background image

CABLE CONNECTIONS

Code Line Connections 

The Control Code line connection to the receiver is made with
user-supplied, shielded 2-wire twisted pair, Belden 8760 or
equivalent (for Plenum, use Belden 88760 or equivalent).  The
maximum code line length is 5000 feet.

The code line connector, J4, is a 4-position terminal strip
located near the rotary switches S1 through S16 (see Figure 1
or OP0064, OP0065 or OP0066).  The PCB is marked B (black
code), W (white code), and S (shield) for the pin positions of
this connector.

Before starting:

1. Check power line to verify the power is off.

2. Open the receiver and find the code terminal connector,

located on the PCB, labeled J4.

Wiring:

1. Pass the code wire through the bushing to the code

connector.  Do not tighten bushing.

2. Insert the Black Code wire into the screw terminal marked

B.

3. Insert the White Code wire into the screw terminal marked

W.

4. Insert the Shield wire into the screw terminal marked S.

5. Remove any excess cable and tighten the bushing.

The 1689B receiver has a 120-ohm terminating resistor
installed on the PCB and is designed for “Star” or “Home
Run” connection to a code distribution unit (see Figure 3). 

If the receiver is to be used in a “daisy chain,” the 120-ohm
terminating resistor must be removed from all but the last
receiver (see Figure 4).  A 120 ohm termination must be
provided on the last piece of equipment on each line.

The 120-ohm resistor for the 1689B is located on the PCB in
the lower left corner of the board and is designated R1.

The green Code LED on these receivers is lit when the unit is
receiving valid code.  A flickering Code LED indicates a
problem in the transmission of the code, poor or loose
connections, improper termination, or a defective receiver.

CONNECTIONS

4

REC

*

REC

*

REC

*

* 120 Ohm Termination

Code

Distribution

Unit

Receiver

Receiver

Receiver

Code

Distribution

Unit

W    B     S

W    B     S

W    B     S

Figure 3 - Code Distribution Unit "Star" Connection

Figure 4 - Code Line “Daisy Chain” Connections

CAUTION - Due to the presence of non-insulated

components with hazardous voltages, the

following internal adjustments should be

performed by qualified service personnel only.

Содержание 1689B

Страница 1: ...torized pan tilt unit and a motorized lens unit Since camera sites are often a great distance from the operator s viewing location these receivers provide the operator with positive control of the camera site Receivers also provide the operator with control of auxiliary devices such as lights doors etc at the camera site Receivers are individually coded for each camera site so only the camera unde...

Страница 2: ...urchaser under a license for use on a single system NOTE Information furnished by SENSORMATIC is believed to be accurate and reliable However no responsibility is assumed by SENSORMATIC for its use nor for any infringements of other rights of third parties which may result from its use No license is granted by implications or otherwise under any patent or patent rights of SENSORMATIC Copyright 199...

Страница 3: ...ved with the packing list with your order Be sure to save 1 The shipping cartons and insert pieces They are the safest material in which to make future shipments of the product 2 The IMPORTANT SAFEGUARDS sheet 3 These Installation and Operating Instructions M M M MA A A AI I I IN N N NT T T TE E E EN N N NA A A AN N N NC C C CE E E E User maintenance of this unit is limited to external cleaning an...

Страница 4: ......

Страница 5: ...Table of Contents Product Description 1 Features 1 Setup 2 Installation 3 Cable Connections 4 ...

Страница 6: ......

Страница 7: ...ired for control of the Pan Tilt and lens Note Certain Pan Tilt units require alternate voltages other than those noted in this manual If necessary call the Technical Support Department for information or assistance 1 800 442 2225 Table 1 Pan Tilt and Lens Ratings Function Voltage Current note 1 Pan Motor 24 VAC 2 Amps Tilt Motor 24 VAC 2 Amps Iris Motor 10 VDC 05 Amps Focus Motor 10 VDC 05 Amps Z...

Страница 8: ...e second connector J201 OUT 2 set S3 to 0 and S4 to 2 To access this auxiliary from the CPU enter 02 when asked for the camera number Note A camera identifier number cannot be assigned to more than one camera channel and an auxiliary number cannot be assigned to more than one auxiliary channel Camera Identifier Conversion Camera identifiers for Control Code Receivers are set to 1 64 only Table 2 b...

Страница 9: ... should be mounted near the camera s to be controlled to minimize voltage drop in the wiring The housing is a standard NEMA 4 fiberglass reinforced polyester non corrosive enclosure The housing size is 17 5 H x 14 8 W x 6 7 D Mount the unit with four 1 4 bolts appropriate to the type of mounting surface See Figure 2 below for mounting dimensions For mounting to wood studs use lag bolts with a dril...

Страница 10: ...d tighten the bushing The 1689B receiver has a 120 ohm terminating resistor installed on the PCB and is designed for Star or Home Run connection to a code distribution unit see Figure 3 If the receiver is to be used in a daisy chain the 120 ohm terminating resistor must be removed from all but the last receiver see Figure 4 A 120 ohm termination must be provided on the last piece of equipment on e...

Страница 11: ...sed pins to the ends of the Pan Tilt and Lens wires For steps 5 through 15 refer to OP0064 OP0065 or OP0066 for pinouts Pan Tilt 5 Insert the Pan Right wire of the Pan Tilt unit into the pin location for Pan Right 6 Insert the Pan Left wire of the Pan Tilt unit into the pin location for Pan Left 7 Insert the Tilt Up wire of the Pan Tilt unit into the pin location for Tilt Up 8 Insert the Tilt Down...

Страница 12: ...ach auxiliary 8 Remove any excess cable and tighten the bushing Note Do not connect the 24 VAC Auxiliary Commons to the line VAC Commons Preposition Cable The connections to the Pan Tilt units are with 9 pin connectors labeled J1 to J8 on the upper board see OP0094 If the unit is configured for four auxiliaries use OP0095 If eight auxiliaries are used no presets are allowed Before Starting 1 Check...

Страница 13: ...green to the Green ground screw marked GND 3 Connect the Hot wire black to the terminal block terminal marked HOT 4 Connect the Neutral wire white to the terminal block terminal marked NEUTRAL 5 Remove any excess power cable and tighten the bushing 6 Turn on the AC power 7 Check the red LED If it is illuminated the unit is powered If the LED is off check the power and the fusing Wiring 230 VAC Mod...

Страница 14: ......

Страница 15: ...Appendix ...

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ...965 Business 845 624 7600 Technical Support Center 1 800 442 2225 FAX 845 624 7685 8000 0871 01 Rev E OP1689BE February 1998 Printed in USA SPECIFICATIONS Supply Voltage AD1689B 8 120 VAC 50 60 Hz AD1689B8 X 230 VAC 50 60 Hz Power 8 W Standby Mounting Surface Mount Size 17 5 H x 14 8 W x 6 7 D NEMA 4 enclosure Weight 18 lbs 8 kg ...

Отзывы: