DNET-IP2 USER MANUAL ISSUE 4
-12-
Modbus
Word
IP
Byte
Description
24 27
Short Circuit Setting
(SHORT_CCT_PARAM)
SC I Trip Mult
1 = 3.0
2 = 3.5
3 = 4.0
4 = 4.5
5 = 5.0
6 = 5.5
7 = 6.0
8 = 6.5
9 = 7.0
10
=
7.5
11
=
8.0
12
=
8.5
13
=
9.0
14
=
9.5
15
=
10.0
25 28
Short Circuit Trip Time Setting
(SC_TRP_TM_PARAM)
SC Trip Time – mS
1 = 20
2 = 40
3 = 60
4 = 80
5 = 100
6 = 20
7 = 160
26 29
Short Circuit Output Relay Selection
(SC_OUT_PARAM)
SC Relay)
1 = CBR
2 = MCR
27 30
Earth Leakage Sensitivity Setting
(EL_SENS)
EL Sens – mA
1 = 100
2 = 150
3 = 200
4 = 250
5 = 300
6 = 350
7 = 400
8 = 450
9 = 500
Modbus
Word
IP
Byte
Description
28 31
Earth Leakage Trip time Setting
(EL_TIME)
EL Time – mS
1 = ins
2 = 150
3 = 190
4 = 230
5 = 270
6 = 310
7 = 350
8 = 390
9 = 430
10
=
470
29 32
Pilot Mode Selection
(PILOT MODE)
Pilot Type
1 = RTU
2 =
⏐
>⏐
-
30 33
CCM Selection
(VOLTS_SELECT)
(EFLO: CCM Volts
1 = C415
2 = C1k
3 = C3k3
4 = A415
5 = A1k
6 = A3k3
7 = A110
8 = None
31 34
Back EMF Timer Selection
(B_EMF_TIME)
B emf Time – Sec
1 = 2
2 = 5
3 = 10
4 = 15
5 = 20
32 35
Insulation Test Trip Setting
(MEG_LEVEL)
Ins. TstT - M
Ω
1 = 0.1
2 = 0.2
3 = 0.5
4 = 1.0
5 = 2.0
6 = 5.0
7 = 10
8 = 15
9 = None
Содержание DNET-IP2
Страница 29: ......
Страница 30: ......
Страница 31: ......
Страница 32: ......
Страница 33: ......
Страница 34: ......
Страница 35: ......
Страница 36: ......
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......