4.3 CABLE SELECTION 

There are three occasions when cable selection is needed; they are explained in the following 
sub-sections. 
 

4.3.1  2-WIRE 4-20 mA DC POWER LOOP 

A two conductor, shielded cable is recommended to transmit the 4-20mA signal from the AMC-
VersaTox sensor/transmitter to the monitor. The same wire pair is used for both signal and 
power due to the low power current loop design of the AMC-VersaTox.  For best signal 
transmission and maximum noise rejection, it is recommended to run the cable through steel 
conduit (the cable shield must be grounded at the monitor or power supply).  
 
The figure below is an aid for wire selection. There are three variables that determine the 
maximum cable length; wire gauge, power supply voltage, and load resistor. The purpose of the 
load resistor is to covert the current signal into a voltage signal. Three common load resistors, 
100

, 250

, 500

 are used in the graph with 12 and 24VDC power supplies and a wire gauge 

range from 22 to 16 AWG. All the curves include a safety margin of 0.5VDC. The user must take 
responsibility for the selection of wire gauge, power supply voltage and load resistor used as the 
values shown may not be suitable for all applications. 
 

2 Wire Cable Selection

100R 12V

100R 24V

250R 12V

250R 24V

500R 24V

0

2000

4000

6000

8000

10000

12000

14000

16000

18000

20000

22000

24000

26000

28000

30000

16

17

18

19

20

21

22

Wire Gauge (AWG)

Cab

le L

e

ng

th

 (

F

eet)

Figure 4-15 2-Wire Cable Selection Graph 

(Based & V

SM

 = .5 V)

 

 

Содержание VersaTox

Страница 1: ...instructions completely and carefully before starting Filename 3156405A doc Copyright October 2007 AMC The Armstrong Monitoring Corporation 215 Colonnade Road South Ottawa Ontario Canada K2E 7K3 Tel 6...

Страница 2: ......

Страница 3: ...16 4 2 1 5 DC Transmitter with Relay to BAS without own Power Supply Optional 16 4 2 1 6 DC Transmitter with relay to Power Supply only Optional 17 4 2 1 7 AC Transmitter with or without Relay to BAS...

Страница 4: ...AMC VersaTox Transmitter Sensor 4...

Страница 5: ...l AMC products must be installed and maintained according to instructions Only qualified personnel should install and maintain the equipment AMC shall have no liability arising from auxiliary interfac...

Страница 6: ...Operating Pressure 0 9 to 1 1 atm Relative Humidity 15 to 85 RH non condensing Signal Linearity Linear to the concentration of gas Relay Contacts SPST 2A 30VDC resistive 2 2 FACTORY CALIBRATION Gas Ty...

Страница 7: ...er unit is factory calibrated and is ready for field installation and operation Each sensor module features alarm indicators adjustment trimmers and connection terminal blocks as listed and described...

Страница 8: ...EST POINT SENSOR SIDE TRIMMER TEST POINT 9 COMMON 10 SIGNAL 7 SPAN ADJUST 8 ZERO ADJUST TRIMMER GND J4 TP14 TB1 5V TP13 TP12 TP11 COM SIG SNS2 ZERO 5V SPAN C R S C S R SNS1 J1 VR5 VR4 SNS6 GND SIG COM...

Страница 9: ...T TP4 ALRM PWR GND ALARM NO RELAY V 5V AC IN 2 GND ALARM ADJ 19 ALARM RELAY SELECTOR 20 ALARM RELAY TEST POINT 16 ALARM TEST POINT 14 SIGNAL TEST POINT ADJUST TRIMMER 17 ALARM TERMINAL BLOCK 13 POWER...

Страница 10: ...voltage DC secondary 23 BUZZER Piezo buzzer controlled by the alarm relay 24 JACK Connects the plug in power supply to the AMC VersaTox AMC VersaTox 1 800 465 5777 www armstrongmonitoring com 3156501...

Страница 11: ...ng articles and sources of interference gases Please refer to local codes for sensor transmitter installation information The installer is required to provide any mounting hardware that may be require...

Страница 12: ...mple stream The duct mount option can only be used in positive pressure ducts and is designed to be directly mounted to the outside of the duct The sampling tube is attached to the AMC VersaTox housin...

Страница 13: ...l and power due to the low power current loop design of the AMC VersaTox For best signal transmission and maximum noise rejection it is recommended to run the cable through steel conduit the cable shi...

Страница 14: ...MONITOR SIG TERMINAL 12 TO 24 VDC NOTE PLUGGABLE CONNECTOR THE AMC VersaTox HOUSING IS NOT SHOWN FOR CLARITY FIGURE 4 4 DC Transmitter 1 board to AMC Monitor 4 2 1 2 DC Transmitter 1 board to BAS The...

Страница 15: ...3 wire connection when interfacing to an AMC monitor This additional board also has an optional relay for relay wiring see section 4 2 2 The AMC VersaTox with optional display and relay should be con...

Страница 16: ...R BOARD NOTE THIS WIRING SCHEME IS THE SAME WITH THE DISPLAY OPTION NOTE PLUGGABLE CONNECTOR THE AMC VersaTox HOUSING IS NOT SHOWN FOR CLARITY WARNING CABLE SHIELD MUST NOT BE USED AS A CONDUCTOR FILT...

Страница 17: ...board option requires a 2 wire connection when interfacing to a DC power supply This additional board also has an optional relay for relay wiring see section 4 2 2 The AMC VersaTox with optional displ...

Страница 18: ...THIS WIRING SCHEME IS THE SAME WITH THE DISPLAY OPTION NOTE PLUGGABLE CONNECTOR THE AMC VersaTox HOUSING IS NOT SHOWN FOR CLARITY WARNING CABLE SHIELD MUST NOT BE USED AS A CONDUCTOR POWER TRANSFORMER...

Страница 19: ...C plug in power supply With this power supply the relay power board is included and the relay is wired to control the buzzer The internal wiring is shown in the following figure TB1 D1 AC IN 1 SIG D2...

Страница 20: ...ional SPST relay with a 2A 30VDC resistive contact rating is included on the board The following figure shows the general relay wiring scheme The contacts may be configured as normally open NO or norm...

Страница 21: ...ction There are three variables that determine the maximum cable length wire gauge power supply voltage and load resistor The purpose of the load resistor is to covert the current signal into a voltag...

Страница 22: ...ire gauge and power supply voltage used as the values shown may not be suitable for all applications Note The maximum 4 20mA length is much longer than the DC power wire lengths 3 and 4 Wire Cable Sel...

Страница 23: ...lay power board is required and it also contains the optional relay The power LED indicates that the board is powered on The wiring for all the variances are described in sections 4 2 1 3 to 4 2 1 9 a...

Страница 24: ...tter units 2 On site installation and calibration by Armstrong Monitoring 3 On site calibration by Armstrong Monitoring 4 Training by Armstrong Monitoring 5 Extended warranty calibration program 5 2 1...

Страница 25: ...r 2 minutes adjust the Zero trimmer for a stabilized zero reading of 0 00 VDC measured at the test points TP11 TP12 see Figure 5 1 except oxygen 7 Unplug test leads and connect Remote Calibration Lead...

Страница 26: ...elay trip point is user settable The trip point is settable within the full range for the sensor Zero concentration is 0 4 VDC and full scale concentration is 2 0 VDC If the desired trip point is half...

Страница 27: ...150 200 250 499 5 25 Full Scale 0 8 0 25 0 75 2 5 6 25 12 5 25 50 75 100 125 249 75 0 Full Scale 0 4 0 0 0 0 0 0 0 0 0 0 0 Alarm Relay Trip Point Selection 10 PPM 25 PPM 50 PPM 100 PPM 200 PPM 300 PP...

Страница 28: ...8 ON THE TOP EDGE OF THE BOARD ON THE TOP EDGE OF THE BOARD V DC V Com MULTIMETER DIGITAL DC VOLTAGE MODE GND TEST POINT ALARM ADJUST TRIMMER ALRM TEST POINT Figure 5 3 Alarm Relay Trip Point Procedur...

Страница 29: ...s sensor transmitters It is recommended that the AMC VersaTox be calibrated a minimum of twice a year As mentioned Armstrong Monitoring offers a number of different maintenance plans to suit your requ...

Отзывы: