![American Standard ACONT402AN32DA Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/american-standard/acont402an32da/acont402an32da_installers-manual_2929803011.webp)
Pub. No. 11-HD03D3-3
11
Installer’s Guide
2nd Stage Compressor
Heating Cycles Per Hour
3
2 - 6 CPH
26
2nd Stage Compressor Heating
Minimum On Time
3
1 - 15 Minutes
27
1st Stage Heater
Cycles Per Hour
3
2 - 6 CPH
28
1st Stage Heater
Minimum ON Time
3
1 - 15 Minutes
29
2nd Stage Heater
Cycles Per Hour
5
2 - 6 CPH
30
2nd Stage Heater
Minimum ON Time
3
1 - 15 Minutes
31
3rd Stage Heater
Cycles Per Hour
5
2 - 6 CPH
32
3rd Stage Heater Minimum ON Time
3
1 - 15 Minutes
33
Control Response Rate
0
0=Normal, 1=Fast
34
Aggressive Recovery Due To A
Setpoint Change > 2 Degrees F
0
0=Disabled,1=Enabled
35
Remote Indoor Sensor
0
0=None,1=Has Sensor
36
Humidistat For Dehumidification
0
0=Disabled,1=Enabled
37
Wet Heat Blower ON Delay
30
0 - 60 Seconds
38
Wet Heat Blower OFF Delay
30
0 - 90 Seconds
39
Cooling Efficiency Booster - Single
Stage Compressor Only
0
0=Disabled,1=Enabled
40
Outdoor Sensor for Control -
Temperature Units (Steps 43-49)
0
0=Fahrenheit,1=Celsius
41
Heat Pump Restricted Mode
Outdoor Temperature
"--"
then
40
"--" = Disabled
10 to 70 Degrees F
43
4.5
-12 to 21 Degrees C
Resume Heat Pump Operation
Outdoor Temperature
"--"
then
44
"--" = Disabled
14 to 74 Degrees F
44
6.5
-10 to 23 Degrees C
Heating Aggressive Recovery
Outdoor Temperature
"--"
then
40
"--" = Disabled
10 to 70 Degrees F
45
4.5
-12 to 21 Degrees C
Auxilliary Heat Lockout
Outdoor Temperature
"--"
then
45
"--" = Disabled
15 to 75 Degrees F
46
7
-9 to 24 Degrees C
W1 Heater Balance Point During
Defrost Outdoor Temperature
"--"
then
55
"--" = Disabled
-10 to 55 Degrees F
47
13
-23 to 13 Degrees C
W2 Heater Balance Point During
Defrost Outdoor Temperature
"--"
then
40
"--" = Disabled
-10 to 55 Degrees F
48
4.5
-23 to 13 Degrees C
W3 Heater Balance Point During
Defrost Outdoor Temperature
"--"
then
25
"--" = Disabled
-10 to 55 Degrees F
49
-4
-23 to 13 Degrees C
Exit Installer Setup
Press $ to advance to step 99
SA
SA = Save
CA = Cancel
CL = Clears History and Service Data only
CS = Clears Setups
FD = Factory Default
99
(Exit)
Table 3 INSTALLER SETUP (ISU)
*see notes at the bottom of setup (ISU) Table 3A
1. Set System MODE to OFF
2. Set FAN to AUTO
3. Press and hold MODE and Up arrow at the same time.
Menu Item
Factory
Setting
Setting (Choices)
(Press UP or DOWN arrow)
Step
(Press
Mode
Fan)
Error Count
0
None
1
Software Version
None
2
Configuration
Signature - LoByte
None
3
Configuration
Signature - HiByte
None
4
System Type
1
1=AC,2=HP
5
Compressor Stages
2
0=None
1=Single Stage
2=Two Stage/Two Step
6
Compressor Type
0
0=Two Step, 1=Two Stage
7
Indoor Heater Type
1
1=Gas,Oil
2=Electric
3=Wet Heat
8
Indoor Heater Stages
2
0=None
1=Single Stage Heater
2=Two Stage Heater
3=Three Stage Heater
9
Outdoor Sensor
0
0=None
1=Has Sensor for Display Only
2=Has Sensor for Display and for Control
10
BK Output
1
0 = BK Disabled
1 = BK Enabled
11
Variable Speed Blower
Turn-On Delay Profile
1
1 = No Delay
2 = 1 Minute @ 50%, 7.5 Minutes @ 80%
3 = 1 Minute @ 50%, 4 Minutes @ 80%
4 = 7.5 Minutes @ 80%
5 = 4 Minutes @ 80%
6 = 1 Minute @ 50%
7 = 30 Second Delay
12
Variable Speed Blower
Turn-Off Delay Profile
1
1 = No Delay
2 = 1.5 Minutes @ 100%
3 = 45 Seconds @ 100%
4 = 30 Seconds @ 50%
5 = 1.5 Minutes @ 50%
6 = 3 Minutes @ 50%
7 = 30 Seconds @ 35%
13
Compressor
Low Stage Airflow
65%
Two Step Range: 55%-80%
14
50%
Two Stage Range: 35%-60%
Heat Pump Warm Air Discharge
0
0=Disabled,1=Enabled
15
Non-Variable Speed
Cooling Blower ON delay
0
0 - 30 Seconds
16
Non-Variable Speed
Cooling Blower OFF delay
0
0 - 90 Seconds
17
Non-Variable Speed Compressor
Heating Blower ON delay
0
0 - 30 Seconds
18
Non-Variable Speed Compressor
Heating Blower OFF delay
0
0 - 90 Seconds
19
1st Stage Compressor
Cooling Cycles Per Hour
3
2 - 6 CPH
20
1st Stage Compressor Cooling
Minimum On Time
3
1 - 15 Minutes
21
2nd Stage Compressor
Cooling Cycles Per Hour
3
2 - 6 CPH
22
2nd Stage Compressor Cooling
Minimum On Time
3
1 - 15 Minutes
23
1st Stage Compressor
Heating Cycles Per Hour
3
2 - 6 CPH
24
1st Stage Compressor Heating
Minimum On Time
3
1 - 15 Minutes
25