![American Standard ACONT402AN32DA Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/american-standard/acont402an32da/acont402an32da_installers-manual_2929803012.webp)
12
Pub. No. 11-HD03D3-3
Installer’s Guide
Note: Pressing the Energy Savings Key ($) anytime during setup
will advance to “step 99.”
Step 99 - Make setting selection and then press MODE to exit.
CAncel = Cancel Selections for current session and return to
previous session selections.
SAve = Save selections
USer = Default User settings
Steps 16 & 18: With BK Output disabled, do not select a Comfort
Control Blower On-Delay if an Enhanced (Comfort-R) airflow profile
is selected at the variable speed indoor unit.
Steps 17 & 19: With BK Output disabled, do not select a Comfort
Control Blower Off-Delay if a blower off delay is selected at the
indoor unit.
Step 5 System Type = 1 (AC): Steps 15, 18-19, 24-27, 41-49 not
available.
Step 5 = 1 and Step 6 = 1 (1C): Step 35 not available.
Step 5 = 2 and Step 6 = 1 and Step 9 = 0 (1H/1C HP): Steps 35, 45
not available.
Step 5 = 1 and Step 9 = 0 (0H/1C): Steps 51-52 not available.
Step 5 = 2 and Step 8 = 1 (Dual Fuel): Step 47 not available.
Step 5 = 2 (HP): Step 6 (Compressor Stages) cannot be set to “0”.
Changing Step 5 to “2” will force the settings for Steps 6, 8, and 9.
Step 6 Compressor Stages = 0 (None): Steps 7, 12-27, 35, 37, 40-
49, 51-52, 54 not available.
Step 6 Compressor Stages = 1 (Single Stage): Steps 7, 14, 22-23,
26-27 not available.
Step 6 Compressor Stages = 2 (Two Stage/Two Step): Step 40 not
available.
Step 8 Heater Type = 1 (Gas/Oil): Steps 38-39 not available.
Step 8 Heater Type = 2 (Electric): Steps 38-39 not available.
Step 8 Heater Type = 3 (Wet Heat): Steps 32-33, 49 not available.
Step 9 Heater Stages = 0 (None): Steps 28-33, 38-39, 43-44, 46-49
not available.
Step 9 Heater Stages = 1 (Single Stage): Steps 30-33, 48-49 not
available.
Step 9 Heater Stages = 2 (Two Stage): Steps 32-33, 49 not
available.
Step 10 Outdoor Sensor = 0 (None): Steps 40-49, 60 not available.
Step 10 Outdoor Sensor = 1 (Display Only): Steps 41-49 not
available.
Step 11 BK Output = 0 (BK Disabled): Steps 12-15, 40 not available.
Step 11 BK Output = 1 (BK Enabled): Steps 16-19 not available.
Step 36 Remote Indoor Sensor = 0 (None): Step 61 not available.
Step 43 HP Restricted Mode = “—“: Step 44 not available.
TABLE 3A USER SETUP (USU)
Press and hold MODE and FAN at the same time.
Menu Item
Default
Setting (Choices)
(Press UP or DOWN arrow)
Step
(Press
Mode or
Fan)
Temperature Display
0
0=Fahrenheit,1=Celsius
50
Auto or Manual Changeover
1
0=Manual,1=Auto
51
Setpoint Deadband
3
2 - 10 Degrees Fahrenheit
1.5 - 5.0 Degrees Celsius
52
Waiting Icon
1
0=Disable,1=Enable
53
Cooling Droop
1
0 = Off
1 = 1 Degree
2 = 2 Degrees
54
Energy Savings -
Cooling Setpoint Offset
5
0 - 25 Degrees Fahrenheit
0 - 15 Degrees Celsius
55
Energy Savings -
Heating Setpoint Offset
5
0 - 45 Degrees Fahrenheit
0 - 25 Degrees Celsius
56
Indoor Filter Timer Method
0
0=Calender Days,1=Fan RunTime
Days
57
Indoor Filter Reminder - Days
30
1-180 Days,0=Disabled
58
Calibrate Indoor Temperature
0
Calibrated Room Temperature
+ / - 5 Degrees (1/2 degree
increments)
59
Calibrate Outdoor Temperature
0
Calibrated Outdoor Temperature
+ / - 5 Degrees (1/2 degree
increments)
60
Calibrate Remote
Indoor Temperature
0
Calibrated Room Indoor Temperature
+ / - 5 Degrees (1/2 degree
increments)
61
Continous Fan Airflow
50%
35%-100%
62
Exit User Setup
(Press Mode)
SA
CA = Cancel
SA = Save
US = Default User Settings
99
(Exit)