Overview
DC Asterion Series
3-54
M330460-01 Rev A
2.
Remote sensing
at the load
should
not
be used during series operation. Each
power supply should have its remote sense leads connected to its own output
terminals.
3.
An anti-parallel diode (power diode capable of the maximum current of the series
group, connected across the output, but reverse biased) is recommended to
protect against sinking current into a supply should one supply be ON while
another other is OFF, as shown in Figure 3-112.
4.
Diode D2 shown in the figure is optional, if the load has stored energy such as a
battery. Refer to Section 2.12.
Figure 3-112. Series Connection with Anti-Parallel Diodes