8. Locate the capillary tube of the existing auto-
reset water temperature limit and remove it from the
strain relief clamp. See Figure 53.
Figure 53
Figure 56
Figure 54
Figure 55
INSTALLING THE NEW MANUAL-RESET WATER
TEMPERATURE LIMIT
1. Remove the cover from the reset button on the
new manual reset water temperature limit switch by
turning counter clockwise. See Figure 54.
2. In a similar manner, remove the locking nut from
the new manual reset water temperature limit. See
Figure 55.
3. Insert the manual reset push button of the water
temperature limit through the hole in the control
panel. See Figure 56.