113289 - 6
www.adclaundry.com
23
The main duct may be any shape or cross-sectional area, as long as the minimum cross section area is
provided. The
illustration below
shows the minimum cross section area for multiple dryer round or
square venting. These figures
must be
increased 10 square inches (64.52 square centimeters) when
rectangular main ducting is used, and the ratio of duct width to depth
should not be
greater than 3-1/2 to
1. These figures
must be
increased in proportion if the main duct run to the last dryer to where it exhausts
to the outdoors is unusually long (over 20 feet [6.1 meters]) or has numerous elbows (more than one [1]) in
it. In calculating ductwork size, the cross-sectional area of a square or rectangular duct
must be
increased
twenty percent (20%) for each additional 20 feet (6.1 meters). The diameter of a round exhaust
must be
increased ten percent (10%) for each additional 20 feet (6.1 meters). Each 90° elbow is equivalent to an
additional 74 feet (22.55 meters) and each 45° elbow is equivalent to an additional 37 feet (11.27 meters).
202 MULTIPLE DRYER VENTING WITH 20-INCHES (50.8 CM) DIAMETER
EXHAUST CONNECTIONS AT COMMON DUCT
Содержание AD-202
Страница 10: ...6 American Dryer Corp 113289 6 202 SPECIFICATIONS WITH MANUAL VERTICAL DOOR ...
Страница 11: ...113289 6 www adclaundry com 7 202 SPECIFICATIONS STEAM WITH OPTIONAL STEEL STEAM COIL ...
Страница 13: ...113289 6 www adclaundry com 9 202DR SPECIFICATIONS WITH MANUAL VERTICAL DOOR ...
Страница 15: ...113289 6 www adclaundry com 11 202 AGA SPECIFICATIONS WITH MANUAL VERTICAL DOOR ...
Страница 35: ...113289 6 www adclaundry com 31 ...
Страница 62: ...ADC Part No 113289 6 02 07 15 ...