18
SPECIFICATIONS
WIRING
Cord connection to a wall socket is not permitted for 265-
volt units. All 265-volt units must be hard wired using the
hard wire kit or make use of the plug-in receptacle in the
standard subbase.
Heaterless Units
If a heaterless unit is ordered, field provisions must be made
for supplemental heat if desired. All 208/230 volt heater-
less units are shipped with a 15 Amp power cord and all
heaterless 265 volt units are shipped with a 20 Amp power
cord.
OPERATING CONTROLS
Users Controls
A 7 button touch key pad, located behind the control door,
controls both temperature and operation mode. The key
pads can be used alone or in combination.
Mode
Switches
Master Switch
The master switch disconnects power to all of the system
components. When this switch is in the off position, the
compressor, fan motor, reversing valve, and electric resis-
tance heater will all be de-energized.
REMOTE/STANDARD
The remote/standard configuration is used to change the
control of the unit from the standard on board controls in
the standard mode, to a remote wall mounted thermostat
in the remote mode. For remote control configuration set-
tings, refer to
Configuration Settings.
Fan Cycle Configuration
The fan cycle configuration sets the operational mode of
the fan. In the ON position, the fan will run continuously
whenever the unit is in the heat or cool mode. In the
AU
position, the fan will cycle on and off with the compressor
or electric heater when the unit is in the cool or heat mode.