21
2. Electrical Service Specifications
IMPORTANT:
The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the left side panel/wall area behind the control door. In the case of 208
VAC OR 230/240 VAC, the supply voltage must match the electric service
specifications of the data label
exactly
.
WARNING: 208 VAC AND 230/240 VAC ARE
NOT
THE
SAME
. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC
reserves the right to make changes in specifications at any time without notice or
obligation.
Electric – 72 kW
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw
rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
3ø
3
213.6
—
300
230
3ø
3
192.3
—
250
380
3ø
4
*
—
115.3
150
480
3ø
3
93.2
—
125
* Three wire is available.
9/10/08
* Three wire is available.
9/10/08
Gas and Steam
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
208
3ø
3
13.7
—
20
220
3ø
3
—
10.4
20
230
3ø
3
11.6
—
20
240
3ø
3
—
10.8
20
380
3ø
4
*
—
5.9
15
400 / 416
3ø
4
*
—
5.9
15
460 / 480
3ø
3
6.6
—
15