The following is a list of possible causes of Transducer Faults
By default, transducer fault errors will be removed as soon as the problem has been corrected. However, if the 7252
module has been programmed for Transducer Fault Latch, the status LED will remain blinking green until the Clear
Latched Transducer Fault command has been sent from the Output Registers. Cycling power to the module will also
clear a Latched Transducer Fault.
AMCI LDT
Status
OK
Status LED
Solid Red
Data Flash Memory Fault
Blinking Red/Green
Module Hardware Comm. Failure
Blinking Red
Non Clearable Transducer Fault
Blinking Green
Clearable Transducer Fault
Solid Green
No Errors
OK LED
Solid Green:
Module Owned, two-way communication
Blinking Green:
PLC in Program Mode or rack configuration not correct
Blinking Red:
Communication between module and PLC interrupted, as
when a new program is downloaded to the PLC.
•
Broken Transducer cable
•
Improperly wired cable
•
Non-compatible transducer
•
Magnet is not on the sensor
•
Magnet is on the sensor but outside of the usable range
•
External Power supply not attached to both the 7252 module
and the sensor