SECTION 4, RO+ STARTUP & OPERATION
4.1
INSTALLATION
NOTE: This entire Operations Manual should be read before operating or servicing
the RO. The Operations Manual should then be kept near the system and
used as a reference and troubleshooting guide.
1.
Feed water to RO must not contain chlorine, iron, manganese, oil, or large quantities
of organic matter. Common waterworks water will normally meet these requirements.
2.
Normally the water temperature must not exceed 80°F
3.
The installation location must be dry and frost-free.
4.
The pressure at the industrial RO inlet, when in operation, must be 20 PSI, minimum,
and must not exceed 90 PSI. If the pressure exceeds the maximum stated pressure,
or it fluctuates to pressures exceeding 90 PSI, install a pressure-reducing valve on
the inlet.
5.
The flow of inlet water supplied to the RO unit shall be an uninterrupted flow at 20
PSI, minimum, and at a minimum flow rate of twice the rated Product Water flow of
the RO unit purchased.
6.
A floor drain close to the unit is required that is capable of carrying away the reject
water flow for the RO unit. The reject flow is approximately the same as the rated
Product Water flow.
7.
The piping, faucets, valves etc. for the Product Water outlet of the Reverse Osmosis
unit must be made of PVC or corrosion resistant stainless steel.
8.
The electrical power shall be provided to the RO through a 60 amp disconnect
located near the unit. The voltage and phase must match and be verified to the RO
unit that was purchased. Control voltage is provided within the RO unit controller via
a transformer.
9.
Local plumbing codes and electrical regulations must be observed and followed.