Fire Hydrant/Hosereel Portable Tester   

.

    

  

 

INSTRUCTION MANUAL 

 
 

INTRODUCTION 
 

The AMBIT P.F. Series of portable testing units have been primarily designed to meet the need for accurate 
pressure and flow measurement at the service point of fire hydrants and/or hose reels.  Custom built variations 
of these basic units can be supplied to satisfy many other similar applications in a variety of industries where 
pressure/flow relationships need to be established. 
 

 

THE EQUIPMENT 

 

Consists of a portable Aluminium cabinet into which is fitted a flow indicator, a pressure gauge  and a flow 
tube/s. 
 
Both instruments are fitted into a detachable front 

‘loading’ panel which enables easy access for service or 

maintenance work. 
 
The flow instrument incorporates high performance microprocessor electronics with the convenience of full-
time  battery  operation  and  will  withstand  the  day  to  day  rugged  handling  normally  required  of  a  portable 
instrument.  The standard flow ranges are :- 

¾” Tube : 0/180 LPM (or optional LPS)

 

2 ½” Tube : 0/1800 LPM (or optional LPS) 

The accuracy for the flow instruments are :- 
 

¾” Tube : +2% F.S.D. up to 120 LPM & +3% from 120 to 180 LPM (or optional LPS) 

 

2 ½” Tube : +2% F.S.D. up to 1200 LPM & +3% from 1200 to 1800 LPM (or optional LPS) 

 

 

The pressure gauge is of a heavy duty construction and has an accuracy of +1% of full range.  The standard 
pressure range is 0/1000 kPa with optional 0/1600 kPa.  As an option the unit 

can be fitted with an “overrange 

protection valve” which will protect it from damage due to pressure surges. 
 
All screws are stainless steel and wetted parts are either stainless steel or polypropylene. 
 
The unit is guaranteed for a period of 12 calender months from the date of supply, with the exception of the 
paddlewheel flow sensor, which is susceptible to damage from debris in the line. 
 

CONDUCTING A TYPICAL TEST 

 
1. 

CAUTION 

 

 

Prior to connecting the test box to any Hydrant/Hosereel outlet it is most important that the service 
outlet valve be fully opened for not less than 2 minutes. This should flush the pipeline clear of any 
foreign particles that could possibly damage the flow sensor (See TROUBLESHOOTING 

– page 4).

 

 

Please  ensure  the  Hydrant/Hosereel  Tester  is  securely  held  down,  prior  to 
allowing flow through the unit.   
Where ever possible, it is highly recommended a diffuser be fitted to the outlet. 

 

When opening the valve (if fitted), please ensure valve is opened SLOWLY 

 

 

2. 

IMPORTANT

 

 

 

To obtain specified accuracy of the Flow indicator:- 

 

(a) 

DO NOT

  Fit valves other than 

‘full bore’ ball valves to either the inlet or outlet connections of 

the tester.  

 

 

 

 

 

(b) 

DO NOT

  Introduce any partial obstruction or bend within 250mm of either connection. 