NEC).  

 
 
 
 
 

 
 

Fig. 4: Ground to Chassis 

Содержание Telect 350CB06

Страница 1: ...Dual Feed 350A 6 Circuit Breaker TFD Distribution Panel with 5 GMTs Installation Guide...

Страница 2: ...rer that serves the data and communications markets We design manufacture and distribute products for customers who need an end to end solution for network connectivity fiber power distribution and ra...

Страница 3: ...ion 5 1 5 Installation 5 1 6 Parts Accessories 13 1 7 Schematic Drawing 15 1 8 Drawings 16 List of Figures Figure 1 350CB06 Distribution Panel 1 Figure 2 Bracket Orientation 5 Figure 3 Rack Mounting 6...

Страница 4: ...cuit breakers up to 100A rated continuous current 80 of rated This panel ships with solid covers over the circuit breaker TFD positions and with fuse slot fillers in the GMT holders Sides A and B are...

Страница 5: ...ow required for safe operation of the equipment is not compromised Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mech...

Страница 6: ...n or 15 mm wrench to 140 in lb 15 5 N m Input wire size 1 AWG to 750 MCM Breaker Fuse Outputs Specifications Max output single pole long delay circuit breaker ea 100A Max output TFD holder schematic C...

Страница 7: ...thority responsible for the location Only qualified technicians may install and maintain this product Grounding Specifications Earth GND terminal studs for dual hole compression lugs 1 4 20 studs on 5...

Страница 8: ...lly unpack it and compare it to the packaging list Please report any defective or missing parts to Amphenol Network Solutions Quality at quality amphenol ns com or call 1 509 926 6000 Amphenol Network...

Страница 9: ...t the panel as high as possible on the rack 3 Tighten the screws to 35 in lb 4 29 N m If you intend on installing more than one panel per rack you need to plan a rack arrangement that dissipates heat...

Страница 10: ...nnect using 1 4 20 hex nuts and flat washers provided as shown in Figure 4 9 Tighten the bolt to 25 in lb 2 83 N m max WARNING Before connecting input power cables make sure input power to panel is tu...

Страница 11: ...Enable the fuse or breaker at the primary distribution unit or battery 440A max to turn on Feed A to Side A of the panel and then check the voltage and polarity at input connectors of panel Also chec...

Страница 12: ...t wire at a time 24 Insulate lug barrels with UL 94V 0 rated heat shrink tubing 25 Clean panel terminals and lugs with a nonabrasive nonmetallic pad 26 If required lightly coat antioxidant on the lugs...

Страница 13: ...r end of the output wire to load ALERT GMT fuses have a small inherent electrical resistance resulting in a small inherent power loss For this reason GMT fuse manufacturer recommends that the load for...

Страница 14: ...itions between breakers Install the GMT fuses so that the failure indicator flags are at the top 36 Do one of the following Switch breakers to ON Install fuses Then test power and polarity at input of...

Страница 15: ...er s designation card shown below is a 10 in 254 mm by 2 1 4 in 57 mm card that folds in half to fit a card holder located to the right of the status LEDs 39 Re install the terminal cover 40 Lastly en...

Страница 16: ...0 amp long delay 090 0052 0020 30 amp long delay 090 0052 0030 40 amp long delay 090 0052 0040 50 amp long delay 090 0052 0050 60 amp long delay 090 0052 0060 70 amp long delay 090 0052 0070 80 amp lo...

Страница 17: ...8 40A 130482 50A 130484 60A 130486 70A 130488 Table 3 GMT Fuses Item Description Part Number of Fuse Part Number of Colored Designation Pin GMT Fuses 18A Yellow YEL 130781 102435 21 25A Violet VIO 100...

Страница 18: ...al Feed 350A 6 Circuit Breaker TFD Distribution Panel with 5 GMTs 1 7 Schematic Drawing BATT BATT BATT BATT RTN RTN RTN RTN A Input B Input C GND C GND Note Relays shown in alarm condition POWER ALARM...

Страница 19: ...olutions All rights reserved 12 16 19 138661 5 A0 509 926 6000 amphenol ns com Dual Feed 350A 6 Circuit Breaker TFD Distribution Panel with 5 GMTs 1 8 Drawings Front View 19 000 17 250 4 970 Top View...

Отзывы: