Amana PTAC 24

16

16 1/16"

410 mm

13 3/4

"

350 m

m

Wall Receptacle Within 58"
From Bottom Right Side Corner
on 115 VAC and
208/230 VAC Units Only

Wall Sleeve Dimensions

Outside Enclosure Panel Removal

The sleeve stiffener must be taken out before the enclo-
sure panel can be removed from the sleeve.
The enclosure panel can be removed by folding the four
flaps up and downward and manipulating the front ends of
the top plus bottom towards the center. The entire panel
can be pulled out diagonally from one side.
Install the wall sleeve condenser air grille by using the screws
and holes provided.

Installation (WS900B or WS900D)

After the wall opening is checked and approved for loca-
tion, size, and clearances, complete the following to install
the wall sleeve.

NOTE:

 Check with Amana

®

 Brand Technical Service when a

chassis is installed in any wall sleeve not supplied by
Goodman.

1. Remove the outside enclosure panel from the wall sleeve.
2. Slide the wall sleeve into the wall opening. Do not dis-

tort the cabinet shape to fit the wall opening. The unit
chassis must fit snugly and uniformly into the wall
sleeve.

3. Locate the sleeve within the range of minimum projec-

tions, as shown in Minimum Wall Opening Dimensions
and Minimum Interior and Exterior Projections Figures,
so both sides are at least the minimum projection from
the wall.

4. Check the level of the wall sleeve. For proper drainage,

the sleeve should be level from side to side and one-
quarter bubble in the sight glass sloping to the outside.

5. Two holes will need to be drilled in both sides of the

wall sleeve for mounting into the wall. Drill holes of
proper size and in the proper location so the screws will
engage into strong supporting members of the wall. 

DO

NOT DRILL THROUGH BOTTOM OF SLEEVE.

 The fol-

lowing figure shows possible fastening methods.

Plastic

Anchor

Expansion

Anchor Bolt

Attaching Wall Sleeve to Opening

6. Check the level of the wall sleeve and adjust if neces-

sary.

7. Caulk or seal around the outside of the entire sleeve.
8. If the unit chassis will not be installed immediately,

replace the enclosure panel on the outside opening of
the sleeve. This will prevent weather damage to the
building interior.

9. Recycle or dispose of packaging materials per local

codes.

OUTDOOR GRILLE

An outside grille must be installed to direct air flow for proper
unit operation and also protect the outdoor coil. The grille
must be installed before installing the chassis. Refer to the
Installation Instructions supplied with the outdoor grille kit
for a complete description of the installation procedure.
This model requires either a Stamped Grille Kit (Model SGK-
-B) or an Architectural Grille Kit (Model AGK--B). When re-
placing an old chassis with an existing grille, please check
with your sales representative to determine if the new chas-
sis should be used with the old outdoor grille. An improper
outdoor grille can decrease cooling or heating capacity, in-
crease energy usage and shorten compressor life.

FRONT REMOVAL

1. Grasp the cabinet front as shown.

2. Pull the bottom of the cabinet front away from the chas-

sis until the retaining clips disengage.

PROPER INSTALLATION

Содержание PTAC 24"

Страница 1: ...served PACKAGE TERMINAL AIR CONDITIONER HEAT PUMP Standard and Remote Applications with LED M70 Control Board and R 410A This manual is to be used by qualified professionally trained HVAC technicians...

Страница 2: ...IMPORTANT INFORMATION INDEX PRODUCT IDENTIFICATION 4 IMPORTANT INFORMATION 2 SPECIFICATIONS 5 PROPER INSTALLATION 9 MAINTENANCE 32 OPERATIONS 34 SERVICING 38 WIRING DIAGRAMS 61 ONLY PERSONNEL THAT HA...

Страница 3: ...HO ARE UNABLE TO REACT TO THE FAILURE OF THIS PRODUCT THE FAILURE OF AN UNATTENDED AIR CONDITION ER MAY RESULT IN EXTREME HEAT IN THE COND ITIONED SPACE CAUSING OVERHEATING OR DEATH OF PERSONS OR ANIM...

Страница 4: ...E Examples 4 265V 60Hz 1Ph A Standard Model PTC073E35AXXX 5 240 220V 50Hz 1Ph C Corrosion Protection Seacoast PTC073E50CXXX D Power Door PTC073E35CDXX E Makeup Air Electric Heater PTC073E35CQVX DESIGN...

Страница 5: ...amps Overcurrent protection on 265 volt models must be cartridge style time delay fuses included and factory installed on all Amana brand 265 volt chassis See heater perform EER Energy Efficiency Rati...

Страница 6: ...less than 250 volts have a Leak Current Detector Interrupter LCDI pow er cord and meet UL 484 standards 11 Refer to electric heat performance data for total MCA and recommended overcurrent protection...

Страница 7: ...omplete model number 8 R 410A refrigerant used in all systems 9 All units meet or exceed ASHRAE90 1 standards 10 All units less than 250 volts have a Leak Current Detector Interrupter LCDI power cord...

Страница 8: ...er 8 R 410A refrigerant used in all systems 9 All units meet or exceed ASHRAE90 1 standards 10 All units less than 250 volts have a Leak Current Detector Interrupter LCDI power cord and meet UL 484 st...

Страница 9: ...tric heaters is 15 amps Overcurrent protection on 265 volt models must be cartridge style time delay fuses included and factory installed on all Amana brand 265 volt chassis See heater perform EER Ene...

Страница 10: ...Wet Coil CFM Dry Coil Ventilated Air CFM Fan Only Dehumidification Pints Hr Notes All 265 volt models must use an Amana brand sub base PTSB4 E or an Amana brand hard wire kit PTPWHWK4 Minimum Circuit...

Страница 11: ...3 7 4 9 6 1 715 700 1090 1090 1350 1330 715 1090 1340 COP5 3 4 3 4 3 1 3 2 3 0 3 0 3 4 3 1 3 0 CFM Dry 360 360 410 360 410 410 COP Coefficiency of Performance per AHRI Test Procedures units are rated...

Страница 12: ...cify two digit heater kW size to complete model number 8 R 410A refrigerant used in all systems 9 All units meet or exceed ASHRAE 90 1 standards 10 All units less than 250 volts have a Leak Current De...

Страница 13: ...ge 1 1 5 1 04 1 27 230 208 1 97 253 265 238 292 Operating Voltages Voltage Utilization Range LCDI or AFCI Power Cords Underwrites Laboratories and the National Electric Code NEC now require power cord...

Страница 14: ...met See Minimum Unit Clearances and Minimum Interior and Exterior Pro jections Figures as well as Minimum Clearances and Projections table for details If installed in a concrete or masonry wall a lin...

Страница 15: ...ight sleeve corner Extension cords must not be used with the unit See the note on Wall Sleeve Dimensions Fig ure 42 1 4 1075 mm Minimum 16 1 4 415 mm Mini mum Dimension B in Table 1 Minimum Wall Openi...

Страница 16: ...sloping to the outside 5 Two holes will need to be drilled in both sides of the wall sleeve for mounting into the wall Drill holes of proper size and in the proper location so the screws will engage...

Страница 17: ...ment 2 If a standard subbase is used be sure the right hand subbase cover is removed before the chassis is installed in the sleeve 3 On 230V 30A units installed with an existing subbase use the subbas...

Страница 18: ...ation Mode Switches Master Switch The master switch disconnects power to all of the system components When this switch is in the off position the compressor fan motor reversing valve and electric resi...

Страница 19: ...of a front desk switch The following figure shows a wiring schematic for connecting the front desk switch to the unit If the unit is configured for wired unrented setback energy management see Configu...

Страница 20: ...er to the Maintenance and Cleaning section for the proper cleaning procedure If this light is still on after cleaning please refer to the Diagnostic Sta tus Report section for assistance ON OFF MASTER...

Страница 21: ...or must be left closed when the outdoor temperature might fall below freez ing or a power door kit must be installed AIR DISCHARGE GRILLE The discharge grille can be adjusted to expel air at either a...

Страница 22: ...ress the OFF key Configuration feature mode will also exit if no keys are pressed for a pe riod of two 2 minutes Refer to the Configuration Chart Wireless Communications PTAC models PT G have the opti...

Страница 23: ...ng additional motion sensing Ensure location is out of the path of foot traffic where a person might accidentally bump into the thermostats and damage the device 2 Remove thermostat from mounting plat...

Страница 24: ...AND POWERED DOOR SENSOR OPTION In cases where there is no top door frame the sensor will need to be mounted on the wall next to the door In these cases a wired magnet a field supplied single pole sing...

Страница 25: ...MUST BE 15 16 FROM THE SENSOR MOUNTING PLATE MAGNET HOLDER MAY EXTEND ABOVE THE DOOR OR THE DD01E OR MAY EXTEND BELOW THE DOOR FRAME TO ENSURE THE MAGNET IS NO MORE THAN 1 8 FROM THE BOTTOM CENTER OF...

Страница 26: ...les The door frame and door usually will not align Place holder on the door and select the slot that places the magnet as close as possible to the 15 16 depth from the back of the DD01 mounting plate...

Страница 27: ...m of the DD01E will line up with the center of the line of the magnet holder containing the magnet Choose magnet position A B or C to align the magnet 15 16 from the back of the DD01E or DD01F DOOR SE...

Страница 28: ...suffix or 02 03 etc To select the room suffix while still in configuration mode press the HEAT key until appears Then press the up and down arrows to select the room suffix Example For the unit servin...

Страница 29: ...efault settings configure the device or devices that were bound See the next section for configuration choices NOTE If a wireless device is replaced or added all de vices including those previously bo...

Страница 30: ...higher You can verify the software version by starting with the unit in the OFF position and while holding down the and buttons doubleclicktheCOOLbuttonandthenreleaseand pushtheFANbuttonwithinoneseco...

Страница 31: ...est leaves room 8 Press HEAT key to scroll to third unoccu pied setback temperature Press either the up or down arrow to the desired third unoccupied set back temperature 9 Press HEAT key to scroll to...

Страница 32: ...The dis play alternates between and 00 Use the up and down arrow keys to change 00 to the previously selected security code NOTE The control will not proceed to the next step until the correct code is...

Страница 33: ...Scale C Celsius Scale d6 Sensorless Un Occ Time 1 32 18 1 32 18 d7 1st Un Occ Set Back Temp 1 16 2 1 16 2 d8 1st Un Occ Set Back Time 1 5 1 24 1 5 1 24 5 d9 2nd Un Occ Set Back Temp 1 16 3 1 16 3 dA...

Страница 34: ...ake filter 1 Grasp each filter by its molded handle located on the front edge of the front below the discharge grill 2 Pull the filter straight up and remove 3 Clean filter with vacuum or with running...

Страница 35: ...e are prop erly sealed The wall sleeve s level should also be rechecked Proper leveling for most installations are a bubble tilt to the outside and level from right to left Contact your sales person f...

Страница 36: ...ounds Water is picked up and distributed over the coil This improves the efficiency and helps with water removal Water Dripping Water will collect in the base pan during high humidity days This can ca...

Страница 37: ...erridden Automatic 2nd Stage Electric Heat Heat Pump Mod els If the room temperature falls to 4 F below the set point temperature the reverse cycle heat pump is shut off and the strip heat is turned o...

Страница 38: ...peed for up to 120 seconds The sample fan is aborted if compressor demand is detected To avoid unnecessary sampling the period between samples will be based on specific room conditions The default sam...

Страница 39: ...enser Compressor Evaporator Capillary Tube Process Strainer Suction Line Discharge Line Capillary Tube Check Valve Open Reversing Valve D i s c a r e i e Suction Line Refrigeration Sealed System Heat...

Страница 40: ...40 OPERATIONS i r i Refrigeration Sealed System Heat Pump Heat Pump Mode REFRIGERATION SEALED SYSTEM...

Страница 41: ...in the system is harmless Nothing could be further from the truth Oxygen from moisture plus normal compressor and motor heat reacts chemically with the refrigerant and oil to form corrosive hydrochlo...

Страница 42: ...set With the valve on the charging cylinder closed open the manifold valve to the cylinder 6 Evacuate the system to at least 29 inches gauge before opening valve to thermocouple vacuum gauge 7 Contin...

Страница 43: ...the sling psychrometer The cooling performance test should not be employed when outside temperatures are 20 below that of the room Best results are obtained when the test is conducted under peak load...

Страница 44: ...abinet front must be in place during this test Record supply voltage to unit Operate unit in highest heat setting Record wattage recorded on wattmeter or total amp draw to unit Refer to heating watts...

Страница 45: ...il T Temperature Across Indoor Coil T 90 85 80 75 70 HEH073 PMH073 PTH073 HEH074 PMH074 PTH074 HEH093 PMH093 PTH093 HEH094 PMH094 PTH094 HEH123 PMH123 PTH123 HEH124 PMH124 PTH124 HEH153 PMH153 PTH153...

Страница 46: ...cleaning the filter or coils does not clear the status code or the code indicates that servicer should be called DIAGNOSTIC STATUS REPORT MODE To enter Diagnostic Status Report mode press and hold th...

Страница 47: ...F3 Indoor Ambient Thermistor reads outside the range 20 F to 200 F Y N Replace black Indoor Ambient Thermistor F4 Indoor Coil Thermistor either above or below operating tolerances N Y Replace Red Indo...

Страница 48: ...ompressor Test Motor Windings S 17 Compressor Stuck Use Test Cord S 17 Open Control Circuit Test Control Circuit with Voltmeter S 1 Low Voltage Test Voltage S 1 Faulty Evap or Cond Fan Motor Repair or...

Страница 49: ...out remove the cover 3 Disconnect the floodback protector wiring or ther mistor from the control board s Indoor Switch termi nals 4 Remove the two screws securing the top screen to the evaporator ass...

Страница 50: ...80000 100000 120000 140000 160000 180000 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 Temperature deg F Resistance ohms THERMISTOR RESISTANCE TEMPERATURE CHARACTERISTIC WARNING 2 Remov...

Страница 51: ...CK 1 Remove front cover 2 Remove the two mounting screws one on each side of the control board cover Tilting the control panel out disconnect ribbon connector from control board DO NOT PULL ON RIBBON...

Страница 52: ...e ohms Capacitance Check Using a hookup as shown below take the amperage and voltage readings and use them in the formula WARNING LINE VOLTAGE NOW PRESENT Voltmeter Ammeter Capacitor 15 Amp Fuse Capac...

Страница 53: ...looking at it and lift the assembly straight up 13 Loosen the set screw on the blower wheel 14 Remove the three screws securing the motor to the housing and remove the motor from the blower wheel 15 D...

Страница 54: ...1 With no power remove the leads from the compressor terminals 2 Touch the leads of an ohmmeter to terminals C S start windings and C R run winding Ground Test With no power and compressor leads remov...

Страница 55: ...and low side of the system 2 Start the system and run a Cooling Performance Test If the test shows a Below normal high side pressure b Above normal low side pressure c Low temperature difference acros...

Страница 56: ...COOLING If the valve fails to change its position test the voltage 230 V or 265 V at the valve coil connector cap while the system is on the HEATING CYCLE WARNING SET THE THERMOSTAT ALL THE WAY COUNT...

Страница 57: ...ng the chassis to the wall sleeve 4 Carefully slide chassis out of wall sleeve placing on floor or protected cart ESCUTCHEON CONTROL BOARD CONTROL PANEL 1 Remove front cover 2 Remove the two mounting...

Страница 58: ...the compressor suc tion line to protect against potential liquid refrigerant en tering the compressor If refrigerant temperatures are too low the compressor will be cutoff to help protect the com pre...

Страница 59: ...lder out side air when needed 6 Filter to assist in keeping the DigiAIR coils cleaner to maintain dehumidification and outside air flow Permanent and washable 7 Vent door is configurable to either be...

Страница 60: ...ized when config ured temperatures outside air RH and operating condi tions are met If codes or property ownership mandate that the makeup air is required 100 of the time then the DigiAIR module shoul...

Страница 61: ...tral location to thoroughly clean and have them ready for the next filter check 4 Clean filter with vacuum or with running water Reverse this procedure to reinstall the filter 5 Also inspect and clean...

Страница 62: ...ll wiring to the heater assembly and re move the assembly 8 Remove the floodback protector or thermistor from the evaporator discharge tube 9 Remove screws holding evaporator to basepan and par tition...

Страница 63: ...ERMINAL BOARD BK DANGER HIGH VOLTAGE 24VAC TRANSFORMER 12VA CLASS 2 ONLY ON OFF MASTER SWITCH HEATER 1 HEATER 2 LINE 1 IN1 COM IN2 AUXILIARY C R GL W2 Y W1 B GH REMOTE THERMOSTAT IAT BLACK ICT RED OCT...

Страница 64: ...L2 10 10 ALTERNATE INDOOR MOTOR WIRING COM GND INPUT AC TO MOTOR VSTM ID R 485 S VSM EM EVAP MOTOR 1400 1250 1200 1000 L1 MC LOW HIGH ID FAN L2 11 11 REV VALVE LOW 10 Model Starts With High Speed VST...

Страница 65: ...date wiring WARNING DigiAIR MAKE UP SOLUTION KIT R YL GY BU BR RD GY TR 1 To MC BU RD PK ALTERNATE HYDRONIC HEAT HEATER 1 HEATER 2 DANGER HIGH MC L1 WH OPTIONAL POWER VENT DOOR TR 2 L1 WH OR 1 2 3 ON...

Страница 66: ...Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring DigiAIR MAKE UP SOLUTION KIT 1 2 3 ON OFF SWITCH S DB R TR 1 R TR 4 DB L1 OPTIONAL AIR DEHUMI...

Страница 67: ...giAIR MAKE UP SOLUTION KIT OPTIONAL LIGHTING CONTROL TR 1 To MC R 6 8 7 2 4 3 1 0 BL RD DB 14 S GY OPTIONAL TRANSFER FAN R 6 8 7 2 4 3 1 0 BL RD TR 1 To MC DB 14 S YL 14 Daughter Board Device Switch 1...

Страница 68: ...GH HIGH SPEED CM COMP DB EM FC F HPS HTR MC RCCF RVC TR TB VSM VSTM R OUTDOOR FAN MOTOR COMPRESSOR DAUGHTER BOARD EVAPORATOR MOTOR FAN CAPACITOR FUSE HIGH PRESSURE SWITCH HEATER ELEMENT MAIN CONTROL R...

Страница 69: ...RED OCT BLUE IHD ORANGE OAT GREEN IDT YELLOW REV VALVE FAN HIGH LOW OD FAN HIGH LOW LINE 2 COMPRESSOR L2 L1 MC 9 BK BK 7 OR RD TB EM FAN MOTOR CM FAN MOTOR TR 1 265 230 S ID OR 13 BK DANGER HIGH VOLT...

Страница 70: ...1170 MC OD FAN LOW HIGH L1 L2 10 10 ALTERNATE INDOOR MOTOR WIRING COM GND INPUT AC TO MOTOR VSTM ID R 485 S VSM EM EVAP MOTOR 1400 1250 1200 1000 L1 MC LOW HIGH ID FAN L2 11 11 REV VALVE LOW TYPE A W...

Страница 71: ...he most up to date wiring WARNING R YL GY BU BR RD GY TR 1 To MC BU RD PK ALTERNATE HYDRONIC HEAT HEATER 1 HEATER 2 DANGER HIGH MC L1 WH OPTIONAL POWER VENT DOOR TR 2 L1 WH OR 1 2 3 ON OFF SWITCH S L2...

Страница 72: ...RAM WARNING Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring 1 2 3 ON OFF SWITCH S DB R TR 1 R TR 4 DB L1 OPTIONAL FRESH AIR DEHUMIDIFICATION K...

Страница 73: ...to change Always refer to the wiring diagram on the unit for the most up to date wiring WARNING OPTIONAL LIGHTING CONTROL TR 1 To MC R 6 8 7 2 4 3 1 0 BL RD DB 14 S GY OPTIONAL TRANSFER FAN R 6 8 7 2...

Страница 74: ...124 1500 1350 PTH153 PTH154 1650 1500 PMH153 PMH154 1650 1500 PTC073 PTC074 1350 1170 PTC093 PTC094 1350 1170 PTC123 PTC124 1350 1170 PTC153 PTC154 1650 1500 Outdoor Motor Speed Selection Model Starts...