Introduction. 

Document Index. 

and servicing is undertaken on radiant tube 
heaters specified in these instructions, due care 
and attention is required to ensure that working 
at height regulations are adhered to. 

 

PLEASE READ this document prior to 

 

 

 

installation to familiarize yourself with the 

components and tools you require at the various 
stages of assembly. 

 
All  dimensions  shown  are  in  inches  unless        
otherwise stated. 
 

The manufacturer reserves the right to alter 
specifications without prior notice.

 

Welcome to the new range of powered harsh 
environment infrared heaters. Local regulations 
may vary and it is the installer’s responsibility to 
ensure that such regulations are satisfied. 
 
All installation, assembly, commissioning and 
service procedures must be carried out by   
suitable qualified competent persons and 

 

 

 

conform with local building codes, or in the   
absence of local codes, with the National Fuel 
Gas  Code  ANSI  Z223.1/NFPA  54  or  the       
National Gas and Propane Installation Code 
CSA B149.1. 
 
When assembling, installing, commissioning 

1. Installation 

Requirements. 

and Propane Installation Code, CSA B149.1.

 

 
D. The unit shall be electrically grounded in  

accordance  with  National  Electric  Code    
ANSI/NFPA 70 and Canadian Electrical 
Code CSA C22.1. 

 
E. The heater may be installed in aircraft   

hangars in accordance with the 

Standard for    

Aircraft Hangars, ANSI/NFPA 409 

and  in       

automotive  garages  when  installed  in       
accordance with the 

Standard for Parking 

Structures, ANSI/NFPA 88A

, or the 

Standard 

for Repair Garages, ANSI/NFPA 88B

, or the 

Canadian 

Natural 

Gas 

and 

Propane         

1.1  Health and Safety 
 

A.  Heater  is  intended  for  heating  outdoor  or               

non-residential indoor spaces and should 
only be installed where flammable gases or 
vapours are not generally present. 

 
B.  Heaters may be suspended either horizontal 

or at any angle. See section 1.3 for 

 

 

 

 

 

 

clearance dimensions. 

 
C. The installation must conform with local 

building codes or, in the absence of local 
codes, with the 

National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 

or the 

Natural Gas 

1   Installation Requirements 

1.1 Health & Safety 
1.2 Heater Suspension 
1.3 Clearance to Combustibles 
1.4 Gas Connection & Supply Details 
1.5 Electrical Connections 
1.6 Ventilation Requirements 

1.6.1 Unvented Units 
1.6.2 Vertical Venting 
1.6.3 Horizontal Venting 

1.7 Fresh Air Intake 
1.8 Technical Details

 

2   Assembly Instructions 

2.1 Tools Required 
2.2 Assembly Notes 

2.2.1 Tubes 
2.2.2 Turbulators 
2.2.3 Brackets 
2.2.4 Couplers 
2.2.5 Reflectors 
2.2.6 End Caps (optional) 
2.2.7 Bends (where required) 
2.2.8 Burner/Fan Assembly 
2.2.9 Heating Configurations 
2.2.10 Detailed Assembly Drawings 
 

3   Start Up Instructions 

3.1 Tools Required 
3.2 Start up procedure 

4   Servicing Instructions 

4.1 Tools Required 
4.2 Burner Description 
4.3 Burner Removal 
4.4 Burner Gas Injector Servicing 
4.5 Burner Head and Electrode Servicing 
4.6 Combustion Fan Assembly 
4.7 Radiant Tube Servicing 
4.8 Reflector Servicing 
4.9 Cleaning of Vent 
4.10 Re-commissioning after Service 

5   Spare Parts 
6   Troubleshooting Guide 
7   Replacing Parts 

7.1 Burner Controller Replacement 
7.2 Air Pressure Switch Replacement 
7.3 Gas Valve Replacement 
7.4 Optional Extra Kits

 

8   User and Operating Instructions 

8.1 To Start Heater 
8.2 To Switch Off Heater 
8.3 Servicing 

Содержание VCLU 100-S40

Страница 1: ...s Fired Tubular Radiant Low Intensity Infrared Heater 700111 WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation...

Страница 2: ...PA 88B or the Canadian Natural Gas and Propane 1 1 Health and Safety A Heater is intended for heating outdoor or non residential indoor spaces and should only be installed where flammable gases or vap...

Страница 3: ...rength or suitability of roof steelwork to which heaters are to be suspended please refer to a Consultant Architect or owner of the building It is recommended that the heater is raised to its final po...

Страница 4: ...ight to maintain required clearance to combustibles Such signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location Refer to mountin...

Страница 5: ...ies C2 C1 A B1 B B A E D2 0 to 55 D1 Ensure that there is adequate provision in the building for combustion and ventilation air supply Installation must meet minimum requirements and appliciable codes...

Страница 6: ...e to expansion WARNING Before installation check that the local distribution conditions nature of gas and pressure and adjustment of the appliance are compatible Figure 3 Correct orientation of Ball V...

Страница 7: ...he main electrical disconnect There may be more than one disconnect switch Lock out and tag switch with a suitable warning label Electrical shock can cause personal injury or death Figure 5a External...

Страница 8: ...nals as shown in the diagram opposite Link F2 F1 R C W1 24V AC Terminals 120V AC Fan Terminals 120V AC Supply 24V AC Single Stage Thermostat Ext R C W1 Burner 1 E N L N E BK R BL BK G W KEY BK BLACK B...

Страница 9: ...z AC external supply is connected to burner Additional wiring is required to install a thermostat and or time clock W ire specification 18 AW G 1 0mm Tri rated 105 C Pressure Switch 120v 24VAC 60Hz Tr...

Страница 10: ...onal wiring is required to install a thermostat and or time clock Wire specification 18 AWG 1 0mm Tri rated 105 C Pressure Switch 120V 24VAC 60Hz Transformer Power ON red BK R Y O BR GR BL KEY BL BLUE...

Страница 11: ...ulated or use an approved insulating thimble Standard vent terminals must extend at least 6 152mm from the wall and at least 24 609mm from any combustible overhang Protect the building material from d...

Страница 12: ...14mm MIN CENTERS ENSURE ALL JOINTS ARE SEALED APPROVED CAT 3 VENT PIPE VENT ELBOWS REFLECTOR END OF RADIANT TUBE VENT ADAPTOR ELBOW 12 0 3 66m 12 0 3 66m APPROXIMATE MAXIMUM DIMENSIONS CODE APPROVED V...

Страница 13: ...0 41 500 41 500 10 3 0 30 9 1 20 6 1 20 6 1 N A Appliances can be installed up to 10 000 ft in the USA Altitude conversion kits are available on request USA Natural Gas 0 2000 ft 0 610m Size 60 80 100...

Страница 14: ...1631 32 Pressure Switch Part No 201508 201697 201676 USA CANADA LP Gas 0 2000 ft 0 610m MODEL 40 60 80 100 125 150 170 200 Burner Orifice Plate Part No 201063 75 201063 74 201063 72 201063 56 201063 5...

Страница 15: ...ed up to 10 000 ft in the USA Altitude conversion kits are available on request Natural Gas 0 2000 ft 0 610m Size 60 80 100 125 150 170 200 WC Hi 4 2 3 9 4 9 4 5 4 4 4 0 3 5 USA WC Lo 2 4 2 3 2 1 2 7...

Страница 16: ...201007 18 201007 19 201007 23 201007 29 201631 28 201631 32 Pressure Switch Part No 201508 201697 201676 USA CANADA LP Gas 0 2000 ft 0 610m MODEL 40 60 80 100 125 150 170 200 Burner Orifice Plate Part...

Страница 17: ...EL U TUBE STRAIGHT TUBE U20 U40 U60 S10 S20 S30 S40 S50 S60 S70 60 80 100 125 150 170 200 40 Options Not available on LP Gas 1 All standard units fitted with unvented vent natural gas and stainless st...

Страница 18: ...urbulators where fitted Insert turbulator into correct tube as indicated in the assembly drawings PLEASE READ this section prior to assembly to familiarize yourself with the components and tools you r...

Страница 19: ...Reflectors are fixed at point F with a reflector support bracket and reflectors are held in position with fixing screws Fixed and sliding joints alternate along the heater at the spacing s indicated o...

Страница 20: ...d with the end cap flanges facing inwards Fasten to reflector using the four Z clips Note For high wind outdoor applications use additional drill screws to secure end cap to the reflector End Cap Bend...

Страница 21: ...l supplies as described in sections 1 4 and 1 5 2 2 9 Heater Configurations The sketches shown on the following page show various heater configurations for the model series dependant on heater length...

Страница 22: ...ed at a distance of at least 50 of the total heat exchanger e g for a 60ft long heater the closest to the burner a bend can be is 30ft Figure 9 Possible Heater Orientations S20 S30 S40 S50 S60 S70 U20...

Страница 23: ...ENSION POINT TUBE STRAP DETAIL TUBE REFLECTOR SUSPENSION BRACKET DETAIL DETAIL FIXED REFLECTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR SUPPLIED NUT BOLT H G F STA...

Страница 24: ...SLIDING REFLECTOR BRACKET DETAIL FIXED REFLECTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR 2 x SCREWS MIN 1 8 GAP TO ALLOW REFLECTOR TO SLIDE SUPPLIED NUT BOLT BUR...

Страница 25: ...CTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR 2 x SCREWS MIN 1 8 GAP TO ALLOW REFLECTOR TO SLIDE SUPPLIED NUT BOLT H G S F STANDARD 4 COUPLER BURNER INSERT DETAIL...

Страница 26: ...POINT TUBE STRAP DETAIL TUBE REFLECTOR SUSPENSION BRACKET DETAIL DETAIL SLIDING REFLECTOR BRACKET DETAIL FIXED REFLECTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR 2...

Страница 27: ...NSION POINT TUBE STRAP DETAIL TUBE REFLECTOR SUSPENSION BRACKET DETAIL DETAIL SLIDING REFLECTOR BRACKET DETAIL FIXED REFLECTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLE...

Страница 28: ...BURNER END CAPS OPTIONAL 6 4 61 6 NOMINAL OVERALL ASSEMBLED LENGTH END CAPS OPTIONAL DISTANCE BETWEEN SUSPENSION POINTS NOT TO EXCEED 12 10 3 REFL S TYPICAL OF 6 G G G S COUPLER HIGH TEMP COUPLER MOD...

Страница 29: ...TIONAL 6 4 71 6 NOMINAL OVERALL ASSEMBLED LENGTH END CAPS OPTIONAL DISTANCE BETWEEN SUSPENSION POINTS NOT TO EXCEED 12 10 3 REFL S TYPICAL OF 7 G G G S 6 OVERLAP G F HT COUPLER 6 OVERLAP S 3 OVERLAP F...

Страница 30: ...81 6 NOMINAL OVERALL ASSEMBLED LENGTH END CAPS OPTIONAL DISTANCE BETWEEN SUSPENSION POINTS NO TO EXCEED 12 10 3 REFL S TYPICAL OF 8 G F 3 OVERLAP G G G S HT COUPLER 6 OVERLAP G F HT COUPLER 6 OVERLAP...

Страница 31: ...REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR SUPPLIED NUT BOLT F STANDARD 4 COUPLER BURNER INSERT SEE DETAIL NAT GAS ONLY G H 3 3 G G F BURNER INSERT DETAIL PT NO 201688 NOTE...

Страница 32: ...TAIL FIXED REFLECTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR 2 x SCREWS MIN 1 8 GAP TO ALLOW REFLECTOR TO SLIDE SUPPLIED NUT BOLT S F G BURNER INSERT SEE DETAIL N...

Страница 33: ...SLIDING REFLECTOR BRACKET DETAIL FIXED REFLECTOR BRACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR 2 x SCREWS MIN 1 8 GAP TO ALLOW REFLECTOR TO SLIDE SUPPLIED NUT BOLT S F...

Страница 34: ...ACKET REFLECTOR TUBE STRAP RADIANT TUBE 2 x SCREWS TIGHTEN TO FIX REFLECTOR 2 x SCREWS MIN 1 8 GAP TO ALLOW REFLECTOR TO SLIDE SUPPLIED NUT BOLT S F G G H 3 3 G G G F S 6 REFLECTOR OVERLAPS S HT COUPL...

Страница 35: ...at are such that the heating system will be required to operate The fan will start to run and the power on lamp will illuminate Safe start checks are carried out automatically After the fan has run up...

Страница 36: ...off the gas supply at the shut off valve The heater should attempt to relight If the gas valve has been left off lock out should occur This is indicated by the power on lamp being illuminated and fan...

Страница 37: ...set to maximum and is calling for heat Switch on electrical supply The red neon should now be illuminated If restarting heater a delay of 15sec should be allowed A successful ignition is indicated by...

Страница 38: ...chanical contractor Soft Brush Phillips Screwdriver Leather Faced Gloves Wrench 4 1 Tools Required The following tools and equipment are advisable to complete the tasks laid out in this manual Suitabl...

Страница 39: ...r support casting to enable the burner to be removed from the radiant tube Step 6 Remove the burner and position in a safe area to prevent the burner or its attached components from falling to the gro...

Страница 40: ...and remove any dust with a soft brush Step 6 Remove any dust from fan scroll and from around the motor Step 7 Ensure the impeller rotates freely Step 8 Refit components 4 6 Burner Head and Electrode S...

Страница 41: ...are not liable to obstruction 4 10 Re commissioning After Service After servicing of the heater has been undertaken it is necessary to re commission the heater as detailed in the commissioning chart i...

Страница 42: ...571 201854 201905 201957 202132 Jet Carrier 40 150 NG 40 170 LPG 170 200 NG Item Required Spares In order to aid troubleshooting and servicing we recommend that the components shown in this section sh...

Страница 43: ...terminal F2 is 120VAC 2 Integrity of wiring connections 3 Fan Do the amber lights illuminate after a purge period NO Is there power to the fan YES NO CHECK 1 Relays 2 3 2 Voltage across terminals A1 A...

Страница 44: ...eady On Power Applied Control OK 1 Flash Combustion Pressure Switch Open With Blower On 2 Flashes Combustion Pressure Switch Closed With Blower Off 3 Flashes Lockout From The Three Ignition Trials 4 F...

Страница 45: ...harness connector Step 7 Test product and close access door 7 2 Air Pressure Switch Replacement Step 1 Disconnect the two silicone tubes from the pressure switch Step 2 Remove the two electrical chas...

Страница 46: ...curing screws arrowed from the base of the injector tube noting earth terminal connection Step 4 Remove the gas valve wiring connections noting their positions Step 5 Remove the four screws arrowed se...

Страница 47: ...inless Steel End Cap Kit 1Pair 90 Elbow Kit 1 Off 180 U Bend Kit 40 202579 202568 270615 202588 202638 60 202580 202569 80 202580 202570 100 202582 202571 125 202583 202572 150 202584 202573 170 20258...

Страница 48: ...Propane Altitude Conversion Kit Wind Rain Hood Kit Outdoor Only Stainless Steel End Cap Kit 1Pair 90 Elbow Kit 1 Off 180 U Bend Kit 40 202579 202568 202564 202588 202638 60 202580 202569 80 202582 20...

Страница 49: ...49...

Страница 50: ...50...

Страница 51: ...51...

Страница 52: ...l unit will lock out the power on lamp will remain illuminated and the fan will continue to run To reset after lockout switch off the power supply to the heater and wait 5 minutes then turn the power...

Отзывы: