BEFORE YOU CALL FOR SERVICE
Problem
Possible Causes
What to Do
Relief valve producing
popping noise or draining.
Unit is not making noise.
Pressure buildup by thermal
expansion to a closed system.
If unit is using resistance elements, it
will not make noise.
• This is an unacceptable condition and must be
corrected. Contact your water supplier or a
plumbing contractor for directions to correct
this issue. Do not plug the relief valve outlet.
• Check mode of unit.
24
ERROR CODE
MEANING
ACTIONS / SOLUTIONS
CHECK WIRES FOR DAMAGE
CHECK WIRES CONNECTIONS FROM SENSOR TO CONTROL BOARD
CHECK T2 FOR INTERFERENCE WITH STRONG MAGNETIC FIELD
CHECK ACTUAL TEMP. SHOULD BE BETWEEN IN 32°F - 140°F
CHECK WIRES FOR DAMAGE. MEASURE RESISTANCE FROM CONTROL BOARD CONNECTION.
CHECK WIRE CONNECTIONS FROM SENSOR TO CONTROL BOARD
CHECK T3 VERIFY IF SENSOR IS DAMAGED USING OHMMETER
CHECK T3 FOR INTERFERENCE WITH STRONG MAGNETIC FIELD
CHECK ACTUAL TEMP. SHOULD BE BETWEEN 23°F-86°F (TOL9°F)
CHECK ELECTRONIC EXPANSION VALVE FOR DAMAGE
CHECK WIRES FOR DAMAGE. MEASURE RESISTANCE FROM CONTROL BOARD CONNECTION
CHECK WIRE CONNECTIONS FROM SENSOR TO CONTROL BOARD
CHECK Th SENSOR FOR DAMAGE
CHECK Th FOR INTERFERENCE WITH STRONG MAGNETIC FIELD
CHECK ACTUAL TEMP. SHOULD BE BETWEEN 41°F-95°F
CHECK WIRES FOR DAMAGE. MEASURE RESISTANCE FROM CONTROL BOARD CONNECTION
CHECK WIRE CONNECTIONS FROM SENSOR TO CONTROL BOARD
CHECK T4 SENSOR FOR DAMAGE
CHECK T4 FOR INTERFERENCE WITH STRONG MAGNETIC FIELD
CHECK ACTUAL TEMP. SHOULD BE BETWEEN IN 68°F-221°F (TOL9°F)
CHECK REFRIGERANT TUBING FOR DAMAGE
CHECK FOR REFRIGERANT LEAKAGE
CHECK WIRES FOR DAMAGE. MEASURE RESISTANCE FROM CONTROL BOARD CONNECTION
CHECK WIRE CONNECTIONS FROM SENSOR TO CONTROL BOARD
CHECK T5 SENSOR FOR DAMAGE
CHECK IF T2 SENSOR WIRING IS BROKEN
CHECK IF T2 SENSOR TERMINAL CONNECTION IS STABLE
CHECK IF THE T2 SENSOR CAN ACCURATELY DETECT THE TEMPERATURE
DISAPPEAR WHEN EVAPORATER TEMP. HIGHER THAN 32°F
CHECK FOR ANY REFRIGERANT LEAKAGE
CHECK THE SUPPLY VOLTAGE < 198 VAC
CHECK COMPRESSOR FOR DAMAGE
CHECK UPPER ELEMENT RESISTANCE
CHECK CONNECTIONS FROM UPPER ELEMENT TO CONTROL BOARD
CHECK UPPER ELEMENT RELAY
CHECK LOWER ELEMENT RESISTANCE
CHECK CONNECTIONS FROM LOWER ELEMENT TO CONTROL BOARD
CHECK UPPER ELEMENT RELAY
P5
AIR FILTER IS TOO DIRTY
CLEAN THE AIR FILTER
CHECK POWER, VOLTAGE AND FREQUENCY
CHECK POWER WIRE, COULD BE LOOSE OR BROKEN
CHECK T5 FOR INTERFERENCE WITH STRONG MAGNETIC FIELD
CHECK PRESSURE IN THE REFRIGERANT SYSTEM
P4
COMPRESSOR CURRENT IS TOO HIGH
Water temperature is too high
(
T2>=165°F
)
E8
ABNORMAL POWER SUPPLY
C0
P8
UPPER ELEMENT CURRENT IS TOO LOW
LOWER ELEMENT CURRENT IS TOO
LOW
PA
T3 SENSOR MALFUNCTION
E1
AIR DISCHARGE HIGH TEMP
PROTECTION
P2
E0
T2 SENSOR MALFUNCTION
T4 SENSOR MALFUNCTION
Th SENSOR MALFUNCTION
E4
E5
E6
T5 SENSOR MALFUNCTION
EVAPORATER TEMP. BELOW 32°F
P0
CHECK IF UPPER/LOWER ELECTRIC HEATERS & COMPRESSOR RELAY CONTROL IS WORKING NORMALLY
HEAT PUMP WATER HEATER