16
4.2.1.4 DC Transmitter with Relay to BAS with own Power Supply (Optional)
The AMC-VersaTox with relay, power board option requires a 3 wire connection when
interfacing to a BAS. This additional board also has an optional relay, for relay wiring see
section 4.2.2 The AMC-VersaTox with optional display and relay should be connected as shown
in the following figure, by three twisted wires in a shielded cable.
For wiring selection, see section 4.3.2.
TB1
D1
AC-IN 1
SIG
D2
ALRM
TB2
TP5
TP1
TP2
TP3
NC
SIG OUT
TP4
ALRM
PWR
GND
ALARM
NO
REL
A
Y
V+
+5V
AC-IN 2
GND
ALARM ADJ.
RELAY, POWER BOARD
NOTE: THIS WIRING SCHEME IS THE
SAME WITH THE DISPLAY OPTION
NOTE: PLUGGABLE CONNECTOR
THE AMC VersaTox HOUSING IS NOT SHOWN FOR CLARITY
WARNING
CABLE SHIELD MUST
NOT BE USED AS A
CONDUCTOR.
FILTERED
12 - 24 VDC
SUPPLY
-
+
POWER
{
BUILDING
+
-
4 - 20 mA
{
AUTOMATION
SYSTEM
FIGURE 4-7 DC Transmitter with Relay to BAS with own Power Supply
4.2.1.5 DC Transmitter with Relay to BAS without own Power Supply (Optional)
The AMC-VersaTox with relay, power board option requires a 4 wire connection when
interfacing to a BAS. This additional board also has an optional relay, for relay wiring see
section 4.2.2. The AMC-VersaTox with optional display and relay should be connected as
shown in the following figure, by four twisted wires in a shielded cable.
For wiring selection, see section 4.3.2.