![American Dryer Corp. MLG-130DR (HSI) Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/american-dryer-corp/mlg-130dr-hsi/mlg-130dr-hsi_installation-manual_2923503028.webp)
24
Type of Gas
Natural
Liquid Propane Gas
Manifold Pressure*
3.5 inches W.C.
8.7 mb
10.5 inches W.C.
26.1 mb
Inline Pressure
6.0 inches W.C.
14.9 mb
10.5 inches W.C.
26.1 mb
Shaded areas are stated in metric equivalents
* Measured at the gas valve pressure tap when the gas valve is on.
1. Gas Supply
The gas dryer installation
must meet
the American National Standard...National Fuel Gas Code ANSI
Z223.1-LATEST EDITION, or in Canada, the Canadian Installation Codes CAN/CGA-B149.1 M91 (Natural
Gas) or CAN/CGA-B149.2-M91 (L.P. Gas) or LATEST EDITION, as well as local codes and ordinances
and
must be
done by a qualified professional.
NOTE:
Undersized gas piping will result in ignition problems, slow drying, increased use of energy, and
can create a safety hazard.
The dryer
must be
connected to the type of heat/gas indicated on the data label affixed to the left wall,
behind the upper control door area (refer to the
illustration
on
page 9
). If this information does not agree
with the type of gas available,
DO NOT OPERATE THE DRYER.
Contact the distributor who sold the
dryer or the
ADC
factory.
IMPORTANT:
Any burner changes or conversions
must be
made by a qualified professional.
The input ratings shown on the dryer data label are for elevations up to 2,000 feet (609.6 meters), unless
elevation requirements of over 2,000 feet (609.6 meters) were specified at the time the dryer order was
placed with the factory. The adjustment or conversion of dryers in the field for elevations over 2,000 feet
(609.6 meters) are made by changing each burner orifice. If this conversion is necessary, contact the
distributor who sold the dryer or contact the
ADC
factory.
2. Technical Data
a. Gas Specifications
b. Gas Connections:
Inlet connection ---------- 1-inch N.P.T.
Inlet supply size ---------- 1-inch N.P.T. (minimum)
Btu/hr input (per dryer)- 300,000 (75,600 kcal/hr)
1) Natural Gas
Regulation is controlled by the dryers gas valves internal regulator. Incoming supply pressure
must be
consistent between a minimum of 6.0 inches (14.9 mb) and a maximum of 12.0 inches
water column (W.C.) - 29.9 mb - pressure.
Содержание MLG-130DR (HSI)
Страница 45: ...ADC113130 1 03 28 00 25 ...