background image

Figure 11 Logic sequence for Herringbone control panel

6 Control system

The control system must be installed in
accordance with the design specification.

6.1 Control panel design

Ambi-Rad control panels are available 
either as standard units to control 
single or multiple zones of heaters 
utilising the Ambi-Rad black bulb 
radiant thermostat. Special control 
functions are available on request.

Herringbone control panels use the
logic in figure 11 to operate in a safe
and satisfactory manner.

6.2 Installation of control panel

To install the Ambi-Rad control panel 
remove the plastic plugs from the four 
9mm diameter holes in the back of the 
control box. Using these holes fix the 
box in a convenient position to a 
suitable plugged wall or solid structure 
with No. 10 gauge wood screws or 
6mm diameter bolts or set screws. 
Access to the holes may be gained from
the inside of the box without the 
necessity of removing the wiring 
chassis. Make the electrical connections
in accordance with figure 12a or 12b 
and cut holes in the removable gland 
plate provided in the box. Conduit or 
strain relief glands should be used.

Power onto panel

Mode switch in off position

Mode switch in auto position

Mode switch in constant position 

(one or all zones)

No heaters on

Time clock off

Time clock on

Break contacts 8 & 9 on 

Make contacts 8 & 9 on 

black bulb controller

black bulb controller (via relay or

time clock contacts for each zone

Control on night temperature

Control on day 

setting for frost protection

temperature setting

Call for heat by black bulb controller 

controlling each zone or all heaters

Delay start of Herringbone fan for 30 seconds 

to ensure vacuum switch on heaters is 

broken (only required for 2 zones or 

more on one fan)

Switch on the power suuply to the 

Herringbone fan and power supply to 

heaters simultaneous

Individual heater vacuum switch senses combustion vacuum

Individual heaters start ignition sequences

Zone control switches off

Other zones carry on firing (if fitted)

Zone control calls for heat

Power off to all heaters or zones 

and to stop Herringbone fan

(Possible 

alternative 

control

function to 

override

temperature

controller)

11

 

Содержание Herringbone HB

Страница 1: ...HERRINGBONE HB COMBINED FLUE SYSTEM...

Страница 2: ...Index General arrangement of Ambi Rad Herringbone system Instructions and installation Manifold assembly Fan to flue arrangement Commissioning Control system Service instructions 7 6 5 4 3 2 1 1...

Страница 3: ...arrangement The exhaust flue should be adequately supported from the building structure and installed in accordance with the British Standard Code of Practice Flues for Gas Appliances Local and Minis...

Страница 4: ...ters in the desired position the manifold system should be laid out on the floor where possible to the design layout before erecting After allowing for a minimum of 75mm 3in of penetration of the fitt...

Страница 5: ...Figure 2 Figure 3 Figure 4 Important fit damper in vertical position Gas flow Important fit rivets and jointing compound SEAL ALL JOINTS 4...

Страница 6: ...AR installation manual GB ARE E 079 0501 Figure 5 3 4 Condensate trap A condensate trap assembly must be provided at the end of the manifold system before the hot gas vacuum fan See figure 8a The min...

Страница 7: ...o Combined Flue Heating System Do s and don ts of Herringbone systems The Type 0 and Type 2 vacuum fans have bottom horizontal discharge with rectangular connections flanged on the type 0 and must be...

Страница 8: ...Figure 7 Vacuum fan mounting details Fan type 0 2 A 124 80 B 38 35 C 175 174 D 7 1 7 E 209 125 F 153 100 G 42 25 H 239 120 J 340 210 K 332 205 L 363 215 All dimensions are in millimetres see Fig 6 7...

Страница 9: ...ure 8b Low fan arrangement Figure 8d Conventional flue arrangement roof exit Figure 8e Conventional flue arrangement wall exit Figure 8c Stainless steel telescopic through the wall arrangement availab...

Страница 10: ...0 2 3 N P refer to natural gas or propane respectively Adjust the damper at exit of each heater using a 4mm hexagon wrench in the M8 locking screw Observing the vacuum reading using a U tube manometer...

Страница 11: ...ssure or anti clockwise to decrease the pressure Set the burner pressure to the required figure given on the data label Switch off the heater by pulling out the mains connector Disconnect U tube manom...

Страница 12: ...cordance with figure 12a or 12b and cut holes in the removable gland plate provided in the box Conduit or strain relief glands should be used Power onto panel Mode switch in off position Mode switch i...

Страница 13: ...Figure 12a Single zone Herringbone control panel wiring diagram for Type 2 fan single phase incorporating the ARBB65 black bulb control thermostat 12...

Страница 14: ...Figure 12b Wiring diagram for Type 0 fan single phase 13...

Страница 15: ...r unit by undoing the four screws c Fix the base to the wall with two screws d Connect the sensor using a three core cable of not less than 0 5mm2 Maximum length of cable is 200m if 0 5mm2 is used Sec...

Страница 16: ...4 489700 Facsimile 01384 489707 UK sales email sales ambirad co uk Website www ambirad co uk 7 Service instructions Under normal working conditions it is recommended that the Ambi Rad heater has a rou...

Отзывы: