18-CG03D1-4
10
Table 3
Model
A
a1
a2
a3
in.
in.
in.
in.
*PFWF071A93ABA
17.0
1 1/4
1 1/4
1/2
*PFWF099A94ABA
20.9
1 1/4
1 1/4
1/2
*PFWF132A95ABA
24.9
1 1/4
1 1/4
1/2
*PFWF164A96ABA
28.8
1 1/4
1 1/4
1/2
*PFWF201A97ABA
32.8
1 1/4
1 1/4
1/2
*PFWF242A98ABA
36.7
1 1/4
1 1/4
1/2
*PFWF286A99ABA
40.6
1 1/4
1 1/4
1/2
* May be “A” or “T”
a1, a2, a3 are all NPT male
Table 2
Minimum Clearan-
ces for Combustion
Minimum Clearan-
ces for Service
Top
6”
36”
Right Side
6”
24” (a)
Left Side
6”
6” (a)
Front
18”
30” (b)
Back
6” 24”
(b)
The minimum clearances from boiler casing surfaces to combustible materials are:
(a) Leave at least 24” on one
side of the boiler and 6” on
the opposite side
(b) Though these are appro-
ved clearances for these boi-
lers, space must be provided
at the front (18 inches mini-
mum, 24-30 inches recom-
mended) and at the rear of
the boiler for access, service,
and replacement of the oil
burner and other hydronic
system components.
2.5 Outline Drawings
Figure 2 - Dimensions and Connections
All dimensions are in inches
19.68
4.13
10.63
33.46
22.05
20.87
5.00
5.39
5.39
5.39
3.94