background image

If ignition is successful the flame is detected
by the flame sensing probe and the ignition
spark is switched off. The amber 

burner on

lamp indicates that the gas solenoid valve 
is energised.

If ignition is unsuccessful the gas valve is
closed and the spark ignition de-energised
after approximately 4 seconds. After
unsuccessful ignition attempt the electronic
sequence controller will lock-out the red

mains on

lamp only will remain illuminated.

To reset this lock-out condition, switch 
the power supply to the system, wait until
the fan stops completely then restart it. If
repeated lock-out occurs, investigate the
cause.

Note

If an individual burner assembly unit 

is switched off and reconnected it cannot
restart. The fan must stop running before the
burner can be restarted.

To shut down the heaters switch off the
power supply to the system. Automatic
control of the heating system is achieved
through the lockable control panel,
incorporated in the electrical supply, which
may contain a time switch, black bulb
controller with day and night settings, a 3
position mode switch giving constant on/off
auto control and fan starter. It is essential to
allow a delay of 30 seconds after switching
off heaters before attempting to restart the
system.

If at any time after completion of the start
up sequence loss of flame should occur, the
electronic sequence controller will attempt
to re-ignite. If this is unsuccessful, heater
lock-out will occur.

To set the burner gas pressure

Close gas valve. Unplug mains input
connector to heater. Unscrew the fixing
screws of the safety control housing lid and
remove pressure test point screw and
connect a ‘U’ tube manometer to the
pressure test nipple located on the
combination valve. Remove the cover from
the pressure regulator to reveal the
adjusting screw. 

Replace mains input connector, open gas
valve and start system.

Using a suitable screwdriver, adjust the
pressure regulator, turning the screw
clockwise to increase the pressure or 
anti-clockwise to decrease the pressure. 
Set the burner pressure to the required
figure given on the data label. Switch off
the heater by pulling out the mains
connector. Disconnect ‘U’ tube manometer
and refit screw in pressure test nipple. Refit
cover of pressure regulator. Replace cover
plate on safety control housing and refit
screws.

Burner ignition

To re-ignite heater, switch system off at
control panel. Wait until fan stops
completely and then restart system.

Re-ignition

Check the operation of the flame safeguard
equipment as follows: 

With the heater running normally switch off
the gas supply at the appliance isolating
valve. Observe that the 

burner on

lamp

extinguishes within 1 second. After a purge
period of approximately 9 seconds the
heater should attempt to re-light and if the
gas isolating valves have been left off, 
lock-out should occur, indicated by power
light only being illuminated and fan
running.

Vacuum proving switch

Check the operation of the vacuum proving
switch as follows:

With the heater running normally, pull out
the mains input connector. Pull off the
silicone tube connecting the vacuum switch
to the combustion chamber. Observe for at
least 20 seconds that there is no attempt to 
re-ignite. Then replace the silicone tube.

Replace the safety control housing lid and
reconnect the mains input connector.

To re-ignite each heater in the system, the
fan must stop running. Switch system off 
at the control panel. Wait until fan stops
completely and then restart system. 

Repeat the above procedure for each of the
heater units in the heating system.

Balancing system

Important

When all the heaters have been

commissioned as above, the vacuum settings
must be finally balanced in the hot condition.

Start all burners up and allow them to run
for at least 20 minutes. With the use of a ‘U’
tube manometer determine vacuum reading
at the damper assembly on each heater. (See
figure 4 for vacuum test point) 

The damper should be readjusted and set at 
a hot condition reading as shown in figure 10
for the appropriate size heater and model.

It will be noted that the emitter has a
tendency to bow when hot, this is normal
and quite acceptable.

10

 

Содержание Herringbone HB

Страница 1: ...HERRINGBONE HB COMBINED FLUE SYSTEM...

Страница 2: ...Index General arrangement of Ambi Rad Herringbone system Instructions and installation Manifold assembly Fan to flue arrangement Commissioning Control system Service instructions 7 6 5 4 3 2 1 1...

Страница 3: ...arrangement The exhaust flue should be adequately supported from the building structure and installed in accordance with the British Standard Code of Practice Flues for Gas Appliances Local and Minis...

Страница 4: ...ters in the desired position the manifold system should be laid out on the floor where possible to the design layout before erecting After allowing for a minimum of 75mm 3in of penetration of the fitt...

Страница 5: ...Figure 2 Figure 3 Figure 4 Important fit damper in vertical position Gas flow Important fit rivets and jointing compound SEAL ALL JOINTS 4...

Страница 6: ...AR installation manual GB ARE E 079 0501 Figure 5 3 4 Condensate trap A condensate trap assembly must be provided at the end of the manifold system before the hot gas vacuum fan See figure 8a The min...

Страница 7: ...o Combined Flue Heating System Do s and don ts of Herringbone systems The Type 0 and Type 2 vacuum fans have bottom horizontal discharge with rectangular connections flanged on the type 0 and must be...

Страница 8: ...Figure 7 Vacuum fan mounting details Fan type 0 2 A 124 80 B 38 35 C 175 174 D 7 1 7 E 209 125 F 153 100 G 42 25 H 239 120 J 340 210 K 332 205 L 363 215 All dimensions are in millimetres see Fig 6 7...

Страница 9: ...ure 8b Low fan arrangement Figure 8d Conventional flue arrangement roof exit Figure 8e Conventional flue arrangement wall exit Figure 8c Stainless steel telescopic through the wall arrangement availab...

Страница 10: ...0 2 3 N P refer to natural gas or propane respectively Adjust the damper at exit of each heater using a 4mm hexagon wrench in the M8 locking screw Observing the vacuum reading using a U tube manometer...

Страница 11: ...ssure or anti clockwise to decrease the pressure Set the burner pressure to the required figure given on the data label Switch off the heater by pulling out the mains connector Disconnect U tube manom...

Страница 12: ...cordance with figure 12a or 12b and cut holes in the removable gland plate provided in the box Conduit or strain relief glands should be used Power onto panel Mode switch in off position Mode switch i...

Страница 13: ...Figure 12a Single zone Herringbone control panel wiring diagram for Type 2 fan single phase incorporating the ARBB65 black bulb control thermostat 12...

Страница 14: ...Figure 12b Wiring diagram for Type 0 fan single phase 13...

Страница 15: ...r unit by undoing the four screws c Fix the base to the wall with two screws d Connect the sensor using a three core cable of not less than 0 5mm2 Maximum length of cable is 200m if 0 5mm2 is used Sec...

Страница 16: ...4 489700 Facsimile 01384 489707 UK sales email sales ambirad co uk Website www ambirad co uk 7 Service instructions Under normal working conditions it is recommended that the Ambi Rad heater has a rou...

Отзывы: