N. CLEANING THE FIELD CHARGER
1.
Turn the air conditioning system to the off position
at the Comfort Control. Loosen thumbscrews to re-
move the filter panel. Remove the COLLECTION
CELL by pulling forward. See Figure 6.
2.
Use a 5/16" nutdriver to remove the screws holding
the FIELD CHARGER retainer bracket. See Fig-
ures 7 and 8.
3.
Remove the FIELD CHARGER from the unit. Lay
the FIELD CHARGER on a secured flat surface.
▲
CAUTION
!
FIELD CHARGER PINS ARE SHARP. DO NOT BEND
FIELD CHARGER PINS. WEAR APPROPRIATE
GLOVES WHEN HANDLING THE FIELD CHARGER.
4.
Wipe down the face plate of the FIELD CHARGER
with a dry shop towel or use a vacuum cleaner.
NOTE:
Do NOT disassemble the FIELD CHARGER.
5
Push a block of foam down over the FIELD
CHARGER Pin as in Figure 28.
6.
Rotate the foam block on the FIELD CHARGER
Pin. See Figure 29.
7.
Use the foam block to clean the faceplate opening
edges.
8.
Repeat steps 5,6 and 7 for each FIELD CHARGER
Pin.
9.
Put FIELD CHARGER back into the air handler
and secure the FIELD CHARGER in place with the
retainer bracket. See Figure 7.
10. Reinstall COLLECTION CELL.
11. Put filter panel back in place.
LED
High Voltage switch
9.6 to 8.0 KVDC
Return from air cleaner
High voltage power lead
24 VAC Hot
24 VAC Common
9.6 KVDC is right side down
8.0 KVDC is left side down
Green
Pink
Red
Blue
|/
|\
Figure 27
Figure 28
Figure 29
in water.
• Do NOT place the COLLECTION CELL into a dish-
washer to clean.
• ALLOW THE COLLECTION CELL TO DRY THOR-
OUGHLY BEFORE REINSTALLING.
Slightly tap the COLLECTION CELL to remove
water retained. Allow the COLLECTION CELL to
completely
dry before reinstalling.