American Standard ACONT402AN32DA Скачать руководство пользователя страница 14

14

Pub. No.  11-HD03D3-3

Installer’s Guide

Features

BK Output

With the BK Output enabled (the factory default) the
Comfort Control sends a Pulse Width Modulated (PWM)
signal to Variable Speed indoor units for directly
controlling the indoor air flow between 35% and 100%.

With the BK Output enabled, the following features
are available:

       •    

Simplified control wiring for two step and two

stage equipment

      •

Cooling Efficiency Booster for single stage
equipment (ISU Step 40)

       

User selectable Continuous Fan air flow rate

       

A wider selection of turn-on and turn-off delay
profiles selectable from the Comfort Control (ISU
Steps 12 & 13)

      •

Warm Air Discharge mode for heat pump heating
(ISU Step 15)

      •

Reduced air flow during Cooling Droop

      •

Enhanced humidity removal when using a
humidistat connected to the Comfort Control (ISU
Step 37)

      •

Variable air flow control for Wet Heat heating
applications

      •

Installer selectable first stage compressor air flow
(ISU Step 14)

When the BK Output is used, the 350/400/450 cfm/ton
setting on the variable speed indoor unit still applies for
determining the final air flow.

NOTE: In order to use the BK Output, the R to BK jumper
must be cut or removed, the indoor unit dip switches 5 & 6
should be set to the OFF position, the “Y” terminals on the
indoor unit are NOT connected, and a BK wire must be
added from the Comfort Control to the Variable Speed
indoor unit.

When the BK Output is disabled, there is not a PWM
signal from the Comfort Control, and standard 24V
connections are made to the Y1 and Y2 terminals of the
indoor unit for determining the indoor air flow.

Adjustable Continuous Air flow – BK Enabled

The Continuous Fan air flow is user adjustable from 35%
to 100% in 5% increments either by entering User Setup
Mode or by holding down the Fan key for a few seconds
(Quick Setup).

Heat Pump Warm Air Discharge - BK Enabled

The indoor air flow is reduced to 77% for each compressor
heating stage for delivery of warmer discharge air.

Aggressive Recovery

The 10 minute delay between compressor stages and
between the highest compressor stage and the first stage of
auxiliary heat is defeated when there is a setpoint change
resulting in a temperature error of 2 degrees or more.  ISU
Step 35 is for both heating and cooling, and overrides ISU
Step 45 when enabled.

Cooling Efficiency Booster - (Single Stage Compressor
Only) - BK Enabled

The indoor air flow is reduced to 80% at outdoor
temperatures below 87°F in cooling mode.  The outdoor
temperature sensor must be installed and enabled in ISU
Step 10.

Control Response Rate

A set of higher gain Proportion-Integral control constants
can be chosen to increase the responsiveness of the
temperature control performance.

Cycle Rate

The selected number of system cycles per hour. If the cycle
rate were set to 3, each cycle would be 20 minutes long
when operating at a 50% load value. The total ON and/or
OFF times depends on actual indoor space load. A shorter
cycle rate (more cycles per hour) may be desired for Heating
in order to maintain a tighter control on indoor setpoint. A
longer cycle rate may be desirable for Cooling so the
system has the opportunity to remove moisture from the
air and improve indoor comfort.

Auto Changeover

When the system mode is set to AUTO, the control
automatically switches between heating and cooling modes
to maintain the desired comfort level.

Setpoint Deadband

The number of degrees separating Heating and Cooling
setpoints. The amount of separation between mode
setpoints is user defined between 2 and 10 degrees. When
the control is set to AUTO, and the cooling setpoint is
changed to a cooler setting, the heating setpoint also
changes to maintain the selected degrees separation. The
same action occurs when the heating setpoint is changed to
a warmer temperature.

Backlit Display & Keys

The liquid crystal display and the keypad will illuminate
whenever a keypad button is pressed to improve control
visibility.  The back light stays on for 20 seconds after the
last key press.

Cooling Droop

Cooling Droop is an automatic function that cycles the
compressor on to improve indoor comfort by removing
moisture from the air. The Droop cycle is activated when
the room temperature is at or below the cooling setpoint.
When this function is active, the control will control
temperature at 1 or 2 degrees below cooling setpoint. The
Droop cycle is deactivated when the temperature rises
above the cooling setpoint.  When the BK output is
enabled, the air flow is reduced to 80% during cooling droop
operation.

Energy Savings 

 $

The Energy Savings mode provides  energy savings by
offsetting the indoor setpoint to a cooler temperature
setting for heating and a warmer temperature setting for
cooling.

Содержание ACONT402AN32DA

Страница 1: ...ER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which could result in minor personal injury or product and property damage Note Read the entire instruction manu...

Страница 2: ...se non hardening caulk putty or insulation 3 Avoid locations such as near dryer vents or placing the sensor close to or directly above the outdoor unit where it would be exposed to hot discharge air from the condenser fan 4 Maximum length of field wiring cable to sensor is 200 feet 5 Minimum wire gauge is 18AWG Mounting and Wiring 1 Turn OFF all power to heating and cooling equipment 2 If an exist...

Страница 3: ...on display See Figure 6 Enter USER Setup See Table 3A steps 50 62 for option details Press and hold Mode and Fan at the same time Note Allow a minimum of 5 seconds after saving selections Step 99 SA for the control to write selections to memory If power is lost or removed prior to the 5 second elapsed time the selections may be lost and must be reentered If the SERVICE icon is flashing on the cont...

Страница 4: ...OFF Table 2 T deg F RESISTANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62 3 60 15 3 105 5 2 15 53 5 65 13 5 110 4 7 20 46 1 70 11 9 115 4 2 25 39 8 75 10 5 120 3 8 30 34 5 Figure 8 2 Set Fan to AUTO 3 Pr...

Страница 5: ...Temp OT2 O D Sensor Note C For Dual Fuel cut the JP1 jumper on the Comfort Control NOTE See Fig OIL 1 for external relay connections for oil furnaces R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL DUAL FUEL ONE OR TWO STAGE OR TWO STEP HEAT PUMP TWO STAGE VS GAS FURNACE BK ENABLED FAN SOV COOL HEAT 1st STAGE HEATING 3rd STAGE HEATING 4th STAGE W2 O R G W2 Y1 YLO Y1 B ONE OR TWO STAGE OR TWO ...

Страница 6: ...AT 1st STAGE HEATING 2nd STAGE HEATING 3rd STAGE W2 O W3 Y2 BK R G W W1 W2 Y Y B SINGLE STAGE HEAT PUMP O R T NON V S ONE OR TWO STAGE GAS FURNACE B C X2 O D Temp OT1 O D Temp OT2 O D Sensor Note C For Dual Fuel cut the JP1 jumper on the Comfort Control NOTE See Fig OIL 1 for external relay connections for oil furnaces Figure DF 5 P2 JP1 Cut for Dual Fuel Applications JP 1 Location ...

Страница 7: ...IL VARIABLE SPEED AIR HANDLER BK ENABLED FAN SOV COOL HEAT 1st STAGE HEATING 3rd STAGE HEATING 4th STAGE W2 O R G W1 W2 Y1 YLO Y B TWO SEPARATE HEAT PUMPS VS AIR HANDLER ELECTRIC HEAT W3 HEATING 5th STAGE Y2 COOL HEAT 2nd STAGE BK VS MODE fan Y Y2 Y BK B SECOND STAGE FIRST STAGE X2 O O X2 A B 9 6 3 7 4 R R B O D Temp OT1 O D Temp OT2 O D Sensor T T W3 O Note B Cut remove the factory installed BK j...

Страница 8: ...E BK Y Y2 Y1 BK W3 O O R O D Temp OT1 O D Temp OT2 O D Sensor T X2 Note A The installer must jumper R to O at the LVTB Note B Cut remove the factory installed BK jumper at the indoor unit R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL SINGLE STAGE HEAT PUMP VARIABLE SPEED AIR HANDLER BK DISABLED FAN SOV COOL HEAT 1st STAGE HEATING 2nd STAGE HEATING 3rd STAGE W2 O R G W1 W2 Y1 YLO B SINGLE ST...

Страница 9: ... W1 B 24VAC HOT 24VAC common COMFORT CONTROL TWO STEP COOLING VARIABLE SPEED INDOOR BK DISABLED FAN COOLING 1st HEATING 1st HEATING 2nd W2 O R G W1 W2 Y1 YLO B TWO STEP AIR CONDITIONER TWO STAGE VS GAS FURNACE or VS AIR HANDLER ELECTRIC HEAT B C W3 HEATING 3rd Y2 COOLING 2nd BK Y Y2 Y1 BK O Y2 W3 Note A The installer must jumper R to O at the LVTB Note B Cut remove the factory installed BK jumper ...

Страница 10: ...ections for oil furnaces NOTE Two additional wires are required for Outdoor Temperature Sensor Figure CL 5 Figure CL 7 Figure CL 6 Figure OIL 1 R G Y Y1 W1 B 24VAC HOT 24VAC common COMFORT CONTROL SINGLE STAGE COOLING SINGLE STAGE OIL FURNACE BK DISABLED FAN COOLING HEATING W2 O R G W W2 Y Y B SINGLE STAGE AIR CONDITIONER SINGLE STAGE OIL FURNACE B C W3 Y2 BK W3 R1 R1 NOTE Two additional wires are...

Страница 11: ...ancel CL Clears History and Service Data only CS Clears Setups FD Factory Default 99 Exit Table 3 INSTALLER SETUP ISU see notes at the bottom of setup ISU Table 3A 1 Set System MODE to OFF 2 Set FAN to AUTO 3 Press and hold MODE and Up arrow at the same time Menu Item Factory Setting Setting Choices Press UP or DOWN arrow Step Press Mode Fan Error Count 0 None 1 Software Version None 2 Configurati...

Страница 12: ...ages 0 None Steps 28 33 38 39 43 44 46 49 not available Step 9 Heater Stages 1 Single Stage Steps 30 33 48 49 not available Step 9 Heater Stages 2 Two Stage Steps 32 33 49 not available Step 10 Outdoor Sensor 0 None Steps 40 49 60 not available Step 10 Outdoor Sensor 1 Display Only Steps 41 49 not available Step 11 BK Output 0 BK Disabled Steps 12 15 40 not available Step 11 BK Output 1 BK Enabled...

Страница 13: ...es Oversized heating or cooling equipment Control cannot respond fast enough to prevent overshooting Set Control Response rate to Fast ISU Step 34 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or system 4 Heating system requires service or control requires replacement 1 Set Mode to heat and raise the setpoint above room...

Страница 14: ...rrides ISU Step 45 when enabled Cooling Efficiency Booster Single Stage Compressor Only BK Enabled The indoor air flow is reduced to 80 at outdoor temperatures below 87 F in cooling mode The outdoor temperature sensor must be installed and enabled in ISU Step 10 Control Response Rate A set of higher gain Proportion Integral control constants can be chosen to increase the responsiveness of the temp...

Страница 15: ...the system Minimum off time delays will be enforced on the next cycle Wait Indicator Waiting will illuminate when the indoor setpoint is moved in the direction of calling for additional system capacity Waiting indicates system time delays are being enforced and that the control is adjusting to the new settings Calibrate Indoor Temperature This option allows calibration of the room temperature sens...

Страница 16: ...ransition from furnace operation to heat pump operation there is a minimum comfort control time delay of 45 seconds between the furnace turning off and the heat pump turning on RESTRICTED MODE Requires Outdoor Temperature Sensor The Heat Pump Restricted Mode Outdoor Temperature changeover point ISU Step 43 must be set at or above the application or economic balance point of the system At any tempe...

Страница 17: ...Pub No 11 HD03D3 3 17 Installer s Guide ...

Страница 18: ...y of continuous product and product data improvement it reserves the right to change design and specifications without notice AmericanStandardInc 6200TroupHighway Tyler TX75707 For more information contact your local dealer distributor ...

Отзывы: