APPENDIX: AK SYSTEM INSTALLATION
4211-1551 06/18/18
Page 1
Technical support: 1-425-951-1120 1-800-363-0251 [email protected]
WARNING
Electrical grounding is required
on all Steam Generators.
All electrical supplies should be
disconnected when servicing a
Steam Generator.
All wiring must be installed by a
licensed electrical contractor in
accordance with local and
national codes.
All plumbing must be installed
by a licensed plumber in
accordance with all applicable
local and national codes.
Steamers are for indoor use only.
Steamers are not for
space-heating purposes.
Be certain that steam bath
enclosures are properly sealed
to avoid water damage from
escaping steam. It is
recommended that 100%
silicone caulk be used to seal
all pipes and fi ttings. Steam
must be prevented from
escaping into the wall cavity.
Never shut off the water to an
appliance that is in use.
Electric Shock Hazard
High Voltage exists within this equipment.
There are no user serviceable parts
in this equipment.
REDUCE THE RISK OF
1. Exit immediately if uncomfortable, dizzy or sleepy. Staying too long in
a heated area is capable of causing overheating.
REDUCE THE RISK OF
Use care when entering or exiting the steam room, floor may be slippery.
NOTE:
For additional safety instructions, see owner's manual.
CAUTION!
Do not contact steam head. Stay at least 12" away
from hot steam escaping from the steam outlet.
OVERHEATING AND SCALDING
2. Supervise children at all times.
3. Check with a doctor before use if pregnant, diabetic, in poor health or
under medical care.
4. Breathing heated air in conjunction with consumption of alcohol, drugs
or medication is capable of causing unconsciousness.
SLIPPING AND FALL INJURY
WARNING
4110-79
05-21-07
Amerec Steam Generators are listed by ETL. The steamers come assembled and ready for installation. Check
that the size and rating of the steamers are suitable for your application; refer to Steam Room Construction and
Generator Sizing Guide (Amerec document 4211-36).
Amerec AK Steam Systems consist of one AK steamer acting as a “primary” steamer which may control one or
two other AK steamers. The sole purpose of ganging steamers is to increase the volume of steam generated
without using multiple controls. The primary steamer controls the secondary steamer(s) through an Amerec
control cable. Cables are available from Amerec.
All controls must connect only to the primary steamer!
IMPORTANT
An exhaust fan installed outside the steam room is strongly recommended to remove excess steam
from the bathroom or shower area.
SECTION 1: GENERAL INFORMATION
AMEREC STEAMBATH GENERATORS
FOR USE WITH STEAM SYSTEMS INCORPORATING
ONE AK PRIMARY STEAM GENERATOR AND
ONE OR TWO AK SECONDARY STEAM GENERATOR(S)
These instructions apply to 9012 series
Amerec Steamers AK7.5, AK11 and AK14
Save these instructions! Read all instructions carefully before installation.
These instructions supplement the AK steamer installation instructions,
Amerec document number 4211-1551
SECONDARY AK
PRIMARY AK
SECONDARY AK
The Amerec Steam Generator can be hung on a wall or set on it’s base. The best mounting location will
satisfy all or most of the following conditions:
1. The steam line should slope to allow condensation to drain into the steam room.
2. The steam line should be less than 20 ft (6m) long; 10 ft (3m) is preferred. Steam lines over 20 ft (6m)
long should be insulated.
3. The mounting location should minimize the number of bends and elbows in the steam line.
4. The steam line should enter the room 18” (460 mm) above the fl oor or at least 12” (305 mm)above a
tub rim or ledge.
SECTION 2: SELECT MOUNTING LOCATION