background image

    328767-001       www. 

  americanwaterheater   .com 35

  BLOWER  ASSEMBLY  INSTALLATION

1.  This power vented water heater comes with blower 

assembly installed.

2.  After unit is set in place, make sure blower assembly is 

still mounted securely. Make sure there is no damage 
to blower.

3.  Make sure there is no packing material in the inlet or 

discharge of the blower.

4.  Make sure that the plastic tubing is still attached from 

the air pressure switch to the port on the blower motor 
housing. Make sure the plastic tubing is not folded 
anywhere between the pressure switch and the blower 
motor housing (see Figure 36 thru Figure 40).

5.  This water heater is a polarity sensitive appliance and 

will not operate if the power supply polarity is reversed. 
Power to this water heater must be wired properly 
(correct polarity).

6.  Do not plug in power cord until vent system is 

completely installed. The Power Direct Vent operates 
on 110 -120 VAC. therefore a grounded outlet must be 
within reach of the 6 foot 

fl

 exible power cord supplied 

with the heater. The power cord supplied may be used 
on a unit only where local codes permit. If local codes 
do not permit use of 

fl

 exible power supply cord:

a.  Make sure the unit is unplugged from the wall 

outlet. Remove the screw and open panel on the 
front of the junction box on the blower.

b. Cut 

the 

fl

 exible power cord, leaving enough to be 

able to make connections. Remove the strain relief 

fi

 tting from the box.

c.  Install a suitable conduit 

fi

 tting inside the enclosure.

d. Splice 

fi

 eld wiring into existing wiring using code 

authorized method (wire nuts, etc).

e.  Be certain that the neutral and line connections 

are not reversed when making these connections.

f.  Ground heater properly. This water heater must be 

grounded in accordance with the current edition of 

 “National Electrical Code”, NFPA 70 

and/or local 

codes. These must be followed in all cases. The 
water heater must be connected to a grounded 
metal, permanent wiring system or an equipment 
grounding conductor must be run with the circuit 
conductors and connected to the equipment 
grounding terminal or lead on the water heater (see 
Figure 11; the wiring diagram).

g.  Close the panel on the junction box. Make sure 

that the access panel is secured shut.

7.  

The blower discharge has a rubber coupling made to 
accept only straight sections of 2” or 3” pipe. To start 
off with an elbow, a short section of the straight pipe 
must be cut and glued into the end of the elbow that 
will mount in the rubber coupling.

  Vent/Intake Pipe Connections To Blower/Air Duct

1.  The plastic vent piping connects into the rubber 

coupling located on the top of the blower assembly. 
This coupling includes gear clamps to connect the 
venting to the blower.

Important:

 These connections must be properly seated 

and tightened to prevent the leakage of 

fl

 ue gases into the 

area. See Figure 36 thru Figure 40.
2.  The 40 and 50-gallon heaters with rated inputs of 45k 

Btu/hr or less are designed and supplied with a 2” 
rubber coupling to accept the vent pipe.

3.  The 50 and 75-gallon models with rated inputs of 58k 

Btu/hr or more are supplied with a 3” rubber coupling 
to accept the vent pipe. 

Note:

 Polypropylene vent 

systems require separate adaptor (

fi

 eld supplied).

4.  Before installing clean and lightly sand the end of the 

ABS/PVC/CPVC plastic vent piping that will connect 
into the rubber coupling. For polypropylene vent 
systems follow manufacturer’s instructions.

5.  Loosen the upper clamp on the rubber coupling and 

insert the sanded end of the vent piping a full  1-1/4” . 
Do not use glue or sealant in the rubber coupling. 
Check that there is no stress on the connection or the 
vent piping that may be caused by twisting or bending.

6.  Tighten the upper clamp so that the vent piping is 

fi

 rmly secured in the coupling and is gas tight. Do not 

over tighten or cause distortion of any of the parts. 
Ensure the bottom of the rubber coupling is 

fi

 rmly 

seated on the blower outlet and that the lower gear 
clamp is also secure. Check to ensure there is no 
distortion or movement of the clamped assembly once 
it is completed.

• 

Do not overtighten the top and bottom gear clamps of the 

rubber coupling.

• 

Do not apply solvent cement or silicone to the rubber 

coupling connection.

Property Damage Hazard

CAUTION

HOSE CONNECTION 

PORT FOR 

CONDENSATE DRAIN

 8”  LOOP

TO 

DRAIN

BLOWER 

ASSEMBLY

Figure 35 

Содержание Powerflex

Страница 1: ...QUIRED POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED MOBILE HOMES For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER ALL TECHNICAL AND WARRAN...

Страница 2: ...23 Filling The Water Heater 24 Venting 25 Termination Clearances Sidewall 26 Side Wall Vent Terminal Installation Roof Vent Terminal Installation Concentric Vent Termination Kit Installation Multiple...

Страница 3: ...sinesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can...

Страница 4: ...4 www americanwaterheater com 328767 001 GENERAL SAFETY...

Страница 5: ...ble vapors Vapors 1 cannot be seen 2 are heavier than air 3 go a long way on the floor and 4 can be carried from other rooms to the the electodes by air currents Flammable Vapors FLAMMBLE DANGER Breat...

Страница 6: ...H SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for installation operation and maintenance of the gas fired water heater It also contains warnings throughout the manua...

Страница 7: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less tha...

Страница 8: ...ATER OUT MASSACHUSETTS INSTALLATION REQUIREMENTS 1 CONNECT ELECTRONICALLY CONTROLLED TIMER TO AN ALL BRONZE PUMP PUMP MUST ACTIVATE EVERY 6 HOURS FOR 60 SECONDS TURN PUMP TIMER OFF BEFORE CLOSING PIPI...

Страница 9: ...node 27 Inlet Water Shut off Valve 28 Rubber Coupling see Figure 5 29 Gear Clamp see Figure 5 30 Blower with Power Cord see Figure 5 31 Air Duct Adapter 32 Air Inlet Snorkel 33 Air Duct 34 Thermal Exp...

Страница 10: ...d as the primary water inlet and outlet connections See Combo Heating Inlet And Outlet Side Taps below Caution harness has 120 VAC In operation See Vent Pipe Installation for more information REPLACEM...

Страница 11: ...NNECTIONS FOR SPACE HEATING THE HOT AND COLD FITTING ASSEMBLIES PART 9001262005 CAN BE ORDERED THROUGH THE MANUFACTURER NOTE THE T P VALVE DISCHARGE PIPE MUST BE PIPED DIRECTLY TO THE DRAIN OR EXTERNA...

Страница 12: ...her reduce system water temperature Mixing valves are available at plumbing supply stores Consult a Qualified Installer or Service Agency Follow mixing valve manufacturer s instructions for installati...

Страница 13: ...water lines of air and sediment and to ensure complete filling of the tank The electrical power may then be turned on Verify proper operation after servicing See also Installation Checklist BLUE 120V...

Страница 14: ...the maximum temperature of the blower If the blower temperature rises above the temperature setting the switch opens causing the heater to shut down The switch will auto reset once the temperature dro...

Страница 15: ...ped to an adequate drain The pan must have a maximum depth of 1 75 Water heater life depends upon water quality water pressure and the environment in which the water heater is installed Water heaters...

Страница 16: ...rbon monoxide can cause brain damage or death Always read and understand instruction manual Install water heater in accordance with the instruction manual and NFPA 54 To avoid injury combustion and ve...

Страница 17: ...SULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products The purpose of an insulation blanket is to red...

Страница 18: ...e changing the factory setting on thermostat read Operating The Temperature Control System section in this manual This water heater should not be connected to any heating systems or components previou...

Страница 19: ...board loop must be adequately insulated to reduce heat loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Com...

Страница 20: ...tank should be installed on all closed systems to control the harmful effects of thermal expansion Contact a plumbing service agency or your retail supplier regarding the installation of a thermal exp...

Страница 21: ...er any circumstances Excessive length over 30 or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between...

Страница 22: ...t pipes to the water heater 4 Locate the slit running the length of a section of pipe insulation 5 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure alo...

Страница 23: ...e testing system Fire and Explosion Hazard WARNING Use pipe joint compound or Teflon tape marked as being resistant to the action of gases The appliance and its gas connection must be leak tested befo...

Страница 24: ...er heater To fill the water heater with water 1 Close the water heater drain valve by turning handle to the right clockwise The drain valve is on the lower front of water heater see Figure 19 2 If the...

Страница 25: ...ere and all combustion products are discharged to the outdoors This water heater must be properly vented for removal of exhaust gases to the outside atmosphere Correct installation of the vent pipe sy...

Страница 26: ...ance to a mechanical air supply inlet 3 above if within 10 horizontally E Clearance to unventilated soffit 12 L Clearance above paved sidewalk or paved driveway located on public property 7 F Clearanc...

Страница 27: ...least 18 above the roof 2 Must provide proper support for all pipes protruding through roof 3 The vertical roof terminations should be sealed with a plumbing roof boot or equivalent flashing A B 1 EXH...

Страница 28: ...exhaust cross circulation see Figure 25 When more than 2 kits are installed only 2 of them shall be less than 9 5 apart Never install 3 termination kits together less than 9 5 apart see Figure 26 9 5...

Страница 29: ...rmination elbow to direct the vent pipe downward 3 A vertical vent must have a 90 elbow to direct the vent pipe horizontally followed by a vent termination 45 elbow to direct the vent pipe downward 4...

Страница 30: ...Plastic screens must be secured with 2 drops of silicone sealant This will allow for easy removal for inspection and cleaning with 2 venting short with 2 venting long For heater models 40 40 50 45 VEN...

Страница 31: ...ortcuts and or improper joining techniques 2 SELECTION OF MATERIALS PVC and CPVC VENTING Cutting Device Saw or Pipe Cutter Deburring Tool Knife File or Beveling Machine 2 and above Brush Pure Bristle...

Страница 32: ...of the fitting Failure to chamfer the edge of the pipe may remove cement from the fitting socket causing the joint to leak Figure 31 C Test dry fit of the joint Tapered fitting sockets are designed s...

Страница 33: ...4 turn to evenly distribute the cement Do not continue to rotate the pipe after it has hit the bottom of the fitting socket A good joint will have sufficient cement to make a bead all the way around...

Страница 34: ...rd WARNING Cans of cement and primer should be closed at all times when not in use to prevent evaporation of chemicals and hardening of cement They are also very flammable and should be kept away from...

Страница 35: ...terminal or lead on the water heater see Figure 11 the wiring diagram g Close the panel on the junction box Make sure that the access panel is secured shut 7 The blower discharge has a rubber couplin...

Страница 36: ...PIPE Figure 37 4 VENT PIPE 3 RUBBER COUPLING ORDER COUPLING Kit 9008311005 TO REPLACE 2 RUBBER COUPLING SUPPLIED 3 VENT PIPE 3 MAX LENGTH 3 4 ADAPTER FIELD SUPPLIED BLOWER CONFIGURATION FOR LO INPUT...

Страница 37: ...ion must be installed in the straight through end of the Sound Suppressor see Figure 43 BLOWER 2 VENT PIPE AIR DUCT ADAPTER 2 SOUND SUPPRESSOR CONFIGURATION FOR HEATERS CONNECTED TO 2 VENTING 12 PREFE...

Страница 38: ...ossible gas leaks Vent Pipe System Vent pipe and fittings of approved material Acceptable size length and number of elbows on exhaust vent system Installed in accordance with prevailing provisions of...

Страница 39: ...on the control to the OFF position 5 Do not attempt to light manually 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If yo...

Страница 40: ...icapped If anyone using hot water fits into one of these groups or if there is a local code or state law requiring certain temperature water at the hot water tap then you must take special precautions...

Страница 41: ...n 5 seconds A 130 More than 30 seconds HOT 120 More than 5 minutes LOW 110 Normal shower temp VAC 70 N A Table 5 Note The temperatures indicated are approximate The actual temperature of the heated wa...

Страница 42: ...ould be considered normal OPERATIONAL CONDITIONS Smelly Water Each water heater contains at least one anode rod for corrosion protection of the tank Certain water conditions will cause a reaction betw...

Страница 43: ...could cause improper venting or leakage of combustion products Be sure the vent piping is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation Obstructio...

Страница 44: ...that water discharge will not cause any property damage as water may be extremely hot Use care when operating valve as the valve may be hot To check the relief valve lift lever at the end of valve sev...

Страница 45: ...Follow instructions in the Filling The Water Heater section 8 Turn ON the gas supply at the main gas shut off valve 9 Follow the lighting instructions on the label or see Lighting Instructions to rest...

Страница 46: ...ns The use of a water softener may decrease the life of the water heater tank The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode...

Страница 47: ...ode rod fitting may be leaking D Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area E The temperature pressure relief val...

Страница 48: ...so Figure 56 31 Air Duct Adapter 32 Air Inlet Snorkel 33 Air Duct 35 Flame Sensor Rod see Figure 3 Figure 4 see also Figure 54 Figure 55 36 Sheet Metal Burner see Figure 3 Figure 4 see also Figure 54...

Страница 49: ...ox Cover removed for clarity 45 48 47 Figure 56 Notes Items not supplied with the water heater The side recirculation loop connections may not be used as the primary water inlet and outlet connections...

Страница 50: ...to the OFF position Wait for 10 seconds and move the switch back to the ON position If the problem that caused the control to lock out has not been corrected the control will remain or again go back...

Страница 51: ...ix One Flash three second pause Soft Lockout Retry Limit Failed Trial For Ignition 8 Six Two Flash three second pause Soft Lockout Recycle Limit Pressure Switch High Limit opened 9 Six Three Flash thr...

Страница 52: ...bly 2 Ensure the air pressure sensing tubes are properly connected and not kinked or damaged 3 Check continuity of the vent temperature limit switch replace switch if contact remain open 4 Check conti...

Страница 53: ...ir intake pipes 7 If there are excessive restrictions in the air intake pipe the air pressure switch N C will open 8 Check air pressure switch performance Check blower vacuum with a manometer Compare...

Страница 54: ...nstall the proper restrictive screens 2 Closed water system 3 Pressure build up 4 Improperly seated valve 1 Ensure the correct size of exhaust and air intake pipes were used per the instruction manual...

Страница 55: ...328767 001 www americanwaterheater com 55 NOTES...

Страница 56: ...500 Princeton Road Johnson City TN 37605 Phone 800 999 9515 Fax 800 999 5210 www americanwaterheater com...

Отзывы: