SHPF3 SCR Power Controller 

 

Options 

Rev 2

 

Ametek HDR Power Systems

 

5

 

CHAPTER 2 - Options 

 

2.1 General 

Several options are available from Ametek HDR Power Systems, and are described below.  Most 
options require current transformers (CTs), which are optional.  On models rated from 60 through 225 
amperes the CTs are mounted in the controller and on models rated from 350 amperes and higher, the 
CTs are shipped separately. 
 

2.2 

Option OC (Three-Phase Overcurrent Trip) 

The Three-Phase Overcurrent Trip Option (OC) provides circuit protection from output current 
overloads by serving as a fast-gate shutdown.  (Option OC functions similar to an electronic fuse.)  
Trip point is adjustable from 30% to 200% of the SCR Power Control’s current transformer rating.  
Current transformers on the SCR Power Control’s output lines allow Option OC to monitor 
instantaneous peak current.  When the peak current level exceeds the preset trip level, SCRs are 
gated off, and the load current is shut down within 1/2 cycle.  The TRIP RESET pushbutton must be 
manually reset to resume operation. 
 
Another feature of the overcurrent trip is an automatic reset. This is included with the current limit and 
current regulation. Open the unit and locate the auto reset switch and reset pushbutton. With this 
switch in the on position, the unit will continue to reset until the fault clears. If in the off position, the 
unit will remain shut off until the reset PB is operated. The auto reset switch will always be in the off 
position unless specified on the order.   
 
The overcurrent trip option includes a Form C relay output and provisions for a remote overcurrent 
reset push button.  The relay output terminals are 39 and 40 for the N.C. and 40 and 41 for the N.O. 
The remote reset terminals are 37 and 38.  Reference Figure 5.1. 
 

2.3 

Option CL/OC (Current Limit/Overcurrent Trip) 

The Three-Phase Current Limit Option (CL) prevents the output current of an SCR Power Control from 
exceeding a preset maximum current level, as determined by the current limit control setting (30% to 
125%).  This option also includes an OC trip with Form C relay output contact and terminals for 
connection of a remote OC reset pushbutton.  The current limit adjustment is on the front of the unit, 
while the overcurrent trip adjustment is located on the current regulation PCB on the inside of the unit. 
 
A current transformer monitors the true RMS current, and feeds the information to Option CL, which 
limits the true RMS current regardless of the process control signal.  Current Limit is adjustable from 
30% to 125% of the CT rating. 
 

2.4 

Option CR/OC (Current Regulation/Overcurrent Trip) 

The Current Regulation option is much like the Current Limit. It includes an overcurrent trip feature, but 
regulates the RMS current rather than limiting it. The adjustment range is 30 to 125% of the unit's 
rating for the current regulation and 30 to 200% for the overcurrent trip.  This option also includes an 
OC trip with Form C relay output contact and terminals for connection of a remote OC reset 
pushbutton.  The current regulation adjustment is on the front of the unit, while the overcurrent trip 
adjustment is located on the current regulation PCB on the inside of the unit.  
 
The Three-Phase Current Regulation Option (CR) compares the feedback signal to the control signal, 
so the line current will be linear to the control signal, and regulated to maintain a constant level at the 
controller output despite load changed.  Current regulation is adjustable from 30% to 125% of the CT 
rating. 

Содержание SHPF3 Series

Страница 1: ...aintenance Manual Number 9100035 Revision 2 530 Lakeview Plaza Blvd Ste C Worthington Ohio USA 43085 Toll Free 1 888 PWR CNTL 797 2685 Phone 614 308 5500 Fax 614 308 5506 Web www hdrpower com SHPF3 SC...

Страница 2: ...representative nearest you please call Ametek HDR Power Systems main office at 614 308 5500 Revision 1 September 2014 Initial Release Revision 2 July 2015 Revised Address 2015 by Ametek HDR Power Sys...

Страница 3: ...r 7 3 4 Wiring Overtemperature Contacts 8 3 5 Command Signal Input 8 3 6 Determining Line Frequency 9 3 7 Voltage Changeover 9 3 8 Options 10 CHAPTER 4 OPERATION 11 4 1 General 11 4 2 Front Panel Indi...

Страница 4: ...5 Input Power and Load Connections 22 7 6 Correcting Troubles in the SHPF3 Itself 23 CHAPTER 8 SERVICE 24 8 1 Communication Procedures 24 8 2 Spare Parts Orders Routine or Emergency 24 8 3 Spare Parts...

Страница 5: ...3 Figure 4 4 Auto Man Control with Controller and Remote Potentiometer 14 Figure 4 5 On Off Control 14 Figure 4 6 Shutdown Control 15 Figure 5 1 Current Limit Trip Board 17 Figure 6 1 AC Switch and SC...

Страница 6: ...Table of Contents SHPF3 SCR Power Controller iv Ametek HDR Power Systems Rev 2...

Страница 7: ...connect or circuit breaker with this Power Controller is required to ensure the safety of operating personnel CAUTION HAZARDOUS VOLTAGES exist at the Power Controller Load AT ALL TIMES when input volt...

Страница 8: ...Safety Instructions SHPF3 SCR Power Controller 2 Ametek HDR Power Systems Rev 2...

Страница 9: ...A zero fired model would be a better choice 1 3 Operation The SHPF3 accomplishes power control by the switching action of a pair of inverse parallel power SCRs The switching or gating of the SCRs is c...

Страница 10: ...ction Current surge Subcycle I T semiconductor fuse Transient voltage spikes dv dt SCCR Rating Metal Oxide Varistor MOV and R C snubber across each SCR pair all SCRs have PIV rating of 1 400 V 100kA M...

Страница 11: ...put terminals are 39 and 40 for the N C and 40 and 41 for the N O The remote reset terminals are 37 and 38 Reference Figure 5 1 2 3 Option CL OC Current Limit Overcurrent Trip The Three Phase Current...

Страница 12: ...the control signal and regulated to maintain a constant power level at the controller output despite line and load changes Current limit holds the current to a preset maximum limit and is adjustable...

Страница 13: ...F3 is phase rotation insensitive That is three phase input power can be connected in any sequence to terminals L1 L2 and L3 and will not cause an out of phase condition The fuses included are NOT mean...

Страница 14: ...n and Thermostat Connections 3 5 Command Signal Input HDR s Phase Fired SCR Power Controllers have the capability of having either an isolated current or non isolated voltage Command Signal input The...

Страница 15: ...a wide range of line voltages 120 240 400 480 575 Vac so long as the load current does not exceed the SHPF3 s current rating This is accomplished by performing the procedure described below Using the...

Страница 16: ...the unit with a label or tag noting that SHPF3 has been modified for line voltage other than what it was specified for This may prevent accidental use on an incorrect line voltage in the future 3 8 O...

Страница 17: ...ignal Indicator The Command Signal Indicator is a green Light Emitting Diode LED located on the front cover of the unit The brilliance of this LED will change with a current Command Signal The brillia...

Страница 18: ...line power to the SHPF3 and disconnect the test equipment The SHPF3 is now ready for automatic operation i If Option CR or PR is installed adjust the CUR PWR potentiometer CW until the output is limit...

Страница 19: ...mum i If necessary readjust ZERO with remote potentiometer fully CCW and SPAN control and remote potentiometer fully CW j Turn off the line power to the SHPF3 and disconnect the test equipment k If Op...

Страница 20: ...se simple applications It can be connected for turn on by a contact closure With the SHPF3 configured for non isolated inputs and the power to the SHPF3 turned off connect the system as shown in figur...

Страница 21: ...down or disable the output it is a simple matter Connect a dry contact closure between terminals 3 and 4 of the firing circuit as shown in Figure 4 6 A closed contact will disable the SHPF3 output 10...

Страница 22: ...Operation SHPF3 SCR Power Controller 16 Ametek HDR Power Systems Rev 2...

Страница 23: ...Limit option PCB on the inside front door The power controller should turn on 5 2 Option CL OC Current Limit Over Current Trip Refer to Chapter 4 and review the setup procedure for the ZERO and SPAN...

Страница 24: ...iometer full CCW e Set the input control signal to demand full output f Adjust the CURRENT REG CUR PWR potentiometer until full scale current level is reached g With the power controller at full level...

Страница 25: ...3 Digital Firing Control Circuit Firing gating of the SCRs is controlled by a digital firing control circuit synchronized to the line frequency 50 or 60 Hz The firing control circuit may be manually c...

Страница 26: ...ively as manually adjusted The SPAN control is used as a final adjustment to set the SHPF3 output to precisely 100 when the principal control device external controller external manual control or ZERO...

Страница 27: ...riable from zero to some intermediate value but cannot be brought to maximum The symptoms listed may be caused by one or more of the following an environmental problem faulty input power or load conne...

Страница 28: ...ks and any item or structure near the SHPF3 power modules Heat sink fins should be free of dust or dirt for proper heat transfer and free of obstructions which could prevent proper airflow Contaminati...

Страница 29: ...Rx1 scale the resistance should be infinite in both directions If a shorted component is indicated in any of these cases replace it 2b Firing control section defective Replace the fuse and return the...

Страница 30: ...rrange for service at your site or by shipment to Ametek HDR Power System as you request We will make every possible attempt to support your emergency on site needs regardless of how contacted 8 2 Spa...

Страница 31: ...Extended Gate PCB Assy DVDT SCR dual pkg 90 A 1400 V 7580070I 2099157 2099103 6791114 3 1 3 3 60 Ampere Units Fuse 80A 700V PCB Assy PF3 Extended Gate PCB Assy DVDT SCR dual pkg 90 A 1400 V 7580070I...

Страница 32: ...c of the SHPF3 These drawings are useful in installing and troubleshooting all SHPF3 models Table 8 2 lists the drawings for each model Appendix provides simplified drawings in the order of their appe...

Страница 33: ...Y OR OTHERWISE IN NO EVENT WILL AMETEK HDR BE LIABLE FOR INCIDENT OR CONSEQUENTIAL DAMAGES NOR IN ANY EVENT SHALL HDR S LIABILITY EXCEED THE UNIT PRICE OF ANY DEFECTIVE PRODUCT OR PART 9 2 In house Re...

Страница 34: ...er Systems Rev 2 9 3 Field Service Repairs Repairs may be performed at your location Please contact Ametek HDR Power Systems at 614 308 5500 to discuss terms and conditions to get the current service...

Страница 35: ...SHPF3 SCR Power Controller Appendix Rev 2 Ametek HDR Power Systems 29 APPENDIX Appendix A System Schematic Note CT s are optional Fans and Thermostats may not be included in certain models...

Страница 36: ...Appendix SHPF3 SCR Power Controller 30 Ametek HDR Power Systems Rev 2 Appendix B 15 and 25 A Outline R...

Страница 37: ...SHPF3 SCR Power Controller Appendix Rev 2 Ametek HDR Power Systems 31 Appendix C 60 225 A Outline R...

Страница 38: ...ration relates is in conformity with the technical requirements of the following documents Title Low voltage switchgear No IEC 947 5 1 and control gear Year 1990 03 Low Voltage Directive No IEC 73 23...

Страница 39: ...Notes...

Страница 40: ...503 Lakeview Plaza Blvd Ste C Worthington Ohio 43085 USA...

Отзывы: