It is suggested that the ductwork from each dryer not exceed 20 feet (6.09 meters) with no more than two
(2) elbows (excluding dryer connections). If the ductwork exceeds 20 feet (6.09 meters) or has numerous
elbows, the cross-sectional area of the ductwork
must be
increased in proportion to the length and number
of elbows in it. In calculating duct size, the cross-sectional area of a square or rectangular duct
must be
increased twenty percent (20%) for each additional 20 feet (6.09 meters). The diameter of a round
exhaust duct
should be
increased ten percent (10%) for each additional 15 feet (4.57 meters). Each 90º
elbow is equivalent to an additional 40 feet (12.19 meters), and each 45º elbow is equivalent to an additional
20 feet (6.09 meters).