18-CG03D1-4
41
PUMP CONNECTIONS AND PORT IDENTIFICA-
TION
This burner is shipped with the oil pump set to oper-
ate on a
single
line system. To operate on a
two-line
system the by-pass plug must be installed.
▲
▲
CAUTION
!
Do NOT
operate a
single
line system with the by-
pass plug installed. Operating a
single
line system
with the by-pass plug installed will result in damage
to the pump shaft seal.
NOTE:
Pump pressure must be set at time of burner
start-up. A pressure gauge is attached to the PRES-
SURE PORT (8) for pressure readings. Two PIPE
CONNECTORS (4) are supplied with the burner for
connection to either a single or two-line system. Also
supplied are two ADAPTORS (3), two female ¼” NPT,
to adapt oil lines to burner pipe connectors. All pump
port threads are British Parallel Thread design.
NOTE:
Direct connection of NPT threads to the
pump will damage the pump body.
Model BF3 and BF5
1. Mounting Flange
2. Mounting Gasket
3. Burner Access Hole
4. M8 x 1.25 Double End Threaded Studs,
included with boiler hardware
The electrical connection between the boiler and the
burner is made using a 7-pin plug. The boiler cord
will be found near the front left base of the boiler.
Connect the burner plug. Electrical connection and
startup are covered later in this document.
1
2
3
4
Figure 39
Pump Legend
1. Pump Cover
2. Pump Cover O-Ring
3. BSPP to NPT Adapters
4. Return Port By-Pass Screw
5. Supply Port
6. Supply and Return Oil Lines
7. Return Port
8. Pump Pressure and Bleeder Port
Figure 40
1
2
3
8
7
4
5
6
4
B
A
WET BASED CHAMBER APPLICATIONS
Figure 39b