10
SPECIFICATIONS
HEAT PUMP - HEH
EER -
Energy Efficiency Ratio per The Air-
Conditioning, Heating, and Refrigeration
Institute (AHRI) Test Procedures and Canadian
Standards Association (CSA) Test Procedures.
COP -
Coefficient of Performance per AHRI Test
Procedures
HEH H SERIES
HEH073H
**AXXX
HEH093H
**AXXX
HEH123H
**AXXX
HEH074H
**AXXX
HEH094H
**AXXX
HEH124H
**AXXX
230 / 208
230 / 208
230 / 208
265
265
265
7,700/7,700
9,000 / 9,000
12,000 / 12,000
7,700
9,100
12,000
4.1 / 4.1
4.7 / 4.7
6.2 / 6.2
3.6
4.2
5.4
595 / 595
720 / 720
1,040 / 1,040
595
730
1,040
12.9 / 12.9
12.5/12.5
11.5/11.5
12.9
12.4
11.5
5.4
5.4
5.4
3.6
3.6
3.6
High
340
330
340
340
330
340
Low
245
245
245
245
245
245
High
370
360
370
370
360
370
Low
270
270
270
270
270
270
65*
65*
65*
65*
65*
65*
1.7
2.2
3.6
1.7
2.2
3.6
107
111
114
107
111
114
122
126
131
122
126
131
* Actual vent CFM performance will vary due to application and installation conditions.
Model ¹,
6
,
8
,
9
Voltage ¹, ³
Capacity (BTU/h)
Amps
10
Watts
10
EER
Net Weight (lbs.)
Ship Weight (lbs.)
Unit without Electric Heater
Min. Circuit Amps ²,
4
,
10
CFM (Cool/Wet Coil)
CFM (Dry Coil)
Ventilated Air, CFM (Fan Only)*
Dehumidification (Pints/Hr.)
Notes
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum Circuit Ampacity (MCA) ratings conform to the National Electric Code; however, local codes should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volts.
⁴
Overcurrent protection for all units without electric heaters is 15 amps.
Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses (included and factory-installed on all Amana® brand 265-volt chassis).
⁵
Heating capacity and efficiency based on unit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambient.
⁶
Specify two-digit heater kW size to complete model number.
⁷
R-410A refrigerant used in all systems.
⁸
All units meet or exceed ASHRAE 90.1 standards.
⁹
All units less than 250 volts have a Leak Current Detector Interrupter (LCDI) power cord and meet UL 484 standards.
¹
⁰
Refer to electric heat performance data for total MCA and recommended overcurrent protection. Amps and Watts notation refers to compressor only.