American Standard ACONT402AN32DA Скачать руководство пользователя страница 16

16

Pub. No.  11-HD03D3-3

Installer’s Guide

Reduces the indoor air flow to 80% when the room
temperature is within 2 degrees of the setpoint
and when the room temperature is below the
setpoint.

      •

Non-Variable Speed Dehumidification – BK
Disabled

Extends the compressor runtime by two minutes
to remove additional moisture from the indoor air.
Defeats the blower turn-off delay.
Applies the greater of the blower turn-on delay, or
30 seconds maximum blower turn-on delay based
on how long the compressor has been off.

Wet Heat

A hot water coil can be applied with a variable speed or
non-variable speed indoor unit to provide heat or to provide
auxiliary heat for heat pumps.  With either type of
equipment, the blower turn-on and turn-off delays apply to
the G output (ISU Steps 38 & 39).

      •

Variable Speed Wet Heat – BK Enabled

W1 turns on continuously for first stage and the
air flow is modulated based on the calculated load.
W2 is duty cycled for second stage based on the
calculated load while the air flow remains at
100%.  The air flow during the fan off delay is at
35%.

      •

Non-Variable Speed Wet Heat – BK Disabled

W1 and W2 are duty cycled the same as for electric
heat operation.

Auxiliary Heat Lockout

Enabled by selecting an outdoor temperature.  None of the
installed auxiliary heat stages will turn on during heating
operation above the selected outdoor temperature.  During
defrost, this outdoor temperature setting is ignored and
the Defrost Heater Balance Point outdoor temperature
thresholds are used instead.

Defrost Heater Balance Point Control

A separate outdoor temperature turn-on threshold can be
chosen for each installed heater stage during defrost.  If not
enabled, that particular heater stage will be energized
during every defrost cycle independent of the outdoor
temperature.  Once the defrost cycle terminates, the
comfort control load calculation will resume duty cycle
control of the heater stages.  During defrost, the comfort
control will not cycle the heat pump off unless an indoor
temperature overshoot of 2.5 degrees or more above the
heating setpoint occurs.

Dual Fuel

 (Heat Pump with Fossil Fuel Auxiliary Heat)

NOTE: No external dual fuel kit (e.g. TAYPLUS103A) is
required for use with this Comfort Control.  During the
transition from furnace operation to heat pump operation,
there is a minimum comfort control time delay of 45
seconds between the furnace turning off and the heat pump
turning on.

RESTRICTED MODE - (Requires Outdoor
Temperature Sensor)

The Heat Pump Restricted Mode Outdoor Temperature
changeover point (ISU Step 43) must be set at or above the
application or economic balance point of the system.

At any temperature above the Heat Pump Restricted Mode
Outdoor Temperature the comfort control will first attempt
to satisfy the heating load by operating the heat pump.  If
the heat pump alone cannot satisfy the load, the comfort
control will transition to furnace operation and will turn off
the heat pump.  The furnace may operate continuously or it
may cycle on and off as required to balance the load.

When the outdoor temperature drops below the ISU Step
43 setting, the comfort control will operate only the furnace
and the heat pump will be off.  When the outdoor
temperature rises above the setting of the Resume Heat
Pump Operation Outdoor Temperature (ISU Step 44), the
system returns to heat pump operation if the building load
is relatively low.

The outdoor temperature sensor reading is compared to the
outdoor temperature changeover point once every 10
minutes.  The Resume Outdoor Temperature can be set no
closer than 4 degrees above the Restricted Mode Outdoor
Temperature.

Placing the comfort control in Emergency Heat mode
converts the system to furnace only operation.

NOTE: 

Economic Balance Point is the outdoor

temperature at which it is more economical to use the
alternate fuel energy than the primary electric heat pump
energy.  Application Balance Point is the outdoor
temperature below which the heat pump alone cannot
handle the load.

UN-RESTRICTED MODE 

-

If the building load is relatively low such that the heat
pump alone can hand the building load, the comfort control
will operate the heat pump to maintain the room
temperature at the setpoint, independant of the outdoor
temperature.

If the heat pump cannot handle the building load, the
comfort control will turn the heat pump off and will operate
the furnace.  The furnace may operate continuously or it
may cycle on and off as required to balance the load.
Transition back to heat pump operation will occur when the
building load returns to a relatively low level.

Placing the comfort control in Emergency Heat mode
converts the system to furnace only operation.

Содержание ACONT402AN32DA

Страница 1: ...ER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which could result in minor personal injury or product and property damage Note Read the entire instruction manu...

Страница 2: ...se non hardening caulk putty or insulation 3 Avoid locations such as near dryer vents or placing the sensor close to or directly above the outdoor unit where it would be exposed to hot discharge air from the condenser fan 4 Maximum length of field wiring cable to sensor is 200 feet 5 Minimum wire gauge is 18AWG Mounting and Wiring 1 Turn OFF all power to heating and cooling equipment 2 If an exist...

Страница 3: ...on display See Figure 6 Enter USER Setup See Table 3A steps 50 62 for option details Press and hold Mode and Fan at the same time Note Allow a minimum of 5 seconds after saving selections Step 99 SA for the control to write selections to memory If power is lost or removed prior to the 5 second elapsed time the selections may be lost and must be reentered If the SERVICE icon is flashing on the cont...

Страница 4: ...OFF Table 2 T deg F RESISTANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62 3 60 15 3 105 5 2 15 53 5 65 13 5 110 4 7 20 46 1 70 11 9 115 4 2 25 39 8 75 10 5 120 3 8 30 34 5 Figure 8 2 Set Fan to AUTO 3 Pr...

Страница 5: ...Temp OT2 O D Sensor Note C For Dual Fuel cut the JP1 jumper on the Comfort Control NOTE See Fig OIL 1 for external relay connections for oil furnaces R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL DUAL FUEL ONE OR TWO STAGE OR TWO STEP HEAT PUMP TWO STAGE VS GAS FURNACE BK ENABLED FAN SOV COOL HEAT 1st STAGE HEATING 3rd STAGE HEATING 4th STAGE W2 O R G W2 Y1 YLO Y1 B ONE OR TWO STAGE OR TWO ...

Страница 6: ...AT 1st STAGE HEATING 2nd STAGE HEATING 3rd STAGE W2 O W3 Y2 BK R G W W1 W2 Y Y B SINGLE STAGE HEAT PUMP O R T NON V S ONE OR TWO STAGE GAS FURNACE B C X2 O D Temp OT1 O D Temp OT2 O D Sensor Note C For Dual Fuel cut the JP1 jumper on the Comfort Control NOTE See Fig OIL 1 for external relay connections for oil furnaces Figure DF 5 P2 JP1 Cut for Dual Fuel Applications JP 1 Location ...

Страница 7: ...IL VARIABLE SPEED AIR HANDLER BK ENABLED FAN SOV COOL HEAT 1st STAGE HEATING 3rd STAGE HEATING 4th STAGE W2 O R G W1 W2 Y1 YLO Y B TWO SEPARATE HEAT PUMPS VS AIR HANDLER ELECTRIC HEAT W3 HEATING 5th STAGE Y2 COOL HEAT 2nd STAGE BK VS MODE fan Y Y2 Y BK B SECOND STAGE FIRST STAGE X2 O O X2 A B 9 6 3 7 4 R R B O D Temp OT1 O D Temp OT2 O D Sensor T T W3 O Note B Cut remove the factory installed BK j...

Страница 8: ...E BK Y Y2 Y1 BK W3 O O R O D Temp OT1 O D Temp OT2 O D Sensor T X2 Note A The installer must jumper R to O at the LVTB Note B Cut remove the factory installed BK jumper at the indoor unit R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL SINGLE STAGE HEAT PUMP VARIABLE SPEED AIR HANDLER BK DISABLED FAN SOV COOL HEAT 1st STAGE HEATING 2nd STAGE HEATING 3rd STAGE W2 O R G W1 W2 Y1 YLO B SINGLE ST...

Страница 9: ... W1 B 24VAC HOT 24VAC common COMFORT CONTROL TWO STEP COOLING VARIABLE SPEED INDOOR BK DISABLED FAN COOLING 1st HEATING 1st HEATING 2nd W2 O R G W1 W2 Y1 YLO B TWO STEP AIR CONDITIONER TWO STAGE VS GAS FURNACE or VS AIR HANDLER ELECTRIC HEAT B C W3 HEATING 3rd Y2 COOLING 2nd BK Y Y2 Y1 BK O Y2 W3 Note A The installer must jumper R to O at the LVTB Note B Cut remove the factory installed BK jumper ...

Страница 10: ...ections for oil furnaces NOTE Two additional wires are required for Outdoor Temperature Sensor Figure CL 5 Figure CL 7 Figure CL 6 Figure OIL 1 R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL SINGLE STAGE COOLING SINGLE STAGE OIL FURNACE BK DISABLED FAN COOLING HEATING W2 O R G W W2 Y Y B SINGLE STAGE AIR CONDITIONER SINGLE STAGE OIL FURNACE B C W3 Y2 BK W3 R1 R1 NOTE Two additional wires are...

Страница 11: ...ancel CL Clears History and Service Data only CS Clears Setups FD Factory Default 99 Exit Table 3 INSTALLER SETUP ISU see notes at the bottom of setup ISU Table 3A 1 Set System MODE to OFF 2 Set FAN to AUTO 3 Press and hold MODE and Up arrow at the same time Menu Item Factory Setting Setting Choices Press UP or DOWN arrow Step Press Mode Fan Error Count 0 None 1 Software Version None 2 Configurati...

Страница 12: ...ages 0 None Steps 28 33 38 39 43 44 46 49 not available Step 9 Heater Stages 1 Single Stage Steps 30 33 48 49 not available Step 9 Heater Stages 2 Two Stage Steps 32 33 49 not available Step 10 Outdoor Sensor 0 None Steps 40 49 60 not available Step 10 Outdoor Sensor 1 Display Only Steps 41 49 not available Step 11 BK Output 0 BK Disabled Steps 12 15 40 not available Step 11 BK Output 1 BK Enabled...

Страница 13: ...es Oversized heating or cooling equipment Control cannot respond fast enough to prevent overshooting Set Control Response rate to Fast ISU Step 34 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or system 4 Heating system requires service or control requires replacement 1 Set Mode to heat and raise the setpoint above room...

Страница 14: ...rrides ISU Step 45 when enabled Cooling Efficiency Booster Single Stage Compressor Only BK Enabled The indoor air flow is reduced to 80 at outdoor temperatures below 87 F in cooling mode The outdoor temperature sensor must be installed and enabled in ISU Step 10 Control Response Rate A set of higher gain Proportion Integral control constants can be chosen to increase the responsiveness of the temp...

Страница 15: ...the system Minimum off time delays will be enforced on the next cycle Wait Indicator Waiting will illuminate when the indoor setpoint is moved in the direction of calling for additional system capacity Waiting indicates system time delays are being enforced and that the control is adjusting to the new settings Calibrate Indoor Temperature This option allows calibration of the room temperature sens...

Страница 16: ...ransition from furnace operation to heat pump operation there is a minimum comfort control time delay of 45 seconds between the furnace turning off and the heat pump turning on RESTRICTED MODE Requires Outdoor Temperature Sensor The Heat Pump Restricted Mode Outdoor Temperature changeover point ISU Step 43 must be set at or above the application or economic balance point of the system At any tempe...

Страница 17: ...Pub No 11 HD03D3 3 17 Installer s Guide ...

Страница 18: ...y of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75707 For more information contact your local dealer distributor ...

Отзывы: