18-GE10D1-5
7
Installer’s Guide
Figure 12 Drip Tray Bracket Removal
Figure 11 Horizontal Drip Tray Removal
Rail
Figure 13 Mounting Installation Options
h. Remove the front triangular baffle from the coil
and install the 1/2" wide gasket provided per Fig-
ure 14. Trim the gasket length to fit the baffle.
Reinstall the baffle to coil, with gasket material
compressed against the coil.
i. Install the water blow-off baffles provided on each
side of the coil with the flange at the top as
shown in Figure 14. The bottom of the baffle is to
be as close to the bottom of the coil as possible.
j. Install the 7/8" wide gasket in each side of the
drain pan as shown in Figure 14 (sect. X-X).
k. The 5 ton model (2/4TEE3D65) requires 2 water
diverter baffles to be placed underneath the coil
on the inside edge of the drain pan. See Figure
14. Fill the bend in the baffle which fits the in-
ner edge of the drain pan with non-acetic acid
RTV type adhesive/sealant before installing the
baffle. Ensure sealant is dry/set before reinstall-
ing the coil.
l. The unit is then placed with the blower side
down and the coil is replaced on the coil channel
supports with the drain connections at the bot-
tom. The unit is now in downflow position with
front access. Do not reattach coil support tab.
m. When supplementary heaters are used, accessory
subbase (TAYBASE101 for 2/4TEE3D31, TAY-
BASE100 for 2/4TEE3D37, and TAYBASE102 for
2/4TEE3D40-65) must be used. See Figure 1.
n. If a return duct is connected to the air handler, it
must be the same dimensions as the return
opening shown in the outline drawing on page
20.
o.
On units with sheet metal returns: Return
plenum must be flanged. Sheetmetal screws
must be 1/2" in length or shorter. Self-tap-
ping screws are supplied with the unit in
accessory packet.
See Figure 17.