![Ampair IntesisBox Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/ampair/intesisbox/intesisbox_user-manual_2934139010.webp)
IntesisBox
®
Modbus Server – Mitsubishi Heavy Industries AC
User’s Manual r1.0 eng
© Intesis Software S.L. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SL
URL
Email
tel
http://www.intesis.com
[email protected]
+34 938047134
10 / 26
Indoor unit
number
Modbus address
(base addr is 1)
Modbus
register type
(R/W)
Signal description and values
…
…
…
…
n*
( n*) x 20 +
1
R
Communication Status
( n*) x 20 +
2
R/W
Indoor Unit On/Off
( n*) x 20 +
3
R/W
Operation Mode
( n*) x 20 +
4
R/W
SetPoint Temperature
( n*) x 20 +
5
R/W
Fan Speed
( n*) x 20 +
6
R/W
Remote Controller Lock/Unlock
( n*) x 20 +
7
R/W
Louver Control
( n*) x 20 +
8
R
Room Temperature
( n*) x 20 +
9
R
Filter Sign status
( n*) x 20 +
10
R
Indoor Unit Error Code
( n*) x 20 +
11
R
Compressor Status
( n*) x 20 +
12
W
Filter Sign Reset
( n*) x 20 +
13
W
Remote Control Error Reset
( n*) x 20 +
14
R
Thermo Status (Inverter Type Only)
…
…
…
…
127
(max number of
supported indoor
units depends on
IntesisBox model)
2541
R
Communication Status
2542
R/W
Indoor Unit On/Off
2543
R/W
Operation Mode
2544
R/W
SetPoint Temperature
2545
R/W
Fan Speed
2546
R/W
Remote Controller Lock/Unlock
2547
R/W
Louver Control
2548
R
Room Temperature
2549
R
Filter Sign status
2550
R
Indoor Unit Error Code
2551
R
Compressor Status
2552
W
Filter Sign Reset
2553
W
Remote Control Error Reset
2554
R
Thermo Status (Inverter Type Only)
*n is the indoor unit address number.
2.5.3
Modbus addresses related to ALL indoor units
Indoor unit
number
Modbus address
(base addr is 1)
Modbus register
type (R/W)
Signal description and values
ALL
2996
W
All Indoor Units On/Off
0: Off
1: On
2997
W
All Indoor Units Operation Mode
0: Cool
1: Heat
2: Fan
3: Auto
4: Dry
2998
W
All Indoor Units SetPoint Temperature
Celsius value (16ºC to 30ºC)
2999
W
All Indoor Units Fan Speed
0: Low
1: Medium
2: High
3: Powerful
3000
W
All Indoor Units Remote Controller Lock/Unlock
0: Remote Controller Locked
1: Remote Controller Unlocked
AMP Air Conditioning
www.ampair.co.uk | [email protected]