A6 Quick Start: Hart
CAUTION
Copyright
©
2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-014 * Rev. B, 06/16
Page 18 of 21
AMFLOW
®
Step 4
VERY SLOWLY open Outlet Isolation Valve.
Step 5
VERY SLOWLY open Inlet Isolation Valve.
This allows fluid to be introduced gradually.
Once
Amflow
®
valve has been filled with fluid, there is little risk of
damage.
Step 6
Allow sufficient time for media to flush any trapped air out of valve.
Step 6
Once all air is eliminated, begin system operation.
Step 7
Turn valve adjustment handle to ensure that it turns easily.
WARRANTY
Amflow
®
warranty does not cover
Amflow
®
valves if proper chemical filtration is
not provided. Reference full warranty at back of Installation and Service Manual
provided with your
Amflow
®
product.
PROCEED with CAUTION
This is very important, especially at high system pressures to prevent potential
damage to seals and other internal components of valve.
IMPORTANT
:
On valves that are configured to meter less that 10 liters per hour it is very important
that at least 20 minutes be allowed for this step.
Trapped air can cause the set flow rate of valve to diminish slowly.