DC Asterion Series
Overview
M330460-01 Rev A
2-15
recommendations are for 30
°
C ambient, and for copper wire only. This table is derived
from the National Electrical Code and is for reference only. Local laws and conditions
may have different requirements. For higher ratings, wires can be paralleled; refer to
the National Electrical Code for guidelines.
Size
Temperature Rating of Copper Conductor
AWG
60°C
75°C
90°C
Types: TW, UF
Types: RHW,
THHW, THW,
THWN, XHHW,
USE, ZW
Types: TBS, SA,
SIS, FEP, FEPB,
MI, RHH, THHN,
THHW, XHH,
XHHW
Current Rating, A(RMS)
18
−
−
14
16
−
−
18
14
15
20
25
12
20
25
30
10
30
35
40
8
40
50
55
6
55
65
75
4
70
85
95
3
85
100
115
2
95
115
130
1
110
130
145
0
125
150
170
00
145
175
195
000
165
200
225
0000
195
230
260
Table 2-7. Minimum Wire Size
When determining the optimum cable specification for your power applications, the
same engineering rules apply whether at the input or output of an electrical device.
Therefore, this guide applies equally to the input cable and output cable for this power
source and application loads.
Power cables must be able to safely carry maximum load current without overheating
or causing insulation degradation. It is important to power source performance to
minimize IR (voltage drop) loss within the cable. These losses have a direct effect on
the quality of power delivered to and from the power source and corresponding loads.
When specifying wire gauge, consider derating due to operating temperature at the
wire location. Wire gauge current capability and insulation performance drops with the
increased temperature developed within a cable bundle and with increased
environmental temperature. Therefore, short cables with derating of gauge size and
insulation properties are recommended for power source applications.
Содержание Sorensen Asterion AST Series
Страница 1: ...M330460 01 Rev A www powerandtest com DC Asterion 1U Operation Manual ...
Страница 2: ......
Страница 26: ......
Страница 53: ...DC Asterion Series Overview M330460 01 Rev A 2 27 This page intentionally left blank ...
Страница 54: ......
Страница 109: ...DC Asterion Series Overview M330460 01 Rev A 3 55 This page intentionally left blank ...
Страница 110: ......
Страница 112: ......
Страница 117: ...DC Asterion Series Index M330460 01 Rev A 3 ...
Страница 118: ...Maintenance DC Asterion Series 4 M330460 01 Rev A This page intentionally left blank ...