DNET-IP2 USER MANUAL ISSUE 4
-16-
Modbus
Word
IP
Byte
Description
18 21
Current Range Setting
(CUR_RANGE PARAM)
OC I Range A
1 = 60
2 = 64
3 = 68
4 = 72
5 = 76
6 = 80
7 = 84
8 = 88
9 = 92
10 = 96
11 = 100
12 = 104
13 = 108
14 = 112
15 = 116
19 22
Current Multiplier Setting
(CUR_MUL_PARAM)
OC I Mult
1 = 1/8
2 = ¼
3 = ½
4 = 1
5 = 2
6 = 4
20 23
Over Current Curve Setting
(OC_CURVE_PARM)
Curve Type
1 = Vinv
2
=
m-OL
Modbus
Word
IP
Byte
Description
21 24
Over Current Time Multiplier
(TIME_MULT_PARM)
OC Time Multiplier
1 = 0.05
2 = 0.075
3 = 0.1
4 = 0.15
5 = 0.2
6 = 0.3
7 = 0.4
8 = 0.5
9 = 0.6
10
=
0.7
11
=
0.9
12
=
1.0
13
=
0.04
14
=
0.03
15
=
0.02
16
=
0.015
17
=
0.01
18
=
0.005
22 25
Cool Multiplier Setting
(COOL_MUL_PARAM)
Cool Mult
1 = 0.2
2 = 0.3
3 = 0.4
4 = 0.5
5 = 0.8
6 = 1.0
7 = 2.0
8 = 5.0
9 = 10
10
=
20
11
=
50
23 26
Current Balance Setting
(CUR_BAL_PARAM)
Cur Bal Trip%
1 = 5
2 = 10
3 = 20
4 = 50
5 = Off