18-HE58D1-3

7

Installer’s Guide

10 Ft. min

12 in. min 
above snow line

OA

EA

FA

RA

Legend
RA - Room Air
OA - Outside Air
FA - Fresh Air
EA - Exhaust Air

Figure 12

The exhaust outlet and fresh air inlet on the outside of the
building should be at least ten (10)  feet apart to avoid
cross contamination.

The Outdoor fresh air inlet must be located a minimum

of 10 feet from any other exhaust vent, gas meter,
outdoor grill, or source of open flame.

Fresh air inlets must also be located a minimum of ten
(10) feet from oil tank fill tubes,  garbage cans and any
other source of contamination.  Fresh air inlet and outlets
should not be installed in areas of stagnant air.  Fresh air
inlet and outlet hoods should be located a minimum of
twelve (12) inches above the normal snow level.

CAUTION

!

Failure to follow installation instructions may lead to
premature failure of the heat transfer core.

The ERV fresh air inlet and return air grilles must not be
located in the same room as an indoor swimming or
exercise "lap" pool.

Determine outlet locations. Cut correct size hole.  Cut a
short piece of 6" round duct to connect to the fresh air inlet
and exhaust air outlet hoods.  For Model *ERVR100 or
*ERVR200.  Use 8" round duct for Model *ERVR300.
Secure duct to inlet and outlet hood duct collars with
installer supplied fasteners.  Install hood and ductwork
through penetration.  See figure 13 for sealing duct
penetration and duct collar.

Fill and seal COMPLETELY
with Expanded Foam

Figure 13

DUCTWORK CONNECTING ERV TO INDOOR
TERMINATION POINTS

CAUTION

!

Failure to follow this installation instruction may result in
property damage from sweating ductwork.

Insulate all connecting ductwork from the ERV to any
indoor termination point that will be subject to forming
condensation.  Flexible or metal duct may be used.

An ERV can be applied either with an independent free
standing fresh and return air duct system or the fresh air
supply can be connected to the cooling and heating system
return air duct. The following guidelines should be consid-
ered when applying and installing either duct system.

FRESH AIR DUCT CONNECTION TO THE COOLING AND
HEATING SYSTEM RETURN AIR DUCT

The Fresh Air Supply duct from the ERV should be
connected a minimum of  three (3) feet up stream of the
indoor unit return plenum. (See Figure 7)
A connection closer than three 3 foot may result in unbal-
anced airflow. Use a minimum of 5 foot section insulated
flexible duct to connect the ERV port labeled “Fresh Air To
Inside” to the return air duct.

FREE STANDING DUCT SYSTEM

For free standing ERV duct systems one or two fresh air
grilles located in a central part of the house will provide
effective distribution of the fresh air into the home par-
ticularly when the air to be exhausted from the home is
returned from several points.  Use a minimum of 5 foot

Содержание AERVR100A9P00A

Страница 1: ...ION NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE CAUTION To prevent shortening its service life the ERV should not be used during the finishing phases of construction Compounds used in c...

Страница 2: ...uctural alterations necessary for installation must comply with all applicable building health and safety code requirements ERV LOCATION CONSIDERATIONS Select a location to install the ERV with the ob...

Страница 3: ...S Access Door Swings Open Down The unit may be fastened directly to floor joists using the hanging bracket and integral flange Mount as described for installation on a concrete foundation wall except...

Страница 4: ...The unit may be installed in a variety of positions EXCEPT as noted in Figure 6d APPROVED MOUNTING POSITIONS HINGE HINGE Figure 6a Hinges on Bottom HINGE HINGE Figure 6b Hinges on Right HINGE HINGE Fi...

Страница 5: ...fan power humidifier Do not install a by pass humidifier as it can freeze based on the installation outdoor temperature and homeowner thermostat setback requirements APPROVED INSTALLATIONS I Separate...

Страница 6: ...ing flexible duct band or tape the inner duct liner to the inner flange of appropriate collar Drive a sheet metal screw through the liner to secure the duct spiral wire to the collar Straighten insula...

Страница 7: ...tall hood and ductwork through penetration See figure 13 for sealing duct penetration and duct collar Fill and seal COMPLETELY with Expanded Foam Figure 13 DUCTWORK CONNECTING ERV TO INDOOR TERMINATIO...

Страница 8: ...ble from your local distributor MicroSoft Excel is required to run this program The calculator input can accept a minimum ventilation airflow requirement per local code or calculate the minimum airflo...

Страница 9: ...ain and the unit will run 40 minutes A third press provides for 60 minutes of operation Percent Timer Control does not need to be on for the PB Control to operate the ERV unit You can cancel a cycle a...

Страница 10: ...o 10 unit should start and run for approximately six minutes 11 Go to outside of building and check for airflow at inlet and outlet hoods Check that weatherhood screens are in place and clean Make sur...

Страница 11: ...18 HE58D1 3 11 Installer s Guide...

Страница 12: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75711 Formoreinformation...

Отзывы: