16
a. Outside Duct Work Protection
1) To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward
should be
installed where the exhaust exits the building. If the duct work travels vertically up
through the roof, it
should be
protected from the weather by using a 180° turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening
and the nearest obstruction.
IMPORTANT:
DO NOT
use screens or caps on the outside of opening of exhaust duct work.
2. Single Dryer Venting
Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct
should
be
laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns
as possible. It is suggested that the use of 90° turns in the ducting be avoided; use 30° and/or 45° angles
instead. The shape of the exhaust duct work is not critical so long as the minimum cross section area is
provided.
IMPORTANT:
Minimum duct size for a dryer is 12-inches (30.48 cm) for a round duct 10-3/4 x
10-3/4 (27.31 cm x 27.31 cm) for a square duct.
THE DUCT SIZE
MUST NOT
BE
REDUCED ANYWHERE DOWN STREAM OF THE DRYER.
IMPORTANT:
Exhaust back pressure measured by a manometer at each tumbler (basket) exhaust
duct area
should not
exceed
0.3 inches of water column (0.74 mb).
Содержание MLG-130DR (HSI)
Страница 45: ...ADC113130 1 03 28 00 25 ...