21
2. Electrical Service Specifications
IMPORTANT:
The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the left wall, behind the upper control door area (refer to the
illustration
on
page 9
). In the case of 208 VAC or 230 VAC, the supply voltage
must match
the
electric service specifications of the data label exactly.
WARNING: 208 VAC and 230 VAC
ARE
NOT
THE
SAME.
Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC
reserves the right to make changes in specifications at any time, without notice or
obligation.
M LG-130DR (Gas)
E
LECTRIC
S
ERVICE
S
PECIFICATIONS
(PER DRYER)
IMPORTANT: 208 VAC and 230 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTE:
A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
208
3ø
3/4
13
---
#12
20
25
230
3ø
3
13
15
#12
20
25
380
3ø
3/4
8
8
#12
12
15
416
3ø
3/4
---
8
#14
12
15
440
3ø
3/4
8
10
#14
12
15
460
3ø
3/4
7
---
#14
12
15
480
3ø
3/4
7
---
#14
12
15
* AWG Stranded Type Wire...for individual lengths less than 100 feet (31 meters).
(Motor lead type wire is recommended.)
Содержание MLG-130DR (HSI)
Страница 45: ...ADC113130 1 03 28 00 25 ...