American Dryer Corp.
113289 - 6
H. STEAM INFORMATION
It is your responsibility to have
ALL
steam plumbing connections made by a qualified professional to ensure that
the installation is adequate and conforms to local and state regulations or codes.
IMPORTANT:
Failure to comply with the requirements stipulated in this manual can result in
component failure, which will VOID THE WARRANTY.
NOTE:
In standard format this dryer is manufactured with a pneumatic (piston) damper system, which
requires an external supply of clean, dry, and regulated air (80 psi ± 10 psi [5.51 bar ± 0.69
bar]). Refer to
Steam Damper Air System Connections
,
Section H
,
item 4
. This dryer
may be
provided with an optional steam solenoid valve, in which case, no pneumatic steam
damper system is provided.
1. Steam Coil pH Level
The normal pH level for copper type steam coils
must be
maintained between a value of 8.5 to 9.5. For
steel type steam coils the pH level
must be
maintained between a value of 9.5 to 10.5. These limits are set
to limit the acid attack of the steam coils.
IMPORTANT:
Coil failure due to improper pH level will VOID THE WARRANTY.
2. Steam Requirements – High Pressure
Inlet ________ 1-1/2” N.P.T. Supply Line Connection – qty. one (1) at top manifold.
Return ______ 1-1/2” N.P.T. Return Line Connection – qty. one (1) at bottom manifold.
Shaded areas are stated in metric equivalents
* The minimum operating pressure for optimum results is 100 psig (689.47 kPa).
3. Installation Instructions
To ensure an adequate supply of steam is provided, be sure that the steam supply line and steam return line
are sized and laid out as stipulated in this manual. Inadequate steam supply line and steam return line or
improper steam plumbing will result in poor performance and can cause component failure. Clean, dry
steam
must be
provided to the dryer.
IMPORTANT:
Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.
a. The presence of condensate in the steam supply line will cause water hammer and subsequent heat
exchanger (steam coil) failure. The steam supply connection into the main supply line
must be
made
with a minimum 10-inch (25.4 cm) riser. This will prevent any condensate from draining towards the
dryer.
OPERATING STEAM PRESSURE
Maximum
125 psig
*
861.84 kPa
Heat Input (Normal Load)
14.5 Bhp
Consumption (Approximate)
540 lb/hr
245 kg/hr
Содержание AD-202
Страница 10: ...6 American Dryer Corp 113289 6 202 SPECIFICATIONS WITH MANUAL VERTICAL DOOR ...
Страница 11: ...113289 6 www adclaundry com 7 202 SPECIFICATIONS STEAM WITH OPTIONAL STEEL STEAM COIL ...
Страница 13: ...113289 6 www adclaundry com 9 202DR SPECIFICATIONS WITH MANUAL VERTICAL DOOR ...
Страница 15: ...113289 6 www adclaundry com 11 202 AGA SPECIFICATIONS WITH MANUAL VERTICAL DOOR ...
Страница 35: ...113289 6 www adclaundry com 31 ...
Страница 62: ...ADC Part No 113289 6 02 07 15 ...