background image

6

18-HE58D1-3

Installer’s Guide

IV) EXHAUST AIR FROM RETURN DUCT / FRESH AIR

DUCTED TO SUPPLY AIR DUCT

Furnace

Minimum 3'

Minimum 3'

SA

RA

(to ERV)

OA

RA

(Furnace)

ERV

EA

FA

Install internal 
elbow here

Figure 10

Note: Duct routing produces a negative pressure on
Exhaust Air and Adds additional pressure on Fresh Air
and can result in a greater than desired pressure differ-
ence and can make the house a negative pressure
volume. If a vented gas appliance is within the home's
envelope this duct application can cause flue gas
backdrafting.

INSTALL DUCT COLLARS

Attach one each of four duct collars to the fresh air inlet
and outlet, exhaust air inlet and outlet with the screws
provided in the plastic small parts bag.  Use duct mastic
or equivalent approved caulk to form seal around
duct collar.
  (Optional)  See figure 11.

Figure 11

DUCTWORK INSTALLATION - ERV TO EXTE-
RIOR WALL OUTLETS

 

CAUTION

!

Failure to follow this installation instruction may result in
property damage from sweating ductwork.

The fresh air duct and exhaust air duct connect the ERV to
the exterior wall outlet. Flexible or metal duct may be
used. The fresh air and exhaust air duct must be insulated.

Keep the fresh air supply and exhaust duct roughly equal
in length and as short and straight as possible.  Typically,
six (6) inch insulated flexible duct is used for the
*ERVR100/200A9P00AA and eight inch for the
*ERVR300A9P00AA.  If using flexible duct band or tape
the inner duct liner to the inner flange of appropriate
collar.  Drive a sheet metal screw through the liner to
secure the duct spiral wire to the collar.   Straighten
insulation, and slide the outer duct jacket onto the outer
flange of the duct collar.  Secure with band or tape.  The
outer flange of the duct collar can be used for both the
inner and outer jacket of eight (8) inch flexible duct.  Care
must be taken to insure that the duct is securely fastened
and sealed to the duct collar.

If duct runs are exceedingly long (over 25 feet of duct for
the *ERVR100 or 300 and over 15 feet for the *ERVR200)
see the Air Conditioning Contractors Association of
America’s (ACCA) duct sizing manual “Manual D” to
design the appropriate sized ductwork.

FRESH AND EXHAUST AIR INLET AND OUT-
LET INSTALLATION

 

WARNING

!

Failure to follow the installation instructions for location
of the fresh air inlet and return air grilles could result in
Carbon Monoxide Poisoning or Death.

The fresh air inlet should be at least ten feet away from
any exhaust such as chimneys, furnace vents, water heater
exhausts, dryer vents, driveways or other sources of carbon
monoxide or contamination.  Do not locate a fresh air inlet
where vehicles may be serviced or left idling.  Never locate
the fresh air inlet inside a structure.

Do not install return air grilles (stale air return) in ga-
rages, or in the same room with any gas fired appliance; for
example a gas fired furnace, gas fired water heater, gas
dryer, etc.
Do not connect ERV ductwork to kitchen vent hoods
Do not connect a dryer directly to an ERV

Содержание AERVR100A9P00A

Страница 1: ...ION NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE CAUTION To prevent shortening its service life the ERV should not be used during the finishing phases of construction Compounds used in c...

Страница 2: ...uctural alterations necessary for installation must comply with all applicable building health and safety code requirements ERV LOCATION CONSIDERATIONS Select a location to install the ERV with the ob...

Страница 3: ...S Access Door Swings Open Down The unit may be fastened directly to floor joists using the hanging bracket and integral flange Mount as described for installation on a concrete foundation wall except...

Страница 4: ...The unit may be installed in a variety of positions EXCEPT as noted in Figure 6d APPROVED MOUNTING POSITIONS HINGE HINGE Figure 6a Hinges on Bottom HINGE HINGE Figure 6b Hinges on Right HINGE HINGE Fi...

Страница 5: ...fan power humidifier Do not install a by pass humidifier as it can freeze based on the installation outdoor temperature and homeowner thermostat setback requirements APPROVED INSTALLATIONS I Separate...

Страница 6: ...ing flexible duct band or tape the inner duct liner to the inner flange of appropriate collar Drive a sheet metal screw through the liner to secure the duct spiral wire to the collar Straighten insula...

Страница 7: ...tall hood and ductwork through penetration See figure 13 for sealing duct penetration and duct collar Fill and seal COMPLETELY with Expanded Foam Figure 13 DUCTWORK CONNECTING ERV TO INDOOR TERMINATIO...

Страница 8: ...ble from your local distributor MicroSoft Excel is required to run this program The calculator input can accept a minimum ventilation airflow requirement per local code or calculate the minimum airflo...

Страница 9: ...ain and the unit will run 40 minutes A third press provides for 60 minutes of operation Percent Timer Control does not need to be on for the PB Control to operate the ERV unit You can cancel a cycle a...

Страница 10: ...o 10 unit should start and run for approximately six minutes 11 Go to outside of building and check for airflow at inlet and outlet hoods Check that weatherhood screens are in place and clean Make sur...

Страница 11: ...18 HE58D1 3 11 Installer s Guide...

Страница 12: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75711 Formoreinformation...

Отзывы: