model rating plate. The inlet gas pressure must not exceed 
14” w.c. for natural gas and propane gas. The minimum 
inlet gas pressure shown on the rating plate is that which 
will permit 

fi

 ring at rated input.

All gas piping must comply with local codes and ordinances 
or with the 

 “National Fuel Gas Code”, ANSI Z223.1/

NFPA 54

. Copper or brass tubing and 

fi

 ttings (except tin 

lined copper tubing) should not be used.
If the gas control valve/thermostat is subjected to 
pressures exceeding 1/2 psi, the damage to the gas 
control valve/thermostat could result in a 

fi

 re or explosion 

from leaking gas.

If the main gas line shut-off serving all gas appliances is 
used, also turn “OFF” the gas at each appliance. Leave 
all gas appliances shut “OFF” until the water heater 
installation is complete.

A gas line of suf

fi

 cient size must be run to the water heater. 

Consult the current edition of 

 “National Fuel Gas Code”, 

ANSI Z223.1/NFPA 54

 and your gas supplier concerning 

pipe size.

There must be:

• 

A readily accessible manual shut-off valve in the gas 
supply line serving the water heater, and

• 

A sediment trap ahead of gas control valve/thermostat 
to help prevent dirt and foreign materials from entering 
the gas control valve/thermostat.

• 

fl

 exible gas connector or a ground joint union  between 

the shut-off valve and gas control valve/thermostat to 
permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting 
the water heater. Use a soapy water solution, not a match 
or open 

fl

 ame. Repair and retest as required. When 

fi

 nished, rinse off soapy solution and wipe dry.

 Use joint compound or tape 

compatible with natural gas 
and propane.

 Leak test before operating 

heater.

 Disconnect gas piping and 

shut-off valve before pressure 
testing system.

Fire and Explosion Hazard

WARNING

Use pipe joint compound or Te

fl

 on

®

 tape marked as being 

resistant to the action of gases.

The appliance and its gas connection must be leak tested 
before placing the appliance in operation.

The appliance and its individual shut-off valve should be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 1/2 psi. It should be isolated from the gas supply 

piping system by closing its individual manual shut-off 
valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 psi.

Connecting gas piping to the gas control valve/thermostat 
of water heater can be accomplished by either of two  
methods shown in Figure 17 & Figure 18.

FLEX PIPE 

(PROPERLY SIZED 

FOR THE HEATER 

INPUT RATE)

SEDIMENT 

TRAP

GAS 

CONTROL 

VALVE

GROUND 

JOINT 

UNION 

(OPTIONAL)

CAP

3” 

MIN.

Figure 17 

BLACK PIPE

SEDIMENT 

TRAP

GAS 

CONTROL 

VALVE

GROUND 

JOINT 

UNION 

(OPTIONAL)

CAP

3” 

MIN.

Figure 18 

 SEDIMENT  TRAPS

 

• 

Contaminants in gas lines can 

cause fire or explosion.

• 

Clean all gas piping before 

installation.

• 

Install sediment trap in accor-

dance with NFPA 54.

Fire and Explosion Hazard

WARNING

A sediment trap should be installed as close to the inlet of 
the water heater as practical at the time of water heater 
installation. The sediment trap should be either a tee 

fi

 tting 

with a capped nipple in the bottom outlet or other device 
recognized as an effective sediment trap. If a tee 

fi

 tting is 

used, it should be installed in conformance with one of the 
methods of installation shown in Figure 17 & Figure 18.
Contaminants in the gas lines may cause improper 
operation of the gas control valve/thermostat that may 
result in 

fi

 re or explosion. Before attaching the gas line be 

sure that all gas pipe is clean on the inside. To trap any 
dirt or foreign material in the gas supply line, a sediment 
trap must be incorporated in the piping. The sediment trap 

Содержание Powerflex

Страница 1: ...QUIRED POWER DIRECT VENT GAS MODELS WITH HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED MOBILE HOMES For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER ALL TECHNICAL AND WARRAN...

Страница 2: ...23 Filling The Water Heater 24 Venting 25 Termination Clearances Sidewall 26 Side Wall Vent Terminal Installation Roof Vent Terminal Installation Concentric Vent Termination Kit Installation Multiple...

Страница 3: ...sinesses to warn of potential exposure to such substances This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can...

Страница 4: ...4 www americanwaterheater com 328767 001 GENERAL SAFETY...

Страница 5: ...ble vapors Vapors 1 cannot be seen 2 are heavier than air 3 go a long way on the floor and 4 can be carried from other rooms to the the electodes by air currents Flammable Vapors FLAMMBLE DANGER Breat...

Страница 6: ...H SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for installation operation and maintenance of the gas fired water heater It also contains warnings throughout the manua...

Страница 7: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less tha...

Страница 8: ...ATER OUT MASSACHUSETTS INSTALLATION REQUIREMENTS 1 CONNECT ELECTRONICALLY CONTROLLED TIMER TO AN ALL BRONZE PUMP PUMP MUST ACTIVATE EVERY 6 HOURS FOR 60 SECONDS TURN PUMP TIMER OFF BEFORE CLOSING PIPI...

Страница 9: ...node 27 Inlet Water Shut off Valve 28 Rubber Coupling see Figure 5 29 Gear Clamp see Figure 5 30 Blower with Power Cord see Figure 5 31 Air Duct Adapter 32 Air Inlet Snorkel 33 Air Duct 34 Thermal Exp...

Страница 10: ...d as the primary water inlet and outlet connections See Combo Heating Inlet And Outlet Side Taps below Caution harness has 120 VAC In operation See Vent Pipe Installation for more information REPLACEM...

Страница 11: ...NNECTIONS FOR SPACE HEATING THE HOT AND COLD FITTING ASSEMBLIES PART 9001262005 CAN BE ORDERED THROUGH THE MANUFACTURER NOTE THE T P VALVE DISCHARGE PIPE MUST BE PIPED DIRECTLY TO THE DRAIN OR EXTERNA...

Страница 12: ...her reduce system water temperature Mixing valves are available at plumbing supply stores Consult a Qualified Installer or Service Agency Follow mixing valve manufacturer s instructions for installati...

Страница 13: ...water lines of air and sediment and to ensure complete filling of the tank The electrical power may then be turned on Verify proper operation after servicing See also Installation Checklist BLUE 120V...

Страница 14: ...the maximum temperature of the blower If the blower temperature rises above the temperature setting the switch opens causing the heater to shut down The switch will auto reset once the temperature dro...

Страница 15: ...ped to an adequate drain The pan must have a maximum depth of 1 75 Water heater life depends upon water quality water pressure and the environment in which the water heater is installed Water heaters...

Страница 16: ...rbon monoxide can cause brain damage or death Always read and understand instruction manual Install water heater in accordance with the instruction manual and NFPA 54 To avoid injury combustion and ve...

Страница 17: ...SULATION BLANKETS Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products The purpose of an insulation blanket is to red...

Страница 18: ...e changing the factory setting on thermostat read Operating The Temperature Control System section in this manual This water heater should not be connected to any heating systems or components previou...

Страница 19: ...board loop must be adequately insulated to reduce heat loss 7 If the local jurisdiction requires a back flow preventer in the cold water line an expansion tank of adequate size must be installed 8 Com...

Страница 20: ...tank should be installed on all closed systems to control the harmful effects of thermal expansion Contact a plumbing service agency or your retail supplier regarding the installation of a thermal exp...

Страница 21: ...er any circumstances Excessive length over 30 or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve No valve or other obstruction is to be placed between...

Страница 22: ...t pipes to the water heater 4 Locate the slit running the length of a section of pipe insulation 5 Spread the slit open and slip the insulation over the cold water inlet pipe Apply gentle pressure alo...

Страница 23: ...e testing system Fire and Explosion Hazard WARNING Use pipe joint compound or Teflon tape marked as being resistant to the action of gases The appliance and its gas connection must be leak tested befo...

Страница 24: ...er heater To fill the water heater with water 1 Close the water heater drain valve by turning handle to the right clockwise The drain valve is on the lower front of water heater see Figure 19 2 If the...

Страница 25: ...ere and all combustion products are discharged to the outdoors This water heater must be properly vented for removal of exhaust gases to the outside atmosphere Correct installation of the vent pipe sy...

Страница 26: ...ance to a mechanical air supply inlet 3 above if within 10 horizontally E Clearance to unventilated soffit 12 L Clearance above paved sidewalk or paved driveway located on public property 7 F Clearanc...

Страница 27: ...least 18 above the roof 2 Must provide proper support for all pipes protruding through roof 3 The vertical roof terminations should be sealed with a plumbing roof boot or equivalent flashing A B 1 EXH...

Страница 28: ...exhaust cross circulation see Figure 25 When more than 2 kits are installed only 2 of them shall be less than 9 5 apart Never install 3 termination kits together less than 9 5 apart see Figure 26 9 5...

Страница 29: ...rmination elbow to direct the vent pipe downward 3 A vertical vent must have a 90 elbow to direct the vent pipe horizontally followed by a vent termination 45 elbow to direct the vent pipe downward 4...

Страница 30: ...Plastic screens must be secured with 2 drops of silicone sealant This will allow for easy removal for inspection and cleaning with 2 venting short with 2 venting long For heater models 40 40 50 45 VEN...

Страница 31: ...ortcuts and or improper joining techniques 2 SELECTION OF MATERIALS PVC and CPVC VENTING Cutting Device Saw or Pipe Cutter Deburring Tool Knife File or Beveling Machine 2 and above Brush Pure Bristle...

Страница 32: ...of the fitting Failure to chamfer the edge of the pipe may remove cement from the fitting socket causing the joint to leak Figure 31 C Test dry fit of the joint Tapered fitting sockets are designed s...

Страница 33: ...4 turn to evenly distribute the cement Do not continue to rotate the pipe after it has hit the bottom of the fitting socket A good joint will have sufficient cement to make a bead all the way around...

Страница 34: ...rd WARNING Cans of cement and primer should be closed at all times when not in use to prevent evaporation of chemicals and hardening of cement They are also very flammable and should be kept away from...

Страница 35: ...terminal or lead on the water heater see Figure 11 the wiring diagram g Close the panel on the junction box Make sure that the access panel is secured shut 7 The blower discharge has a rubber couplin...

Страница 36: ...PIPE Figure 37 4 VENT PIPE 3 RUBBER COUPLING ORDER COUPLING Kit 9008311005 TO REPLACE 2 RUBBER COUPLING SUPPLIED 3 VENT PIPE 3 MAX LENGTH 3 4 ADAPTER FIELD SUPPLIED BLOWER CONFIGURATION FOR LO INPUT...

Страница 37: ...ion must be installed in the straight through end of the Sound Suppressor see Figure 43 BLOWER 2 VENT PIPE AIR DUCT ADAPTER 2 SOUND SUPPRESSOR CONFIGURATION FOR HEATERS CONNECTED TO 2 VENTING 12 PREFE...

Страница 38: ...ossible gas leaks Vent Pipe System Vent pipe and fittings of approved material Acceptable size length and number of elbows on exhaust vent system Installed in accordance with prevailing provisions of...

Страница 39: ...on the control to the OFF position 5 Do not attempt to light manually 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If yo...

Страница 40: ...icapped If anyone using hot water fits into one of these groups or if there is a local code or state law requiring certain temperature water at the hot water tap then you must take special precautions...

Страница 41: ...n 5 seconds A 130 More than 30 seconds HOT 120 More than 5 minutes LOW 110 Normal shower temp VAC 70 N A Table 5 Note The temperatures indicated are approximate The actual temperature of the heated wa...

Страница 42: ...ould be considered normal OPERATIONAL CONDITIONS Smelly Water Each water heater contains at least one anode rod for corrosion protection of the tank Certain water conditions will cause a reaction betw...

Страница 43: ...could cause improper venting or leakage of combustion products Be sure the vent piping is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation Obstructio...

Страница 44: ...that water discharge will not cause any property damage as water may be extremely hot Use care when operating valve as the valve may be hot To check the relief valve lift lever at the end of valve sev...

Страница 45: ...Follow instructions in the Filling The Water Heater section 8 Turn ON the gas supply at the main gas shut off valve 9 Follow the lighting instructions on the label or see Lighting Instructions to rest...

Страница 46: ...ns The use of a water softener may decrease the life of the water heater tank The anode rod should be inspected after a maximum of three years and annually thereafter until the condition of the anode...

Страница 47: ...ode rod fitting may be leaking D Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pressure in your area E The temperature pressure relief val...

Страница 48: ...so Figure 56 31 Air Duct Adapter 32 Air Inlet Snorkel 33 Air Duct 35 Flame Sensor Rod see Figure 3 Figure 4 see also Figure 54 Figure 55 36 Sheet Metal Burner see Figure 3 Figure 4 see also Figure 54...

Страница 49: ...ox Cover removed for clarity 45 48 47 Figure 56 Notes Items not supplied with the water heater The side recirculation loop connections may not be used as the primary water inlet and outlet connections...

Страница 50: ...to the OFF position Wait for 10 seconds and move the switch back to the ON position If the problem that caused the control to lock out has not been corrected the control will remain or again go back...

Страница 51: ...ix One Flash three second pause Soft Lockout Retry Limit Failed Trial For Ignition 8 Six Two Flash three second pause Soft Lockout Recycle Limit Pressure Switch High Limit opened 9 Six Three Flash thr...

Страница 52: ...bly 2 Ensure the air pressure sensing tubes are properly connected and not kinked or damaged 3 Check continuity of the vent temperature limit switch replace switch if contact remain open 4 Check conti...

Страница 53: ...ir intake pipes 7 If there are excessive restrictions in the air intake pipe the air pressure switch N C will open 8 Check air pressure switch performance Check blower vacuum with a manometer Compare...

Страница 54: ...nstall the proper restrictive screens 2 Closed water system 3 Pressure build up 4 Improperly seated valve 1 Ensure the correct size of exhaust and air intake pipes were used per the instruction manual...

Страница 55: ...328767 001 www americanwaterheater com 55 NOTES...

Страница 56: ...500 Princeton Road Johnson City TN 37605 Phone 800 999 9515 Fax 800 999 5210 www americanwaterheater com...

Отзывы: