Installation
7
2.2
Mounting and Installation Guidelines (continued)
• Do not mount a Cote-Shield sensing element through a
nozzle that exceeds length of first insulator.
• Ensure that there are no obstructions or agitator blades to
interfere with sensing element.
• Rigid sensing elements can be mounted at any angle.
2.3
Installation of Flush-Mounted Sensing Elements
These instructions apply to all flush on/off sensing elements,
models 700-0207-001, 700-0207-002, 700-0207-003, 700-0207-
004, 700-0207-006. These systems will sense presence of
material (no flow or plugged chute) and absence of material
(flow or empty chute) at the sensing element.
The Flush Sensing
Element will ignore free falling material.
Material Backed-Up Above
Sensing Element
(No Flow)
Sensing Element at the Top of a Chute.
•
The flush sensing element should be mounted
In
The Flow Stream
. These sensing elements are
designed and built to withstand the impact of coal,
rock, wood, chips, etc. This location is important
to prevent excessive build up of material on the
face of the sensing element.
•
Excessive build up, typically consisting of wet and/
or sticky fines, can occur if the sensing element is
protected from falling material.
Sensing Element in an angle chute.
• Do not mount on the top or bottom.
• Best mounted on either side
Sensing Element at the Bottom
• Mount on any side.
• Low-Level sensors can be used to detect
a plug or to insure that a seal is present
(chute is full at this point).
Содержание ThePoint Series
Страница 4: ...Contents...
Страница 6: ...Section 1...
Страница 28: ...ThePoint Series 22 Section 3...
Страница 36: ...Section 4...
Страница 39: ...Control Drawings 33 Section 5 Control Drawings 5 1 FM FMc Control Drawings...
Страница 40: ...ThePoint Series 34 5 1 FM FMc Control Drawings Continued...
Страница 41: ...Control Drawings 35 5 1 FM FMc Control Drawings Continued...
Страница 42: ...ThePoint Series 36 5 1 FM FMc Control Drawings Continued...
Страница 43: ...Control Drawings 37 5 1 FM FMc Control Drawings Continued...
Страница 44: ...ThePoint Series 38 5 1 FM FMc Control Drawings Continued...
Страница 45: ...Control Drawings 39 5 1 FM FMc Control Drawings Continued...
Страница 46: ...ThePoint Series 40 5 1 FM FMc Control Drawings Continued...
Страница 47: ...Control Drawings 41 5 1 FM FMc Control Drawings Continued...
Страница 48: ...ThePoint Series 42 5 1 FM FMc Control Drawings Continued...
Страница 49: ...Control Drawings 43 5 1 FM FMc Control Drawings Continued...
Страница 50: ...ThePoint Series 44 5 2 ATEX Control Drawings...
Страница 51: ...Control Drawings 45 5 2 ATEX Control Drawings Continued...
Страница 52: ...ThePoint Series 46 5 2 ATEX Control Drawings Continued...
Страница 55: ...Control Drawings 49 5 2 ATEX Control Drawings Continued...
Страница 56: ...ThePoint Series 50 5 3 Heavy Duty Spark Protection...
Страница 57: ...Control Drawings 51 5 3 Heavy Duty Spark Protection Continued...
Страница 58: ...ThePoint Series 52 5 4 Adding a Padded Capacitor...
Страница 59: ...Control Drawings 53 5 4 Adding a Padded Capacitor Continued...
Страница 60: ...ThePoint Series 54 5 4 Adding a Padded Capacitor Continued...
Страница 61: ...Control Drawings 55 5 5 Dual Seal Assembly for 700 Series Sensing Elements...
Страница 62: ...ThePoint Series 56 5 5 Dual Seal Assembly Continued...
Страница 63: ...Control Drawings 57 5 5 Dual Seal Assembly Continued...
Страница 64: ...Appendix A...
Страница 69: ......