B. Equipment storage and installation requirements.
The equipment should be stored or installed in a shady, normal
temperature, ventilated and dry place.
C
.
SPECIFICATIONS OF CONCRETE
Specifications of concrete must be adhered to the specification as following.
Failure to do so may result in lift and/or vehicle falling.
1
.
Concrete must be thickness
4’’
mm minimum and without reinforcing steel bars
,
and must be dried completely before the installation.
2
.
Concrete must be in good condition and must be of test strength 3,000psi
(210kg/cm²) minimum.
3
.
Floors must be level and no cracks.
D
.
POWER SUPPLY
The electrical source must be 2.0HP minimum. The source cable size must be
2.5mm² and in good condition of contacting with floor.
III. STEPS OF INSTALLATION
A. Location of Installation
Check and insure the installation location (concrete, layout, space size etc.) is
suitable for lift installation.
1. For Standard Installation: On surface installation
1.1 On surface installation foundation
(See Fig. 3)
.
Fig. 3