![Ametek SHPF3 Series Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/ametek/shpf3-series/shpf3-series_instruction-operation-and-maintenance-manual_2931249029.webp)
SHPF3 SCR Power Controller
Troubleshooting
Rev 2
Ametek HDR Power Systems
23
7.6
Correcting Troubles in the SHPF3 Itself
Table 7.1 provides a comprehensive guide for troubleshooting the SHPF3.
Table 7.1 Troubleshooting Chart (Symptoms and Solutions)
Cause Solution
No output even with manual control (Zero) turned full CW.
(1a) Open SCR fuse
Remove and check the fuse. If it has opened, replace it after completing (b)
(1b) SCRs not firing
Install a good fuse in the circuit, and apply power to the SHPF3. If the output is
fully controllable using the manual control, then resume normal operation. If the
power output is still zero, contact Ametek HDR Power Systems service.
Maximum power at all times regardless of control setting.
(2a) All SCR networks
shorted
Remove the fuse and check the front-to-back SCR pairs by measuring
resistance between terminals L1 (of the SCR) and X1. On the Rx1 scale, the
resistance should be infinite in both directions. If a shorted component is
indicated in any of these cases, replace it.
(2b) Firing control
section defective
Replace the fuse and return the power to the unit. If the problem persists,
contact Ametek HDR Power Systems service.
Output is variable but can’t be brought to zero with ZERO control
(3a) SCR network
shorted
Check SCR network per solution 2a.
(3b) Firing control
section defective
Contact Ametek HDR Power Systems service for assistance
Output is variable but can’t be brought to maximum with SPAN control
(4a) Firing control
section defective
Contact service for assistance
Table 7.2 Torque Specifications
TORQUE, INCH POUNDS
INPUT/OUTPUT CONDUCTOR
SIZE, AWG OR CIR. MILS
SLOT WIDTH*
HEX HEAD
(ALL)
¼” OR LESS
OVER ¼”
6-4 AWG
25
45
110
2 AWG
35
50
150
1 AWG
40
50
150
1/0 – 2/0 AWG
50
180
3/0 – 4/0 AWG
--
250
250 – 350 MCM
--
325
500 – 700 MCM
--
375
800 – 1000 MCM
500
* = Screwdriver Blade Width to Match
(With Socket-Head Screws, all Conductor Sizes)
SOCKET SIZE, ACROSS FLATS
TORQUE INCH POUNDS
3/16” 120
1/4” 200
5/16” 275
3/8” 375
1/2" 500
Содержание SHPF3 Series
Страница 6: ...Table of Contents SHPF3 SCR Power Controller iv Ametek HDR Power Systems Rev 2...
Страница 8: ...Safety Instructions SHPF3 SCR Power Controller 2 Ametek HDR Power Systems Rev 2...
Страница 22: ...Operation SHPF3 SCR Power Controller 16 Ametek HDR Power Systems Rev 2...
Страница 36: ...Appendix SHPF3 SCR Power Controller 30 Ametek HDR Power Systems Rev 2 Appendix B 15 and 25 A Outline R...
Страница 37: ...SHPF3 SCR Power Controller Appendix Rev 2 Ametek HDR Power Systems 31 Appendix C 60 225 A Outline R...
Страница 39: ...Notes...
Страница 40: ...503 Lakeview Plaza Blvd Ste C Worthington Ohio 43085 USA...